2014-04-18 07:01:24 | BUILDING PLAN REVIEW |
| PERMIT: 14040379 |
| ADD: 2101 OKEECHOBEE BLVD |
| CONT: HEDRICK BROTHERS RENE YERNANDEZ CELL 561-568-4182 |
| TEL: (561)689-8880 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: FRIDAY/ APRIL 18/ 2014 |
| ACTION: DENIED |
| |
| NOTE SOILS REPORTS WERE SUBMITTED UNDE RTHE FOUNDATION |
| PERMIT, SOILS REPORT BY TIERRA SOURH FLORIDA |
| REPORT # 7111-13-202 |
| PREPARED BY TIERRA SOUTH FLORIDA, INC |
| DATED AUGUST 16, 2013 |
| THIS REPORT SHALL BE CONSIDERED PART OF THE CONTRACT |
| DOCUMENTS FOUNDATION-DESIGN IS BASED ONA A SOIL BEARING |
| PRESSURE OF 3000 PSF. |
| |
| 1) THE PLANS INDICATE THIS PROJECT BE TILT WALL |
| REQUIRING A RESIDENT INSPECTOR. THREE (3) SETS OF ALL |
| PLANS AND SUBMITTALS. 2010 WEST PALM BEACH AMENDMENTS |
| TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, 2010 EDITION 110.3.9 OTHER INSPECTIONS |
| SERVICES. THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO |
| BE MADE BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION |
| 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF |
| RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| STRENGTH (F ?C) IN EXCESS OF 3000 |
| POUNDS PER SQUARE INCH |
| 4. FOR PILE DRIVING |
| 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| FOOT |
| 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| METHODS OF CONSTRUCTION (TILT WALL) |
| |
| 1A) SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT |
| TIMES WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF |
| THE BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| THE RESIDENT INSPECTOR. AT THE COMPLETION OF THE |
| CONSTRUCTION WORK OR PROJECT, SUCH INSPECTORS SHALL |
| SUBMIT A CERTIFICATE OF COMPLIANCE TO THE BUILDING |
| OFFICIAL, STATING THAT THE WORK WAS DONE IN COMPLIANCE |
| WITH THIS CODE AND IN ACCORDANCE WITH THE PERMITTED |
| DRAWING. FINAL INSPECTION SHALL BE MADE BY THE BUILDING |
| OFFICIAL BEFORE A CERTIFICATE OF OCCUPANCY OR |
| CERTIFICATE OF COMPLETION IS ISSUED; AND CONFIRMATION |
| INSPECTIONS MAY BE MADE AT ANY TIME TO MONITOR |
| ACTIVITIES AND RESIDENT INSPECTORS. |
| |
| 1B) ONLY (2) SETS OF PLANS WERE SUBMITTED, (3) ARE |
| REQUIRED FOR RESIDENT INSPECTOR PROGRAMS. 2010 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, ADMINISTRATION, 2010 EDITION 110.3.9 |
| |
| 2) NEITHER SHEET A101 BUILDING DATA HEADING NOR LIFE |
| SAFETY SHEET A-001 NOR A-002 LIFE SAFETY SHEETS |
| INDICATE THE MINIMUM CRITERIA FOR PLAN REVIEW: |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 110.3.9 |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS |
| :107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| 2A) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE 503). |
| 2B) OCCUPANCY GROUPS IF SEPERATED OR NON SEPERATED |
| FBC-B 508.3 VERSES 508.4. |
| 2C) IF FIRE SPRINKLERED OR NOT TABLE 503 |
| 2B) WHAT AREA INCREASES WERE TAKEN 506.2 (FRONTAGE) AND |
| OR 506.3 (FIRE SPRINKLER) |
| 2E) FOR EACH OCCUPANCY TYPE/ OCCUPANCY LOAD TABLE |
| 1004.1.1. |
| 2F) PLUMBING FIXTURE COUNT OF EACH OCCUPANCY TYPE AND |
| OCCUPANCY LOAD FBC-P TABLE 403.1. |
