Plan Review Details - Permit 14030822
Plan Review Stops For Permit 14030822 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2014-04-09 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-04-09 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-04-09 |
Time |
13:18 |
Sent To |
I |
|
Notes |
2014-04-09 14:35:55 | ELECTRICAL PROVOSO: THOUGH NOT INDICATED ON THE | | APPROVED DRAWINGS, THE EXISTING POWER SUPPLY AND THE | | ELECTRIC ROOM SHALL BE PROTECTED BY A SMOKE DETECTOR AS | | REQUIRED BY FBC & NFPA 72. | | ALL DOCUMENTATION AS REQUIRED BY NFPA 72 SECTION 4.5 | | SHALL BE PROVIDED UPON COMPLETION AND AVAILABLE FOR | | INSPECTION. | | FOR FINAL INSPECTION, THIS SYSTEM SHALL UNDERGO A | | REACCEPTANCE TEST AS REQUIRED BY NFPA 72 SECTION | | 10.4.1.2; RECORDS OF THAT SHALL BE KEPT IN THE SYSTEM | | LOG AS REQUIRED. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-03-26 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-03-26 |
Time |
13:14 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-03-26 |
Time |
13:03 |
Sent To |
I |
|
Notes |
2014-03-26 13:19:51 | THE FOLLOWING CORRECTIONS SHALL BE MADE TO THE DRAWINGS | | FOR APPROVAL. | | 1. PROVIDE A LEGEND TO IDENTIFY ALL DEVICES EXISTING TO | | REMAIN, EXISTING TO BE REMOVED, NEW DEVICE, AREA OF | | WORK ETC. | | 2. CLEARLY INDICATE THE LOCATION OF THE NEW DEVICES. | | 3. SHOW LOCATION OF POWER SOURCE AND INDICATE LOCATION | | OF FACP | | 4. THE SYSTEM SHALL BE TESTED FOR FINAL INSPECTION. | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | CONTACT: | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | PH: (561) 805-6718, EMAIL: [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2014-04-08 |
|
|
Cont ID |
|
Sent By |
rferguso |
Date |
2014-04-08 |
Time |
12:37 |
Rev Time |
0.00 |
Received By |
rferguso |
Date |
2014-04-08 |
Time |
12:37 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2014-03-24 |
|
|
Cont ID |
|
Sent By |
rferguso |
Date |
2014-03-24 |
Time |
17:32 |
Rev Time |
0.00 |
Received By |
rferguso |
Date |
2014-03-24 |
Time |
17:32 |
Sent To |
E |
|
Notes |
2014-03-24 17:49:33 | 777 SOUTH FLAGLER DRIVE #1200W | | PERMIT #14030822 | | | | WEST PALM BEACH FIRE RESCUE PLAN REVIEW COMMENTS | | | | * EXPLAIN, SHOW AND BE CLEAR WHAT AND WHERE WORK IS | | BEING PERFORMED. | | | | RONALD E. FERGUSON, ASSITANT FIRE MARSHAL | | BUREAU OF FIRE PREVENTION | | WEST PALM BEACH FIRE RESCUE | | PHONE (561)804-4700 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-04-09 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-04-09 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-04-01 |
Time |
17:46 |
Sent To |
PC |
|
Notes |
2014-04-09 14:38:11 | SAK BOX | 2014-04-01 17:46:53 | SENT TO FIRE BOX. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |