Plan Review Details - Permit 14040070
Plan Review Stops For Permit 14040070
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-05-22 Cont ID  
Sent By jwitmer Date 2014-05-02 Time 05:45 Rev Time 0.00
Received By jwitmer Date 2014-05-22 Time 12:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-09 Cont ID  
Sent By jwitmer Date 2014-04-09 Time 18:45 Rev Time 0.00
Received By jwitmer Date 2014-04-09 Time 17:45 Sent To  
Notes
2014-04-09 18:09:27BUILDING PLAN REVIEW
 PERMIT: 14040070
 ADD: 400 N FLAGLER # PHA-5
 CONT: CONKLING & LEWIS CONSTRUCTION
 TEL: (561)833-4441
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 09/2014
 ACTION: DENIED
  
 1) SHEET A101 PLAN NOTES # 5 PROVIDES A PARTIAL WIND
 DESIGN.
 MISSING FROM THE DESIGN ARE THE REQUIRED PRESSURES BOTH
 POSITIVE AND NEGATIVE. FOR WIND DESIGN ABOVE 60 FEET
 FROM GRADE ASCE 7-10 SHOULD BE USED, 2010 FBC-B
 1609.1.1. ARE THE SLIDING GLASS DOORS THAT ARE BEING
 MOVED TO THE NEW LOCATION IN A END ZONE OR INTERIOR
 ZONE, THIS WILL ALSO AFFECT THE PRESSURES.
  
  
  
 2) PLEASE PROVIDE A RATIONAL ANALYSIS FOR THE FASTENING
 OF THE FRAMES INTO THE (MWFRS) STRUCTURAL ELEMENTS,
 COLUMNS, BALCONY FLOOR SLAB AND OVERHEAD BALCONY SLAB.
 INCLUDE THE TYPE OF ANCHORS, LENGTH, DIAMETER, QUANTITY
 & SPACING OF ANCHORS. THE REUSING OF THE EXISTING DOORS
 IS SIMILAR O THE REQUIREMENTS FOR CUSTOM DOORS.
 2010 FBC-B 1715.5.3.2 CUSTOM DOORS. CUSTOM (ONE OF A
 KIND) EXTERIOR DOOR ASSEMBLIES SHALL BE TESTED BY AN
 APPROVED TESTING LABORATORY OR BE ENGINEERED IN
 ACCORDANCE WITH ACCEPTED ENGINEERING PRACTICES.
  
 3) THE EXISTING SLIDING GLASS DOORS DID HAVE A OVER
 HANG, WITH THE NEW PROPOSED LOCATION THEY WILL NEED TO
 MEET WATER INFILTRATION REQUIREMENTS FOUND IN 2010
 FBC-B 1715.5.2.1 TESTING AND LABELING.
 EXTERIOR WINDOWS AND GLASS DOORS SHALL BE TESTED BY AN
 APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE
 LABELED TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF
 ONE OF THE FOLLOWING SPECIFICATIONS:
  
 ANSI/AAMA/NWWDA 101/I.S. 2 OR ANSI/AAMA/ WDMA/101/I.S.
 2/NAFS OR AAMA/WDMA/CSA 101/I.S. 2/A440 OR TAS202 (HVHZ
 SHALL COMPLY WITH TAS202 UTILIZING ASTM E 1300-98 OR
 ASTM E 1300-04 OR SECTION 2404).
  
 EXTERIOR WINDOWS AND SLIDING GLASS DOORS SHALL BE
 LABELED WITH A PERMANENT LABEL, MARKING, OR ETCHING
 PROVIDING TRACEABILITY TO THE MANUFACTURER AND PRODUCT.
 THE FOLLOWING SHALL ALSO BE REQUIRED EITHER ON A
 PERMANENT LABEL OR ON A TEMPORARY SUPPLEMENTAL LABEL
 APPLIED BY THE MANUFACTURER: INFORMATION IDENTIFYING
 THE MANUFACTURER, THE PRODUCT MODEL/SERIES NUMBER,
 POSITIVE AND NEGATIVE DESIGN PRESSURE RATING, PRODUCT
 MAXIMUM SIZE, GLAZING THICKNESS, IMPACT-RESISTANCE
 RATING IF APPLICABLE, FLORIDA PRODUCT APPROVAL NUMBER
 OR MIAMI-DADE PRODUCT APPROVAL NUMBER, APPLICABLE TEST
 STANDARD(S), AND APPROVED PRODUCT CERTIFICATION AGENCY,
 TESTING LABORATORY, EVALUATION ENTITY OR MIAMI-DADE
 PRODUCT APPROVAL.
  
