Plan Review Details - Permit 14031086
Plan Review Stops For Permit 14031086
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-04-11 Cont ID  
Sent By jwitmer Date 2014-04-11 Time 10:25 Rev Time 0.00
Received By jwitmer Date 2014-04-11 Time 09:34 Sent To  
Notes
2014-04-11 10:17:38BUILDING PLAN REVIEW
 PERMIT: 14031086
 ADD: 550 OKEECHOBEE BLVD
 CONT: D'ANGELO BUILDERS INC
 TEL: (561) 262-1784
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY APRIL 11, 2014
 ACTION: BUILDING PROVISO
  
 1) PLANS DO NOT INDICATE ANY FLOORING WORK TO BE
 ACCOMPLISHED UNDER THIS PERMIT. PLEASE BE AWARE OF THE
 FOLLOWING REQUIREMENTS:
  
 TYPE I/ TYPE II BUILDINGS
 2010 FBC-B 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM
 PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25.
 EXCEPTIONS:
 1. INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
  
 TYPE I TYPE II WOOD FLOOR 805.1.3 INSULATING BOARDS.
 COMBUSTIBLE INSULATING BOARDS NOT MORE THAN 1/2 INCH
 (12.7 MM) THICK AND COVERED WITH FINISH FLOORING ARE
 PERMITTED WHERE ATTACHED DIRECTLY TO A NONCOMBUSTIBLE
 FLOOR ASSEMBLY OR TO WOOD SUBFLOORING ATTACHED TO
 SLEEPERS AS PROVIDED FOR IN SECTION 805.1.1.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-04-01 Cont ID  
Sent By rlecky Date 2014-04-01 Time 13:27 Rev Time 0.00
Received By rlecky Date 2014-04-01 Time 13:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-02 Cont ID  
Sent By pleduc Date 2014-04-02 Time 12:03 Rev Time 0.00
Received By pleduc Date 2014-04-02 Time 11:36 Sent To B
Notes
2014-04-02 12:03:04THE PERMIT PLAN WAS REVIEWED AND APPROVED WITH THE
 FOLLOWING COMMENTS BY PETER LEDUC, FIRE MARSHAL, BUREAU
 OF FIRE PREVENTION, WEST PALM BEACH FIRE RESCUE.
  
 1. ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO
 BE COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR
 AND SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS,
 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY
 THE FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE
 SYSTEM.
  
 2. ALL FIRE ALARM SYSTEM WORK SHALL BE DONE BY A
 CERTIFIED FIRE ALARM CONTRACTOR AND COMPLY WITH NFPA
 72. A SEPARATE SHOP DRAWING IS REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
  
 3. THE LIFE SAFETY SYSTEMS, SPRINKLER AND/OR FIRE
 ALARM, SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION
 PERIOD.
  
 4. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-11 Cont ID  
Sent By jwitmer Date 2014-04-11 Time 10:25 Rev Time 0.00
Received By jwitmer Date 2014-03-27 Time 18:23 Sent To  
Notes
2014-03-27 18:24:41INCOMING SENT TO B-02. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-04-11 Cont ID  
Sent By jwitmer Date 2014-04-11 Time 09:49 Rev Time 0.00
Received By jwitmer Date 2014-04-11 Time 09:49 Sent To  
Notes
2014-04-11 09:50:29NO MECHANICAL WORK SHOWN ON PLANS.

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-04-11 Cont ID  
Sent By jwitmer Date 2014-04-11 Time 09:49 Rev Time 0.00
Received By jwitmer Date 2014-04-11 Time 09:34 Sent To  
Notes
2014-04-11 09:55:47NO PLUMBING WORK SHOWN ON THE PLANS. JW

Review Stop Z ZONING
Rev No 1 Status P Date 2014-03-28 Cont ID  
Sent By ajones Date 2014-03-28 Time 10:01 Rev Time 0.00
Received By ajones Date 2014-03-28 Time 10:01 Sent To  
Notes
***NONE***