| 2G) FLOOR LOADING OF MEZZANINE FBC-B TABLE 1607.1 (36) |
| LIGHT 125 LBS. OR HEAVY 250 LBS. |
| |
| 3) SHEET A-001 THE MAIN BUILDING SHOWROOMS A BUSINESS |
| OCCUPANCY SHOWS A CONFERANCE ROOM WITH 2 EXIT DOORS. |
| ADJACENT TO THIS AREA IS A EXIT ACCESS CORRIDOR AND |
| DOOR OPENING # 1-129B (SEE SHEET A-113) THIS DOOR |
| SWINGS INTO THE COORIDOR, THE OCCUPANT LOAD IS GREATER |
| THAN 50 AND SHOULD BE A OUTSWING DOOR. 2010 FBC-B |
| 1008.1.2. |
| |
| 4) SHEET A-001 & A-113 NEITHER OF THESE SHEETS ACTUALLY |
| STATE THE OCCUPANCY FOR THE SERVICE DRIVE, IT WOULD |
| APPEAR THIS AREA WOULD BE DECLARED EITHER A AUTO |
| STORAGE, A UTILITY OCCUPANCY CAN ONLY BE FOR PRIVATE |
| RESIDENTIAL GARGES MEETING THE DEFINITION. WITH THE S-2 |
| STORAGE REQUIREMENT, THE DOOR # 1-129B WILL BE LEADING |
| INTO A MORE HAZARDOUS OCCUPANCY. |
| |
| 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES. |
| EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH |
| THIS SECTION. 1.EGRESS FROM A ROOM OR SPACE SHALL NOT |
| PASS THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS, |
| EXCEPT WHERE SUCH ADJOINING ROOMS OR AREAS AND THE AREA |
| SERVED ARE ACCESSORY TO ONE OR THE OTHER, ARE NOT A |
| GROUP H OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF |
| EGRESS TRAVEL TO AN EXIT. |
| EXCEPTION: MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| ADJOINING OR INTERVENING ROOMS OR SPACES IN A GROUP H, |
| S OR F OCCUPANCY WHEN THE ADJOINING OR INTERVENING |
| ROOMS OR SPACES ARE THE SAME OR A LESSER HAZARD |
| OCCUPANCY GROUP. |
| |
| 5A) SHEET A-001 & A-113 NEITHER OF THSES SHEETS |
| INDICATE OCCUPANCY SEPERATION WALLS INCOMPLIANCE WITH |
| 2010 FBC-B TABLE 508.4 FOR B & S2 PARKING GARAGES |
| (SERVICE DRIVE) SEE 3.11.3 S-2 PARKING GARAGES, |
| REQUIRING A 1 HOUR SEPERATION. |
| 707.3.8 SEPARATED OCCUPANCIES. |
| WHERE THE PROVISIONS OF SECTION 508.4 ARE APPLICABLE, |
| THE FIRE BARRIER SEPARATING MIXED OCCUPANCIES SHALL |
| HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN THAT |
| INDICATED IN TABLE 508.4 BASED ON THE OCCUPANCIES BEING |
| SEPARATED. |
| |
| 5B) 406.6.1 GENERAL. |
| REPAIR GARAGES SHALL BE CONSTRUCTED IN ACCORDANCE WITH |
| THE FLORIDA FIRE PREVENTION CODE AND SECTIONS 406.6.1 |
| THROUGH 406.6.6. THIS OCCUPANCY SHALL NOT INCLUDE MOTOR |
| FUEL-DISPENSING FACILITIES, AS REGULATED IN SECTION |
| 406.5. |
| |
| |
| 6A) SHEET A-001 & A-113 THE OCCUPANCY SEPARATION |
| BETWEEN THE SERVICE DRIVE (PARKING GARAGE) S-2 AND THE |
| AUTOMOBILE REPAIR GARAGE (F-1) IS MISSING SEE THE |
| OPENING PROTECTIVES FOUND UNDER 2010FBC-B T 715.4 UNDER |
| THE HEADING OTHER FIRE BARRIERS. 3/4 HOUR FIRE BARRIER. |
| FBC-B TABLE 508.4. REQUIRES A 1 HOUR FIRE SEPERATION |
| FOR SPRINKLERED BUILDINGS. 406.6.1 GENERAL. REPAIR |
| GARAGES SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE |
| FLORIDA FIRE PREVENTION CODE AND SECTIONS 406.6.1 |
| THROUGH 406.6.6. THIS OCCUPANCY SHALL NOT INCLUDE MOTOR |
| FUEL-DISPENSING FACILITIES, AS REGULATED IN SECTION |
| 406.5. 2010 FL FIRE PREVENTION CODE TABLE |
| 6.1.1.4.4.1(B) ALSO 1 HOUR FIRE SEPARATION, REPAIR |
