Plan Review Details - Permit 14040711
Plan Review Stops For Permit 14040711 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2014-05-02 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-05-02 |
Time |
05:56 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-05-02 |
Time |
05:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-05-12 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-05-12 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-05-12 |
Time |
16:07 |
Sent To |
|
|
Notes |
2014-05-12 16:30:50 | ELECTRICAL PROVISO: | | | | 1) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY | | AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS | | THAT SERVING THE NORMAL LIGHTING IN THE AREA AND | | CONNECTED AHEAD OF ANY LOCAL SWITCHES. 2008 EDITION OF | | THE NEC ARTICLE 701.11(G) | | | | 2) OCCUPANCY SENSORS REQUIRED IN ACCORDANCE WITH | | FBC-ENERGY CODE SECTION 505.2.2 PROVIDE AUTOMATIC | | LIGHTING SHUTOFF. | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2014-04-22 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-04-22 |
Time |
15:37 |
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-04-22 |
Time |
15:05 |
Sent To |
E |
|
Notes |
2014-04-22 15:37:31 | THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL, | | WITH THE FOLLOWING COMMENT. | | | | ALL FIRE ALARM WORK SHALL BE PERMITTED THROUGH SEPARATE | | SHOP DRAWINGS. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-05-12 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-05-12 |
Time |
16:31 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-04-18 |
Time |
16:41 |
Sent To |
|
|
Notes |
2014-04-18 16:42:17 | INCOMING SENT TO B21 BOX. JW |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2014-05-02 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-05-02 |
Time |
05:56 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-05-02 |
Time |
05:36 |
Sent To |
|
|
Notes |
2014-05-02 06:02:12 | BUILDING APPROVED WITH EXCEPTION! | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | SHEET M2.1 THE NEW DUCTWORK DOES NOT INDICATE THE TYPE | | OR SIZE OF DUCT WORK, PLEASE COMPLY WITH : | | 2010 FBC-MECH 603.2 DUCT SIZING & 2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION, 2010 EDITION 107.3.5.1.4(6) DUCT SYSTEM | | SIZING. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2014-05-02 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-05-02 |
Time |
05:56 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-05-02 |
Time |
05:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2014-04-21 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2014-04-21 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2014-04-21 |
Time |
15:16 |
Sent To |
|
|
Notes |
|
|
|