Plan Review Details - Permit 14040710
Plan Review Stops For Permit 14040710
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-04-29 Cont ID  
Sent By jwitmer Date 2014-04-29 Time 08:07 Rev Time 0.00
Received By jwitmer Date 2014-04-29 Time 07:20 Sent To  
Notes
2014-04-29 07:48:54BUILDING / PLUMBING PROVISO:
 2010 FBC-EXISTING BUILDING CODE:
  
 LEVEL 1
 A HIGH/ LOW DRINKING FOUNTAIN IS REQUIRED.
  
 ACCESSIBILITY 605.1 GENERAL. ACCESSIBILITY SHALL BE IN
 ACCORDANCE WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY.
 2010 FL ACCESSIBILITY CODE:
 202.4 ALTERATIONS AFFECTING PRIMARY FUNCTION AREAS.
 IN ADDITION TO THE REQUIREMENTS OF 202.3, AN ALTERATION
 THAT AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS
 TO AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE
 SO AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE,
 THE PATH OF TRAVEL TO THE ALTERED AREA, INCLUDING THE
 REST ROOMS, TELEPHONES, AND DRINKING FOUNTAINS SERVING
 THE ALTERED AREA, ARE READILY ACCESSIBLE TO AND USABLE
 BY INDIVIDUALS WITH DISABILITIES, UNLESS SUCH
 ALTERATIONS ARE DISPROPORTIONATE TO THE OVERALL
 ALTERATIONS IN TERMS OF COST PURSUANT TO 202.4.1
 202.4.1 DISPROPORTIONATE COST. UP TO $9600.00 IN
 ACCESSIBILITY UPGRADES ARE REQUIRED IF NOT CODE
 COMPLIANT ALREADY. THE DRINKING FOUNTAIN WILL NEED TO
 COMPLY WITH:
  
 211 DRINKING FOUNTAINS
 211.1 GENERAL. WHERE DRINKING FOUNTAINS ARE PROVIDED ON
 AN EXTERIOR SITE, ON A FLOOR, OR WITHIN A SECURED AREA
 THEY SHALL BE PROVIDED IN ACCORDANCE WITH 211.
 EXCEPTION: IN DETENTION OR CORRECTIONAL FACILITIES,
 DRINKING FOUNTAINS ONLY SERVING HOLDING OR HOUSING
 CELLS NOT REQUIRED TO COMPLY WITH 232 SHALL NOT BE
 REQUIRED TO COMPLY WITH 211.
  
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES
 (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-05-12 Cont ID  
Sent By dhayes Date 2014-05-12 Time 15:24 Rev Time 0.00
Received By dhayes Date 2014-05-12 Time 15:24 Sent To  
Notes
2014-05-12 15:26:29ELECTRICAL PROVISO.
  
 1) DRINKING FOUNTAIN REQUIRED BY FL ACCESSABILITY CODE.
 SEE BUILDING AND PLUMBING COMMENTS.
  
 2) RECEPTACLES FOR WATER COOLERS SHALL BE GFI
 PROTECTED. SEE ARTICLE 422.52 OF THE 2008 EDITION OF
 THE NEC.
  
 3) OCCUPANCY SENSORS REQUIRED IN ACCORDANCE WITH FBC-EC
 505.2.2 PROVIDE AUTOMATIC LIGHTING SHUTOFF.
  
 DAVID A. HAYES, ELECTRICAL PLANS EXAMINER.
 [email protected] 561-508-6717
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-22 Cont ID  
Sent By pleduc Date 2014-04-22 Time 15:54 Rev Time 0.00
Received By pleduc Date 2014-04-22 Time 15:43 Sent To E
Notes
2014-04-22 15:53:58THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMENT.
  
 ALL FIRE ALARM WORK IS REQUIRED TO BE DONE UNDER
 SEPARATE SHOP DRAWINGS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-05-12 Cont ID  
Sent By dhayes Date 2014-05-12 Time 15:24 Rev Time 0.00
Received By dhayes Date 2014-04-18 Time 16:35 Sent To  
Notes
2014-04-18 16:37:40INCOMING SENT TO B-19 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-08 Cont ID  
Sent By hmoser Date 2014-05-08 Time 14:14 Rev Time 0.00
Received By hmoser Date 2014-05-08 Time 14:13 Sent To  
Notes
2014-05-08 14:15:09PLAN REVIEW BY J Z PX1328

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-04-29 Cont ID  
Sent By jwitmer Date 2014-04-29 Time 07:49 Rev Time 0.00
Received By jwitmer Date 2014-04-29 Time 07:49 Sent To  
Notes
2014-04-29 07:38:13PLUMBING PROVISO:
 2010 FBC-EXISTING BUILDING CODE:
  
 LEVEL 1
 A HIGH/ LOW DRINKING FOUNTAIN IS REQUIRED.
  
 ACCESSIBILITY 605.1 GENERAL. ACCESSIBILITY SHALL BE IN
 ACCORDANCE WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY.
 2010 FL ACCESSIBILITY CODE:
 202.4 ALTERATIONS AFFECTING PRIMARY FUNCTION AREAS.
 IN ADDITION TO THE REQUIREMENTS OF 202.3, AN ALTERATION
 THAT AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS
 TO AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE
 SO AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE,
 THE PATH OF TRAVEL TO THE ALTERED AREA, INCLUDING THE
 REST ROOMS, TELEPHONES, AND DRINKING FOUNTAINS SERVING
 THE ALTERED AREA, ARE READILY ACCESSIBLE TO AND USABLE
 BY INDIVIDUALS WITH DISABILITIES, UNLESS SUCH
 ALTERATIONS ARE DISPROPORTIONATE TO THE OVERALL
 ALTERATIONS IN TERMS OF COST PURSUANT TO 202.4.1
 202.4.1 DISPROPORTIONATE COST. UP TO $9600.00 IN
 ACCESSIBILITY UPGRADES ARE REQUIRED IF NOT CODE
 COMPLIANT ALREADY. THE DRINKING FOUNTAIN WILL NEED TO
 COMPLY WITH:
  
 211 DRINKING FOUNTAINS
 211.1 GENERAL. WHERE DRINKING FOUNTAINS ARE PROVIDED ON
 AN EXTERIOR SITE, ON A FLOOR, OR WITHIN A SECURED AREA
 THEY SHALL BE PROVIDED IN ACCORDANCE WITH 211.
 EXCEPTION: IN DETENTION OR CORRECTIONAL FACILITIES,
 DRINKING FOUNTAINS ONLY SERVING HOLDING OR HOUSING
 CELLS NOT REQUIRED TO COMPLY WITH 232 SHALL NOT BE
 REQUIRED TO COMPLY WITH 211.
  
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES
 (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-04-21 Cont ID  
Sent By ajones Date 2014-04-21 Time 15:15 Rev Time 0.00
Received By ajones Date 2014-04-21 Time 15:15 Sent To  
Notes
***NONE***