| GARAGES ARE CLASSIFIED AS SPECIAL PURPOSE INDUSTRIAL |
| GARAGES. |
| |
| 6B) SHEET A-001 & A-113 THE OCCUPANCY SEPARATION |
| BETWEEN THE SERVICE DRIVE (PARKING GARAGE) S-2 AND THE |
| AUTOMOBILE REPAIR GARAGE (F-1) IS MISSING SEE THE |
| OPENING PROTECTIVES FOUND UNDER 2010FBC-B T 715.4 UNDER |
| THE HEADING OTHER FIRE BARRIERS. 3/4 HOUR FIRE BARRIER. |
| |
| 7) MEZZANINE SHEETS A-001, A-111, A-114, A-122 & A-124 |
| ALL THESE SHEETS INDICATE A MEZZANINE. SEE DEFITION OF |
| MEZZANINE AREA LIMITATIONS. 505.2 AREA LIMITATION. |
| THE AGGREGATE AREA OF A MEZZANINE OR MEZZANINES WITHIN |
| A ROOM SHALL NOT EXCEED ONE-THIRD OF THE FLOOR AREA OF |
| THAT ROOM OR SPACE IN WHICH THEY ARE LOCATED. THE |
| ENCLOSED PORTION OF A ROOM SHALL NOT BE INCLUDED IN A |
| DETERMINATION OF THE FLOOR AREA OF THE ROOM IN WHICH |
| THE MEZZANINE IS LOCATED. IN DETERMINING THE ALLOWABLE |
| MEZZANINE AREA, THE AREA OF THE MEZZANINE SHALL NOT BE |
| INCLUDED IN THE FLOOR AREA OF THE ROOM. |
| EXCEPTIONS: |
| 1. THE AGGREGATE AREA OF MEZZANINES IN BUILDINGS AND |
| STRUCTURES OF TYPE I OR II CONSTRUCTION FOR SPECIAL |
| INDUSTRIAL OCCUPANCIES IN ACCORDANCE WITH SECTION 306.4 |
| SHALL NOT EXCEED TWO-THIRDS OF THE FLOOR AREA OF THE |
| ROOM. |
| |
| PLEASE PROVIDE THE AREA OF THE PART STORAGE AREA AND |
| THE AREA TO BE OPEN AREA 31,32,AND 33 TO SEE IF |
| EXCEPTION 1 WILL QUALIFY THIS AREA AS A MEZZANINE. THE |
| OTHER ISSUE THAT WILL BE IMPORTANT TO KNOW IS WHAT |
| MATERIAL THE FLOOR WILL BE MADE OF, THE PLANS ONLY |
| STATE STEEL MEZZANINE BY SPECIALITY ENGINEER, IS THIS A |
| SOLID FLOOR OR GRATING TYPE FLOORING? |
| |
| 8) SHEET -114 STAIR # 3 DOES NOT INDICATE WALL TYPE |
| MISSING WALL TAG IDENTIFICATION. 2010 FBC-B 1022.1. |
| |
| 9) PLEASE INDICATE COMPLIANCE WITH 2010 FBC-B 406.6.3 |
| VENTILATION FOR THE REPAIR GARAGE AND FOR THE CAR |
| DETAIL AREA. |
| |
| 10A) SHEET A119 DETAIL 2 & 3 BOTH INDICATE ROOF DRAINS |
| WITHIN THE STAIRWELLS. SHEET A314 & A315 BOTH DETAIL 3 |
| INDICATE THE ROOF DRAIN WITHIN THE STAIRWELL AS WELL AS |
| P2.12 SANITARY VENT, PLEASE REVIEW 2010 FBC-B 1022.4 |
| PENETRATIONS. PENETRATIONS INTO AND OPENINGS THROUGH AN |
| EXIT ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| VENTILATION OR PRESSURIZATION, SPRINKLER PIPING, |
| STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT |
| COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING |
| THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT |
| EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH |
| SECTION 713. THERE SHALL BE NO PENETRATIONS OR |
| COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT, |
| BETWEEN ADJACENT EXIT ENCLOSURES. |
| |
| 10B) THE STAIRWELL DIAGRAMS DO NOT SHOW A HANDRAIL ON |
| BOTH SIDES OF THE STAIRWELL. 2010 FBC-B TAIRWAYS SHALL |
| HAVE HANDRAILS ON EACH SIDE AND SHALL COMPLY WITH |
| SECTION 1012. |
| |
| 11) SHEET A201, A202 & A203 SHOW CURTAIN WALL TYPE |
| CONSTRUCTION, NO PRODUCT APPROVALS WERE SUBMITTED FOR |
| THIS GLAZING SYSTEM. 2010 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(C) CURTAIN WALLS |
| |
| 12) SHEET A201, A202 & A508 ALL SHOW ACM PANELS SHOW |
| COMPLIANCE WITH 2010 FBC-B: |
| 1407.1.1 PLASTIC CORE. |
| THE PLASTIC CORE OF THE MCM SHALL NOT CONTAIN FOAM |
| PLASTIC INSULATION AS DEFINED IN SECTION 2602.1. |
| |
| 12A) 1407.2 EXTERIOR WALL FINISH. MCM USED AS EXTERIOR |
| WALL FINISH OR AS ELEMENTS OF BALCONIES AND SIMILAR |
| PROJECTIONS AND BAY AND ORIEL WINDOWS TO PROVIDE |
| CLADDING OR WEATHER RESISTANCE SHALL COMPLY WITH |
| SECTIONS 1407.4 THROUGH 1407.14. |
| |
| 12B) 1407.3 ARCHITECTURAL TRIM AND EMBELLISHMENTS. MCM |
| USED AS ARCHITECTURAL TRIM OR EMBELLISHMENTS SHALL |
| COMPLY WITH SECTIONS 1407.7 THROUGH 1407.14. |
| |
| 12C) 1407.4 STRUCTURAL DESIGN. MCM SYSTEMS SHALL BE |
| DESIGNED AND CONSTRUCTED TO RESIST WIND LOADS AS |
| REQUIRED BY CHAPTER 16 FOR COMPONENTS AND CLADDING. |
| |
| 12D) 1407.5 APPROVAL. RESULTS OF APPROVED TESTS OR AN |
| ENGINEERING ANALYSIS SHALL BE SUBMITTED TO THE BUILDING |
| OFFICIAL TO VERIFY COMPLIANCE WITH THE REQUIREMENTS OF |
| CHAPTER 16 FOR WIND LOADS. FLORIDA DEPARTMENT OF |
| COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: (31)(C) PANEL WALLS |
| |
| 12E) 1407.6 WEATHER RESISTANCE.MCM SYSTEMS SHALL COMPLY |
| WITH SECTION 1403 AND SHALL BE DESIGNED AND CONSTRUCTED |
| TO RESIST WIND AND RAIN IN ACCORDANCE WITH THIS SECTION |
| AND THE MANUFACTURER?S INSTALLATION INSTRUCTIONS. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:(31)(C) |
| PANEL WALLS |
| |
| 12F) 1407.7 DURABILITY. MCM SYSTEMS SHALL BE |
| CONSTRUCTED OF APPROVED MATERIALS THAT MAINTAIN THE |
| PERFORMANCE CHARACTERISTICS REQUIRED IN SECTION 1407 |
| FOR THE DURATION OF USE. |
| |
| 12G) 1407.8 FIRE-RESISTANCE RATING. WHERE MCM SYSTEMS |
| ARE USED ON EXTERIOR WALLS REQUIRED TO HAVE A |
| FIRE-RESISTANCE RATING IN ACCORDANCE WITH SECTION 705, |
| EVIDENCE SHALL BE SUBMITTED TO THE BUILDING OFFICIAL |
| THAT THE REQUIRED FIRE-RESISTANCE RATING IS MAINTAINED. |
| EXCEPTION: MCM SYSTEMS NOT CONTAINING FOAM PLASTIC |
| INSULATION, WHICH ARE INSTALLED ON THE OUTER SURFACE OF |
| A FIRE-RESISTANCE-RATED EXTERIOR WALL IN A MANNER SUCH |
| THAT THE ATTACHMENTS DO NOT PENETRATE THROUGH THE |
| ENTIRE EXTERIOR WALL ASSEMBLY, SHALL NOT BE REQUIRED TO |
| COMPLY WITH THIS SECTION. |
| |
| 12H) 1407.9 SURFACE-BURNING CHARACTERISTICS. UNLESS |
| OTHERWISE SPECIFIED, MCM SHALL HAVE A FLAME SPREAD |
| INDEX OF 75 OR LESS AND A SMOKE-DEVELOPED INDEX OF 450 |
| OR LESS WHEN TESTED IN THE MAXIMUM THICKNESS INTENDED |
| FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 12I) 1407.10 TYPE I, II, III AND IV CONSTRUCTION. WHERE |
| INSTALLED ON BUILDINGS OF TYPE I, II, III AND IV |
| CONSTRUCTION, MCM SYSTEMS SHALL COMPLY WITH SECTIONS |
| 1407.10.1 THROUGH 1407.10.4, OR SECTION 1407.11. |
| |
| 12J) 1407.10.1 SURFACE-BURNING CHARACTERISTICS. MCM |
| SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND |
| A SMOKE DEVELOPED INDEX OF NOT MORE THAN 450 WHEN |
| TESTED AS AN ASSEMBLY IN THE MAXIMUM THICKNESS INTENDED |
| FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 13) SHEETS A201, A202 & A203 ALL SHOW THE USE OF A RAIN |
| SCEEN WALL AS WELL AS A508 PLEASE PROVIDE |
