Plan Review Stops For Permit 14031127 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-04-17 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-04-17 |
Time |
11:09 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-04-17 |
Time |
10:20 |
Sent To |
I |
|
Notes |
2014-04-17 11:12:27 | NOTICE TO FIRE ALARM CONTRACTOR: | | ALL DOCUMENTATION AS REQUIRED PER NFPA 72 SECTION 4.5 | | SHALL BE PROVIDED UPON COMPLETION AND BE AVAILABLE FOR | | FINAL INSPECTION. | | FOR FINAL INSPECTION THIS SYSTEM SHALL UNDERGO A | | REACCEPTANCE TEST AS PER NFPA 72, SECTION 10.4.1.2. | | RECORDS OF SUCH SHALL BE KEPT IN THE SYSTEM LOG AS | | REQUIRED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2014-03-31 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2014-03-31 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2014-03-31 |
Time |
11:16 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-04-17 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-04-17 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-03-28 |
Time |
15:18 |
Sent To |
PC |
|
Notes |
2014-04-17 11:13:08 | TAKEN TO ALLISON | 2014-03-28 15:18:26 | ROUTED TO FIRE |
|
|
|