Plan Review Details - Permit 14040343
Plan Review Stops For Permit 14040343
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-05-21 Cont ID  
Sent By jwitmer Date 2014-05-21 Time 17:55 Rev Time 0.00
Received By jwitmer Date 2014-05-21 Time 17:55 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-04-10 Cont ID  
Sent By jwitmer Date 2014-04-10 Time 13:04 Rev Time 0.00
Received By jwitmer Date 2014-04-10 Time 07:05 Sent To  
Notes
2014-04-10 12:12:13FUEL GAS/ PLUMBING PLAN REVIEW
 PERMIT: 14040343
 ADD: 2510 BROADWAY
 CONT: BERERON PLUMBING
 TEL: (561)445-2115
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY APRIL 10/2014
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 105.1
 REQUIRED. ANY CONTRACTOR, OWNER, OR AGENT AUTHORIZED IN
 ACCORDANCE WITH FLORIDA STATUTE 489 WHO INTENDS TO
 CONSTRUCT, ENLARGE, ALTER, REPAIR, MOVE, DEMOLISH, OR
 CHANGE THE OCCUPANCY OF A BUILDING OR STRUCTURE, OR TO
 ERECT, INSTALL, ENLARGE, ALTER, REPAIR, REMOVE, CONVERT
 OR REPLACE ANY IMPACTRESISTANT COVERINGS, ELECTRICAL,
 GAS, MECHANICAL, PLUMBING OR FIRE PROTECTION SYSTEM, OR
 ACCESSIBLE OR FLOOD RESISTANT SITE ELEMENT, THE
 INSTALLATION OF WHICH IS REGULATED BY THIS CODE, OR TO
 CAUSE ANY SUCH WORK TO BE DONE, SHALL FIRST MAKE
 APPLICATION TO THE BUILDING OFFICIAL AND OBTAIN THE
 REQUIRED PERMIT.
  
 1A) WITH THE NEW GAS APPLIANCES BEING INTRODUCED INTO
 THIS DELI A GREASE INTERCEPTOR PERMIT WILL BE REQUIRED,
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5.1.3(11).
  
 1B) THE PLANS SUBMITTED FOR THE NEW GAS APPLIANCES
 LOCATION ALSO SHOWS A NEW LOCATION FOR THE REQUIRED
 HAND SINK THAT WAS INSTALLED UNDER THE MASTER PERMIT
 10080639 (PLANS) PLUMBING SUB-PERMIT 11060592. PERMIT
 IS REQUIRED FOR THE NEW LOCATION OF HAND SINK AND ANY
 OTHER PLUMBING THAT HAS BEEN MOVED. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION, 107.3.5.1.3 PLUMBING (4) SANITARY,
 (6) VENTS & (1) MINIMUM PLUMBING FIXTURES .
  
 1C) THIS TENNANCY AND USE OF THIS PORTION OF THE
 BUILDING WILL REQUIRE A SERVICE SINK FOR THE REMOVAL OF
 GREASY WASTE FROM ON THE FLOOR. 2010 FBC-P 403.1.3.1(2)
 & TABLE 403.1(1)A-2.
  
 2) GAS PERIMT MISSING PLAN REVIEW CRITERIA:
 107.3.5.1.5
  
 2.1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS. PLANS INDICATE THE USE OF A 2 LB
 REGULATOR BUT THE TABLE LISTED 402.4(2) IS FOR A 1/2 LB
 SYSTEM/ DISCREPANCY
  
 2.2. COMPLIED. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, AND THE EDH NUMBER OF
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE IF
 BEING USED.
  
 2.3.COMPLIED. TYPE OF GAS, (LP OR NATURAL).
  
 2.4.CLEAR UP DISCRENCY . BTU LOAD OF EACH APPLIANCE AND
 THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2010
 FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1)
 THRU 402.4(35)
  
 2.5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 2.6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 2.7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 2.8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS
 CODE SEC. 502 THRU 505.
  
 2.9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 3) LOW VALUE OF PROJECT. W P B ADMINISTRTIVE CODE 108.2
 SCHEDULE OF PERMIT FEES. ON BUILDINGS, STRUCTURES,
 ELECTRICAL, GAS, MECHANICAL, AND PLUMBING SYSTEMS OR
 ALTERATIONS REQUIRING A PERMIT, A FEE FOR EACH PERMIT
 SHALL BE PAID AS REQUIRED, IN ACCORDANCE WITH THE
 SCHEDULE ESTABLISHED BY THE APPLICABLE GOVERNING
 AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-10 Cont ID  
Sent By jwitmer Date 2014-04-10 Time 13:05 Rev Time 0.00
Received By jwitmer Date 2014-04-10 Time 13:05 Sent To  
Notes
2014-04-09 08:18:19ROUTED TO PLUMBING $5000 & UNDER