Plan Review Details - Permit 14030912
Plan Review Stops For Permit 14030912
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-04-26 Cont ID  
Sent By shill Date 2014-04-26 Time 10:28 Rev Time 0.00
Received By shill Date 2014-04-26 Time 10:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-26 Cont ID  
Sent By shill Date 2014-03-26 Time 16:39 Rev Time 0.00
Received By shill Date 2014-03-26 Time 16:39 Sent To  
Notes
2014-03-26 16:41:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW
 COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 2. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
 3. PROVIDE DIMENSIONS ON THE SITE PLAN FBC 107,
 INCLUDING THE DIMENSIONS OF THE AWNING AS WELL AS
 DISTANCE TO PROPERTY LINE.
  
 4. THE AWNING ENGINEERING CONFLICTS WITH THE SITE PLAN.
 SITE PLAN SHOWS A NARROW LONG AWNING ATTCHED TO THE
 BUILDING, ENGINEERING IS FOR A NEARLY SQUARE (11'6" X
 8'5") AWNING.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-26 Cont ID  
Sent By shill Date 2014-04-26 Time 10:28 Rev Time 0.00
Received By shill Date 2014-04-18 Time 17:31 Sent To  
Notes
2014-04-18 17:32:00INCOMING SENT TO ZONING BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-26 Cont ID  
Sent By shill Date 2014-03-26 Time 16:42 Rev Time 0.00
Received By shill Date 2014-03-24 Time 10:15 Sent To  
Notes
2014-03-24 10:15:42ROUTED TP ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2014-04-21 Cont ID  
Sent By sgraham Date 2014-04-21 Time 11:31 Rev Time 0.00
Received By sgraham Date 2014-04-21 Time 11:31 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-03-24 Cont ID  
Sent By sgraham Date 2014-03-24 Time 11:58 Rev Time 0.00
Received By sgraham Date 2014-03-24 Time 11:58 Sent To B
Notes
2014-03-24 11:58:013/24/14 ZONING FAILED
 1. PLEASE PROVIDE SETBACK INFORMATION FOR THE AWNING
 FROM THE PROPERTY LINE