Plan Review Details - Permit 14040650
Plan Review Stops For Permit 14040650
Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time 17:13 Rev Time 0.00
Received By dhayes Date   Time 17:13 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-04-22 Cont ID  
Sent By dhayes Date 2014-04-22 Time 11:46 Rev Time 0.00
Received By dhayes Date 2014-04-22 Time 10:54 Sent To  
Notes
2014-04-22 11:45:41NEC
 TABLE 310.15(B)(6) CONDUCTOR TYPES AND SIZES FOR
 120/240-VOLT, 3-WIRE, SINGLE-PHASE DWELLING SERVICES
 AND FEEDERS.
 THE PLAN SUBMITTED INDICATES A 1/0? IN 2" C. PLEASE
 INDICATE THE APPROPRIATE SIZE OF WIRE TO FEED A 200AMP
 MAIN INCLUDING THE MATERIAL (ALUMINUM OR COPPER) AND
 THE INSULLATION TYPE.
  
 210.70 LIGHTING OUTLETS REQUIRED. LIGHTING OUTLETS
 SHALL BE INSTALLED WHERE SPECIFIED IN 210.70(A), (B),
 AND (C).
 PLEASE PROVIDE ADDITIONAL LIGHTING OUTLETS PER 210.70
 OR INDICATE ON THE PLANS THAT THE PROJECT IS ALREADY IN
 COMPLIANCE.
  
 FBC 107.2.1 "CONSTRUCTION DOCUMENTS SHOULD BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF WORK PROPOSED. "
 THE PLAN'S RISER SUBMITTED INDICATES A DISC.? JUST TO
 THE LEFT OF THE METER. PLEASE INDICATE WHAT THIS IS,
 HOW IT IS FED, AND WHAT IT FEEDS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By dhayes Date   Time 17:13 Rev Time 0.00
Received By dhayes Date 2014-04-29 Time 17:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2014-04-22 Cont ID  
Sent By dhayes Date 2014-04-22 Time 11:46 Rev Time 0.00
Received By dhayes Date 2014-04-17 Time 07:29 Sent To  
Notes
2014-04-22 11:47:54CONTACTED CONTRACTOR. ROUTED TO DENIED DRAWER UNDER
 SAMLL "B"
2014-04-21 07:30:33SENT TO ELECTRIC UNDER $5000 BOX