Plan Review Details - Permit 14040040
Plan Review Stops For Permit 14040040
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-04-17 Cont ID  
Sent By rmcdouga Date 2014-04-17 Time 13:39 Rev Time 0.00
Received By rmcdouga Date 2014-04-17 Time 13:28 Sent To  
Notes
2014-04-17 13:41:30BUILDING PROVISO
 A MECHANICAL SUB-PERMIT WILL BE REQUIRED TO REMOVE THE
 A/C CONDENSING UNITS AND RE-INSTALL
 THEM ON STANDS PER FBC 1509.7. THE ATTACHMENT OF THE
 STANDS TO THE ROOF WILL NEED TO BE INSPECTED
 BY THE MECHANICAL INSPECTOR BEFORE THEY ARE COVERED BY
 THE ROOFING MATERIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-02 Cont ID  
Sent By rmcdouga Date 2014-04-02 Time 08:59 Rev Time 0.00
Received By rmcdouga Date 2014-04-02 Time 07:23 Sent To  
Notes
2014-04-02 07:25:102010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN A 170 MPH VULT WIND
 SPEED AND IS EXPOSURE CATEGORY C. SUBMIT TWO SETS OF
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING OF THE PERIMETER AND CORNER AREAS AS REQUIRED
 BY LIMITATION NUMBER 7 OF THE CERTAIN-TEED NOA
 NO.10-0330.02.
  
 2) A MECHANICAL SUB-PERMIT WILL BE REQUIRED TO REMOVE
 THE A/C CONDENSING UNITS AND RE-INSTALL THEM ON STANDS
 PER FBC 1509.7. THE ATTACHMENT OF THE STANDS TO THE
 ROOF WILL NEED TO BE INSPECTED BY THE MECHANICAL
 INSPECTOR BEFORE THEY ARE COVERED BY THE ROOFING
 MATERIAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-01 Cont ID  
Sent By shill Date 2014-05-01 Time 13:23 Rev Time 0.00
Received By shill Date 2014-05-01 Time 13:23 Sent To  
Notes
2014-05-01 13:24:41OK PER H MOSER TO ISSUE MECHANICAL SUB PERMIT
 STAND ENGINEERING TO BE PROVIDED AT INSPECTION
  