 THE LABELS ARE LIMITED TO ONE DESIGN PRESSURE RATING
 PER REFERENCE STANDARD. THE TEMPORARY SUPPLEMENTAL
 LABEL SHALL REMAIN ON THE WINDOW OR DOOR UNTIL FINAL
 APPROVAL BY THE BUILDING OFFICIAL.
 EXCEPTIONS:
 1.DOOR ASSEMBLIES INSTALLED IN NONHABITABLE AREAS WHERE
 THE DOOR ASSEMBLY AND AREA ARE DESIGNED TO ACCEPT WATER
 INFILTRATION NEED NOT BE TESTED FOR WATER INFILTRATION.
 2.DOOR ASSEMBLIES INSTALLED WHERE THE OVERHANG (OH)
 RATIO IS EQUAL TO OR MORE THAN 1 NEED NOT BE TESTED FOR
 WATER INFILTRATION. THE OVERHANG RATIO SHALL BE
 CALCULATED BY THE FOLLOWING EQUATION:
 OH RATIO = OH LENGTH/OH HEIGHT
 WHERE:
 OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN
 OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE.
 OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM
 THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A
 DOOR.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-04-21 Cont ID  
Sent By albarran Date 2014-04-21 Time 15:24 Rev Time 0.00
Received By albarran Date 2014-04-21 Time 14:45 Sent To I
Notes
2014-04-21 15:25:19ELECTRICAL PROVISO FOR PERMIT #14040070
 1. ALL UNUSED WIRING & CONDUIT SHALL BE REMOVED BACK
 FROM THE LAST JUNCTION BOX.
 2. ALL OUTLET PLACEMENT SHALL COMPLY W/T 2008 EDITION
 OF THE NEC 210.52
 3. ALL NEW WORK SHALL COMPLY WITH NEC?S REQUIREMENTS
 FOR ARC-FAULT, GFI & TAMPER-RESISTANT REQUIREMENTS.
 4. SMOKE DETECTORS AS PER FBC-R314 SHALL BE INSTALLED
 IF NOT ALREADY IN PLACE.
 ALL WORK SHALL BE SUBJECT TO FIELD INSPECTOR?S
 APPROVAL.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-11 Cont ID  
Sent By wjolin Date 2014-04-11 Time 13:12 Rev Time 0.00
Received By wjolin Date 2014-04-11 Time 13:05 Sent To  
Notes
2014-04-11 13:12:37SEPARATE PLANS AND PERMIT NEEDED TO PROVIDE FIRE
 SPRINKLER PROTECTION FOR THE NEWLY ENCLOSED BALCONY
 SPACE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-22 Cont ID  
Sent By jwitmer Date 2014-05-22 Time 16:53 Rev Time 0.00
Received By jwitmer Date 2014-05-08 Time   Sent To  
Notes
2014-05-08 10:00:42ROUTED TO JW.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-21 Cont ID  
Sent By albarran Date 2014-04-21 Time 15:25 Rev Time 0.00
Received By albarran Date 2014-04-02 Time 14:29 Sent To PC
Notes
2014-04-21 15:28:59PROCESSED CALLED TERRY & SENT TO DENIED BIN "C"
2014-04-02 14:30:36INCOMING SENT TO B03 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-04-09 Cont ID  
Sent By jwitmer Date 2014-04-09 Time 18:07 Rev Time 0.00
Received By jwitmer Date 2014-04-09 Time 18:07 Sent To  
Notes
2014-04-09 18:08:50NO MECHANICAL WORK SHOWN ON PLANS. JW

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-04-09 Cont ID  
Sent By jwitmer Date 2014-04-09 Time 18:07 Rev Time 0.00
Received By jwitmer Date 2014-04-09 Time 18:07 Sent To  
Notes
2014-04-09 18:08:04NO PLUMBING WORK SHOWN ON PLANS PLUMBING FIXTURES SHOWN
 IN SAME LOCATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-04-03 Cont ID  
Sent By ajones Date 2014-04-03 Time 10:04 Rev Time 0.00
Received By ajones Date 2014-04-03 Time 10:04 Sent To  
Notes
***NONE***