| MANUFACTURERES SPECIFICATIONS FOR THIS SYSTEM, |
| MATERIAL,HOW ITWILL BE FASTENED TO THE TILT UP PANELS |
| AND TESTING FOR WIND DESIGN POSITIVE AND NEGATIVE |
| PRESSURES. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: (31)(D) SYSTEMS & PRODUCTS INTRODUCED AS A |
| RESULT FROM NEW TECHNOLOGY. |
| |
| 14A) SHEET A118 & A315 BOTH INDICATE PER-ENGINEEERED |
| A/C STANDS PLEASE SHOW COMPLIANCE WITH: FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| THAT WILL REQUIRE PRODUCT APPROVALS: (31)(G) |
| PRE-ENGINEERED A/C STANDS. |
| |
| 14B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 15A) SHEET S-2.3 NOTES FOR PRECAST JOIST ROOF NOTES |
| INDICATES THE STEEL AND THICKNESS OF THE ROOF DECK, THE |
| ROOF DECK IS THE ROOF FOR THE AUTO REPAIR GARAGE BELOW, |
| PLEASE PROVIDE COMPLIANCE WITH 2010FBC-B 1503.1 |
| GENERAL. ROOF DECKS SHALL BE COVERED WITH APPROVED ROOF |
| COVERINGS SECURED TO THE BUILDING OR STRUCTURE IN |
| ACCORDANCE WITH THE PROVISIONS OF THIS CHAPTER. ROOF |
| COVERINGS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE |
| WITH THIS CODE AND THE APPROVED MANUFACTURER?S |
| INSTRUCTIONS SUCH THAT THE ROOF COVERING SHALL SERVE TO |
| PROTECT THE BUILDING OR STRUCTURE. |
| |
| SHEET A-118.1 NOTE 121 INDICATES TTHE USE OF VULKEM 350 |
| NF BY TREMCO. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: (31)(D) ROOFING PRODUCTS AND ASSEMBLIES. |
| |
| 15B) FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE |
| FOR SUPERVISING AND REVIEWING ALL PROJECT DATA, |
| REPORTS, SHOP DRAWINGS ETC.. 2010 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| CLADDING |
| |
| 16) SHEET A105 THE VACUUM BUILDING DOES NOT INDICATED |
| TO BE A OPEN OR PARTIALLY OPEN DESIGN, SHEET S5.1 DOES |
| NOT PROVIDE THE WIND DESIGN CRITERIA FOR THIS BUILDING |
| OR PRESSURES. |
| 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| 1609.3 WIND SPEED CONVERSION |
| 16.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| 16.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| 16.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| 16.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| 16.5) COMPONENTS & CLADDING PRESSURES POSITVE & |
| NEGATIVE TABLE 1609.2(2) . |
| |
| NO PRODUCT INFORMATION IS PROVIDED FOR THIS BUILDING |
| |
| 17) SHEET A107 CAR WASH HAS A DIFFERENT ROOF HEIGHT |
| THAN THE MAIN BUILDING AND WILL NEED A PRESSURE CHART |
| SIMILAR TO THAT ON SHEET S-5.1 FOR THIS MEAN ROOF |
| HEIGHT. |
| |
| 18) THIS SAME SHEET SHOW 2 FUEL TANKS BUT THERE IS NO |
| INFORMATION FOR THE TANKS SINGLE WALL OR DOUBLE WALL, |
| TYPE OF MATERIALS LEAK SENSORS. THE TANKS THEMSELVES |
| |
| 19) IMPACT FEES WERE NOT PAID ON FOUNDATION PERMIT, |
| OWNER/ DEVELOPER HAD REQUESTED P B C IMPACT FEES TO BE |
| PAID ON THE BUILDING PERMIT. MR SWOOPE & BO ROBERT |
| BROWN BOTH AGREED THE BUILDING PERMIT SET OF PLANS TO |
| BE REVIEWED BY P B COUNTY IMPACT FEE OFFICE FOR |
| ASSESSMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED. |
| |
| BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 20): WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |