Plan Review Details - Permit 14030971
Plan Review Stops For Permit 14030971
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-25 Cont ID  
Sent By jgomez Date 2014-03-25 Time 18:30 Rev Time 0.00
Received By jgomez Date 2014-03-25 Time 17:06 Sent To  
Notes
2014-03-25 18:39:36RE-ROOF REVISION, BUILDING REVIEW COMMENTS.
  
  
 1- NOA 13-0129.19 SUBMITTED IS FOR MODIFIED BITUMEN
 ROOFING SYSTEMS OVER STEEL DECKS. IT DOESN'T APPLY TO
 THE EXISTING CONDITIONS. NEED TO PROVIDE NOA THAT
 MATCHES EXISTING CONDITIONS AND PROPOSED INSTALLATION.
 NEED PRODUCT APPROVAL (2 COPIES) FOR ROOFING SYSTEMS
 OVER LIGHTWEIGHT CONCRETE DECK. AND, NEED TO SELECT
 ASSEMBLY THAT SHOWS FASTENING TO THE STEEL DECK THROUGH
 THE LIGHT WEIGHT CONCRETE AS REQUIRED BY DCA RULE 9N-3.
  
 2- ENGINEER TO REVISE RAS 117 CALCULATIONS USING THE
 PRODUCT APPROVAL ASSEMBLY REQUIRED BY ITEM #1 ABOVE.
 SEC. 1609 OF FBC-2010
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-25 Cont ID  
Sent By jgomez Date 2014-03-25 Time 18:30 Rev Time 0.00
Received By jgomez Date 2014-03-25 Time 14:06 Sent To  
Notes
2014-03-25 14:06:52TO JG DESK
  