Plan Review Stops For Permit 14040651 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2014-05-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-05-03 |
Time |
07:41 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-05-03 |
Time |
06:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-04-21 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-04-21 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-04-21 |
Time |
10:47 |
Sent To |
|
|
Notes |
2014-04-21 11:21:25 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE SCOPE OF WORK FOR THIS PROJECT IS NOT CLEAR. | | PLEASE SPECIFY THE COMPLETE SCOPE OF WORK THAT IS TO BE | | DONE ON THE PLANS. CITY AMENDMENTS 107.2.1 | | | | 2) SUBMIT TWO SETS OF PLANS THAT SHOW THE AREA OF WORK | | IN ITS EXISTING CONDITION. CITY AMENDMENTS 107.2.1 | | | | 3) SHOW COMPLIANCE WITH FBC R314 FOR SMOKE ALARMS. | | | | 4) PROVIDE A DETAIL OF THE EXTERIOR OPENING AT THE | | SHOWER THAT IS TO BE ENCLOSED, PROVIDE STRUCTURAL | | INFORMATION, INSULATION, WATERPROOFING, EXTERIOR AND | | INTERIOR FINISHES. CITY AMENDMENTS 107.2.1.3 AND FBC | | R301.2.1 | | | | 5) THE PRINTED NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR THE DESIGN IS REQUIRED TO BE ON THE | | PLANS. CITY AMENDMENTS 107.2.1 | | | | 6) IN ORDER TO REDUCE YOUR REVIEW TIME, PLEASE PROVIDE | | A RESPONSE LETTER THAT INDICATES HOW EACH OF THE REVIEW | | COMMENTS HAS BEEN ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2014-05-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-05-03 |
Time |
07:59 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-05-03 |
Time |
06:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-04-21 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-04-21 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-04-21 |
Time |
12:24 |
Sent To |
|
|
Notes |
2014-04-21 14:14:22 | 2010 FBC / 2008 NEC | | | | DENIED BY ELECTRICAL | | | | 1) SHOW COMPLIANCE WITH FBC R314 FOR SMOKE ALARMS. | | | | 2) SHOW COMPLIANCE WITH NEC 210.11 (C) (3) WHICH | | REQUIRES AT LEAST ONE 20 AMP BRANCH CIRCUIT TO SUPPLY | | BATHROOM RECEPTACLE OUTLETS. | | | | 3) SHOW COMPLIANCE WITH NEC 406.11 FOR TAMPER RESISTANT | | RECETACLES. | | | | 4) SHOW COMPLIANCE WITH NEC 210.12 (B) FOR AFCI | | PROTECTION. | | | | 5) THE PRINTED NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR THE DESIGN IS REQUIRED TO BE ON THE | | PLANS. CITY AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2014-05-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-05-07 |
Time |
08:12 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-05-06 |
Time |
09:27 |
Sent To |
|
|
Notes |
2014-05-06 09:29:06 | SENT TO R MCDOUGAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-05-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-05-03 |
Time |
07:59 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-04-30 |
Time |
06:42 |
Sent To |
|
|
Notes |
2014-05-01 06:44:23 | INCOMING TO R. MCDOUGALS DESK . JW |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-04-21 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-04-21 |
Time |
13:34 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-04-17 |
Time |
10:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2014-05-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-05-07 |
Time |
08:01 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-05-07 |
Time |
07:28 |
Sent To |
|
|
Notes |
2014-05-07 08:12:52 | PASSED WITH EXCEPTION. AN ACCESS DOOR TO THE AIR | | HANDLER CLOSET WILL BE INSTALLED IN THE HALLWAY PER | | LETTER FROM THE CONTRACTOR. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2014-05-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-05-03 |
Time |
06:59 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-05-03 |
Time |
06:39 |
Sent To |
|
|
Notes |
2014-05-03 07:18:40 | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) ITEM #3 FROM FIRST REVIEW. THE LOCATION OF THE WATER | | CLOSET SPECIFIED ON THE PLANS APPEARS TO PREVENT THE | | REQUIRED ACCESS TO THE A/C EQUIPMENT FOR INSPECTION, | | SERVICE, REPAIR AND REPLACEMENT. SEE FBCR M1305.1 | | REMOVING THE WATER CLOSET TO PROVIDE ACCESS TO THE A/C | | EQUIPMENT IS NOT AN OPTION THAT WOULD COMPLY WITH THE | | BUILDING CODE REQUIREMENTS. ONE OPTION WOULD BE TO | | INSTALL AN ACCESS DOOR ON THE OTHER SIDE OF THE CLOSET | | THAT WOULD OPEN INTO THE HALLWAY. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2014-04-21 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-04-21 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-04-21 |
Time |
11:27 |
Sent To |
|
|
Notes |
2014-04-21 11:41:01 | 2010 FBC | | | | DENIED BY MECHANICAL | | | | 1) THE SCOPE OF WORK FOR THIS PROJECT IS NOT CLEAR. | | PLEASE SPECIFY THE COMPLETE SCOPE OF WORK THAT IS TO BE | | DONE ON THE PLANS. CITY AMENDMENTS 107.2.1 | | | | 2) THE NEW EXHAUST FANS ARE REQUIRED TO BE EXHAUSTED | | DIRECTLY TO THE OUTDOORS. FBCR M1507.2 | | | | 3) THE LOCATION OF THE WATER CLOSET SPECIFIED ON THE | | PLANS APPEARS TO PREVENT THE REQUIRED ACCESS TO THE A/C | | EQUIPMENT FOR INSPECTION, SERVICE, REPAIR AND | | REPLACEMENT. SEE FBCR M1305.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2014-05-07 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-05-07 |
Time |
08:01 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-05-07 |
Time |
07:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2014-05-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-05-03 |
Time |
06:42 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-05-03 |
Time |
06:39 |
Sent To |
|
|
Notes |
2014-05-03 06:51:23 | 2010 FBC | | | | DENIED BY PLUMBING | | | | 1) THE BATHROOM IS NOT PROPERLY VENTED. FBCR P3108.2.1 | | NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN SHALL | | DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN | | CONNECTION. | | | | 2) THE NAME, SIGNATURE AND LICENSE NUMBER OF THE PERSON | | RESPONSIBLE FOR THE PLUMBING DESIGN IS REQUIRED ON THE | | PLUMBING PLANS. CITY AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2014-04-21 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-04-21 |
Time |
11:41 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-04-21 |
Time |
11:22 |
Sent To |
|
|
Notes |
2014-04-21 11:27:19 | 2010 FBC | | | | DENIED BY PLUMBING | | | | 1) THE SCOPE OF WORK FOR THIS PROJECT IS NOT CLEAR. | | PLEASE SPECIFY THE COMPLETE SCOPE OF PLUMBING WORK THAT | | IS TO BE DONE ON THE PLANS. CITY AMENDMENTS 107.2.1 | | | | 2) SUBMIT TWO SETS OF A PLUMBING RISER DIAGRAM. CITY | | AMENDMENTS 107.3.5.3 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|