Plan Review Details - Permit 14040874
Plan Review Stops For Permit 14040874
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-06-24 Cont ID  
Sent By skennedy Date 2014-06-24 Time 09:09 Rev Time 0.00
Received By skennedy Date 2014-06-23 Time 09:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-06-04 Cont ID  
Sent By shill Date 2014-06-04 Time 09:29 Rev Time 0.00
Received By shill Date 2014-06-04 Time 09:29 Sent To  
Notes
2014-06-04 09:36:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. FBC 1609, ATTACHMENT TO INCLUDE THE FOLLOWING
 INFORMATION FOR FASTENERS: TYPE, DIAMETER, LENGTH OR
 MINIMUM EMBEDMENT, AND NUMBER REQUIRED.
  
 TO EXPEDITE PLAN REVIEW, IT WOULD BE PREFERABLE TO HAVE
 THIS INFORMATION SUBMITTED ON A NEW SHEET. IF THE
 SHEETS ALREADY REVIEWED AND PASSED BY ZONING AND
 ELECTRICAL ARE REVISED, THE NEW SHEETS WOULD REQUIRE A
 REVIEW BY THOSE TRADES. IF ALL STRUCTURAL INFORMATION
 IS SUBMITTED ON A NEW SHEET, THAT WILL BE REVIEWED BY
 BUILDING ONLY.
  
 2ND REVIEW:
  
 CHANGES NOT CLOUDED. HOWEVER, SEE ITEM 13. BOLTS ARE TO
 BE INSTALLED AT A MINIMUM OF 00" ACROSS TOP ONLY.
 PLEASE CLARIFY.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-05-08 Cont ID  
Sent By shill Date 2014-05-08 Time 16:17 Rev Time 0.00
Received By shill Date 2014-05-08 Time 16:17 Sent To  
Notes
2014-05-08 16:19:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 1609, ATTACHMENT TO INCLUDE THE FOLLOWING
 INFORMATION FOR FASTENERS: TYPE, DIAMETER, LENGTH OR
 MINIMUM EMBEDMENT, AND NUMBER REQUIRED.
  
 TO EXPEDITE PLAN REVIEW, IT WOULD BE PREFERABLE TO HAVE
 THIS INFORMATION SUBMITTED ON A NEW SHEET. IF THE
 SHEETS ALREADY REVIEWED AND PASSED BY ZONING AND
 ELECTRICAL ARE REVISED, THE NEW SHEETS WOULD REQUIRE A
 REVIEW BY THOSE TRADES. IF ALL STRUCTURAL INFORMATION
 IS SUBMITTED ON A NEW SHEET, THAT WILL BE REVIEWED BY
 BUILDING ONLY.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-07 Cont ID  
Sent By dhayes Date 2014-05-07 Time 09:00 Rev Time 0.00
Received By dhayes Date 2014-05-07 Time 09:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-04 Cont ID  
Sent By shill Date 2014-06-04 Time 09:47 Rev Time 0.00
Received By shill Date 2014-06-03 Time 08:01 Sent To  
Notes
2014-06-04 08:02:37SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-08 Cont ID  
Sent By shill Date 2014-05-08 Time 16:21 Rev Time 0.00
Received By shill Date 2014-04-24 Time 12:36 Sent To  
Notes
2014-04-24 12:37:02ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2014-04-28 Cont ID  
Sent By ajones Date 2014-04-28 Time 15:46 Rev Time 0.00
Received By ajones Date 2014-04-25 Time 10:50 Sent To E
Notes
2014-04-25 10:51:07GIVEN AV