Plan Review Details - Permit 14040711
Plan Review Stops For Permit 14040711
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-05-02 Cont ID  
Sent By jwitmer Date 2014-05-02 Time 05:56 Rev Time 0.00
Received By jwitmer Date 2014-05-02 Time 05:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-12 Cont ID  
Sent By dhayes Date 2014-05-12 Time 16:29 Rev Time 0.00
Received By dhayes Date 2014-05-12 Time 16:07 Sent To  
Notes
2014-05-12 16:30:50ELECTRICAL PROVISO:
  
 1) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY
 AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES. 2008 EDITION OF
 THE NEC ARTICLE 701.11(G)
  
 2) OCCUPANCY SENSORS REQUIRED IN ACCORDANCE WITH
 FBC-ENERGY CODE SECTION 505.2.2 PROVIDE AUTOMATIC
 LIGHTING SHUTOFF.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-22 Cont ID  
Sent By pleduc Date 2014-04-22 Time 15:37 Rev Time 0.00
Received By pleduc Date 2014-04-22 Time 15:05 Sent To E
Notes
2014-04-22 15:37:31THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMENT.
  
 ALL FIRE ALARM WORK SHALL BE PERMITTED THROUGH SEPARATE
 SHOP DRAWINGS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-12 Cont ID  
Sent By dhayes Date 2014-05-12 Time 16:31 Rev Time 0.00
Received By dhayes Date 2014-04-18 Time 16:41 Sent To  
Notes
2014-04-18 16:42:17INCOMING SENT TO B21 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-02 Cont ID  
Sent By jwitmer Date 2014-05-02 Time 05:56 Rev Time 0.00
Received By jwitmer Date 2014-05-02 Time 05:36 Sent To  
Notes
2014-05-02 06:02:12BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 SHEET M2.1 THE NEW DUCTWORK DOES NOT INDICATE THE TYPE
 OR SIZE OF DUCT WORK, PLEASE COMPLY WITH :
 2010 FBC-MECH 603.2 DUCT SIZING & 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 107.3.5.1.4(6) DUCT SYSTEM
 SIZING.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-05-02 Cont ID  
Sent By jwitmer Date 2014-05-02 Time 05:56 Rev Time 0.00
Received By jwitmer Date 2014-05-02 Time 05:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-04-21 Cont ID  
Sent By ajones Date 2014-04-21 Time 15:16 Rev Time 0.00
Received By ajones Date 2014-04-21 Time 15:16 Sent To  
Notes
***NONE***