Plan Review Details - Permit 14030862
Plan Review Stops For Permit 14030862 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2014-06-03 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-06-03 |
Time |
09:43 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-06-03 |
Time |
09:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-04-15 |
Time |
08:26 |
Sent To |
|
|
Notes |
2014-04-15 17:51:32 | IN ADDITION TO THE FIRE DEPARTMENT COMMENTS WHICH CALL | | FOR THE ADDITION OF A COUPLE OF MANUAL PULL STATIONS | | ETC. PROVIDE A DRAWING OF THE PROPOSED SMOKE BARRIER | | DOOR SHOWING CORRIDOR HEIGHTS IN RELATION TO DOOR | | HEIGHTS. INDICATE IF DOOR RELEASE IS DIRECTLY FROM THE | | RESPECTIVE SMOKE DETECTOR OR FROM THE FACP. REARRANGE | | THE DOORS AND HOLDERS SO THAT THE DOORS SWING IN THE | | NORMAL PATH OF EGRESS. PLEASE INDICATE ON THE DRAWING | | IF THE BLDG. IS FULLY SPRINKLED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2014-04-28 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-04-28 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-04-28 |
Time |
15:32 |
Sent To |
E |
|
Notes |
2014-04-28 12:29:38 | NEW SHEETS SUBMITTED. JG. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2014-03-24 |
|
|
Cont ID |
|
Sent By |
rferguso |
Date |
2014-03-24 |
Time |
16:22 |
Rev Time |
0.00 |
Received By |
rferguso |
Date |
2014-03-24 |
Time |
16:22 |
Sent To |
E |
|
Notes |
2014-03-24 17:02:32 | 8151 OKEECHOBEE BOULIVARD | | PERMIT #14030862 | | | | WEST PALM BEACH FIRE RESCUE PLAN REVIEW COMMENTS. | | | | PLAN (OK) PROVISO. | | * INDICATE ON PLAN THAT PER LOCAL AHJ POLICY, DUCT | | SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE ALARM | | CONDITION. | | | | * INDICATE ON PLAN THAT A CERTIFICATE OF COMPLETION AND | | A THIRD PARTY MONITORING/VERIFICATION (UL OR ETL) | | CERTIFICATE SHALL BE PROVIDED AT TIME OF FINAL FIRE | | ALARM INSPECTION. | | | | * INSTALL ONE HORN STROB DEVICE IN ADMIN SPACE # 100 | | AND AN ADDITIONAL PULL STATION NEAR THE EXIT NEXT TO | | NAC2 - 2-1. | | | | RONALD E. FERGUSON, ASSISTANT FIRE MARSHAL | | BUREAU OF FIRE PREVENTION | | WEST PALM BEACH FIRE RESCUE | | PHONE (561)804-4700 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-06-03 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2014-06-03 |
Time |
09:49 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-04-25 |
Time |
12:30 |
Sent To |
|
|
Notes |
2014-04-28 12:30:36 | NEW SHEETS SENT TO FIRE SHELF FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-04-15 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-04-15 |
Time |
18:16 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-03-20 |
Time |
14:29 |
Sent To |
|
|
Notes |
2014-04-15 18:16:45 | ROUTED TO SMALL DENIED BIN "K" | 2014-03-20 14:29:12 | ROUTED TO FIRE |
|
|
|
Account Summary | Usage Policy | Privacy Policy