2014-04-10 12:12:13 | FUEL GAS/ PLUMBING PLAN REVIEW |
| PERMIT: 14040343 |
| ADD: 2510 BROADWAY |
| CONT: BERERON PLUMBING |
| TEL: (561)445-2115 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURSDAY APRIL 10/2014 |
| ACTION: DENIED |
| |
| 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 105.1 |
| REQUIRED. ANY CONTRACTOR, OWNER, OR AGENT AUTHORIZED IN |
| ACCORDANCE WITH FLORIDA STATUTE 489 WHO INTENDS TO |
| CONSTRUCT, ENLARGE, ALTER, REPAIR, MOVE, DEMOLISH, OR |
| CHANGE THE OCCUPANCY OF A BUILDING OR STRUCTURE, OR TO |
| ERECT, INSTALL, ENLARGE, ALTER, REPAIR, REMOVE, CONVERT |
| OR REPLACE ANY IMPACTRESISTANT COVERINGS, ELECTRICAL, |
| GAS, MECHANICAL, PLUMBING OR FIRE PROTECTION SYSTEM, OR |
| ACCESSIBLE OR FLOOD RESISTANT SITE ELEMENT, THE |
| INSTALLATION OF WHICH IS REGULATED BY THIS CODE, OR TO |
| CAUSE ANY SUCH WORK TO BE DONE, SHALL FIRST MAKE |
| APPLICATION TO THE BUILDING OFFICIAL AND OBTAIN THE |
| REQUIRED PERMIT. |
| |
| 1A) WITH THE NEW GAS APPLIANCES BEING INTRODUCED INTO |
| THIS DELI A GREASE INTERCEPTOR PERMIT WILL BE REQUIRED, |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 107.3.5.1.3(11). |
| |
| 1B) THE PLANS SUBMITTED FOR THE NEW GAS APPLIANCES |
| LOCATION ALSO SHOWS A NEW LOCATION FOR THE REQUIRED |
| HAND SINK THAT WAS INSTALLED UNDER THE MASTER PERMIT |
| 10080639 (PLANS) PLUMBING SUB-PERMIT 11060592. PERMIT |
| IS REQUIRED FOR THE NEW LOCATION OF HAND SINK AND ANY |
| OTHER PLUMBING THAT HAS BEEN MOVED. 2010 WEST PALM |
| BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATION, 107.3.5.1.3 PLUMBING (4) SANITARY, |
| (6) VENTS & (1) MINIMUM PLUMBING FIXTURES . |
| |
| 1C) THIS TENNANCY AND USE OF THIS PORTION OF THE |
| BUILDING WILL REQUIRE A SERVICE SINK FOR THE REMOVAL OF |
| GREASY WASTE FROM ON THE FLOOR. 2010 FBC-P 403.1.3.1(2) |
| & TABLE 403.1(1)A-2. |
| |
| 2) GAS PERIMT MISSING PLAN REVIEW CRITERIA: |
| 107.3.5.1.5 |
| |
| 2.1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| FBC-2010 FUEL GAS. PLANS INDICATE THE USE OF A 2 LB |
| REGULATOR BUT THE TABLE LISTED 402.4(2) IS FOR A 1/2 LB |
| SYSTEM/ DISCREPANCY |
| |
| 2.2. COMPLIED. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, AND THE EDH NUMBER OF |
| CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE IF |
| BEING USED. |
| |
| 2.3.COMPLIED. TYPE OF GAS, (LP OR NATURAL). |
| |
| 2.4.CLEAR UP DISCRENCY . BTU LOAD OF EACH APPLIANCE AND |
| THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2010 |
| FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1) |
| THRU 402.4(35) |
| |
| 2.5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? |
| USE OF CAPACITY SECTION A.3.1(4) |
| |
| 2.6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| FBC-2010 FUEL GAS CODE SEC. 304 |
| |
| 2.7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 |
| FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 |
| PSI. |
| |
| 2.8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| AND TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS |
| CODE SEC. 502 THRU 505. |
| |
| 2.9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2010 FUEL GAS SEC. 402.2 |
| |
| 3) LOW VALUE OF PROJECT. W P B ADMINISTRTIVE CODE 108.2 |
| SCHEDULE OF PERMIT FEES. ON BUILDINGS, STRUCTURES, |
| ELECTRICAL, GAS, MECHANICAL, AND PLUMBING SYSTEMS OR |
| ALTERATIONS REQUIRING A PERMIT, A FEE FOR EACH PERMIT |
| SHALL BE PAID AS REQUIRED, IN ACCORDANCE WITH THE |
| SCHEDULE ESTABLISHED BY THE APPLICABLE GOVERNING |
| AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |