Plan Review Details - Permit 14030818
Plan Review Stops For Permit 14030818
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-04-25 Cont ID  
Sent By jwitmer Date 2015-04-25 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2015-04-25 Time 13:30 Sent To  
Notes
2015-04-01 09:17:44NEW DRAWINGS SUBMITTED. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-12-08 Cont ID  
Sent By jwitmer Date 2014-12-08 Time 13:19 Rev Time 0.00
Received By jwitmer Date 2014-12-07 Time 11:20 Sent To  
Notes
2014-12-08 12:14:00BUILDING PLAN REVIEW
 PERMIT: 14030818
 ADD: 526 CLEMATIS ST 1ST FLOOR & 2ND FLOOR- CHANGE OF
 OCCUPANY/INTERIOR & EXTERIOR
 CONT: JM PROPERTIES OF WEST PALM BEACH, INC
 TEL: (561)756-5744
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BLDG TYPE III-B SPRINKLERED
  
 3RD REVIEW
 DATE: MON. DEC. 08/ 2014
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 THE LAST RENOVATIONS TO THIS BUILDING UNDER PERMIT
 03060274, FIRST FLOOR MERCANTILE AND THE 2ND FLOOR R2
 APARTMENTS, THIS REVIEW WILL BE CONSIDERED A CHANGE IN
 OCCUPANCY AND CHAPTER 9 OF THE EXISITNG BUILDING CODE.
 901.3 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
  
  
 CONTRACTOR IS PROCEEDING AT THEIR OWN RISK!!! 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 105.13 PHASED PERMIT
 APPROVAL. AFTER SUBMITTAL OF THE APPROPRIATE
 CONSTRUCTION DOCUMENTS, THE BUILDING OFFICIAL IS
 AUTHORIZED TO ISSUE A PERMIT FOR THE CONSTRUCTION OF
 FOUNDATIONS OR ANY OTHER PART OF A BUILDING OR
 STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS FOR THE
 WHOLE BUILDING OR STRUCTURE HAVE BEEN SUBMITTED. THE
 HOLDER OF SUCH PERMIT FOR THE FOUNDATION OR OTHER PARTS
 OF A BUILDING OR STRUCTURE SHALL PROCEED AT THE
 HOLDER?S OWN RISK WITH THE BUILDING OPERATION AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 1) REVISION REQUIRED. AN ARCHITECTURAL SHEET IS
 REQUIRED SHOWING THE SCHEMATIC LAYOUT FOR THE FIRE
 SPRINKLERS, A FULL NFPA 13 SYSTEM WILL BE REQUIRED.
 A HOLD WILL BE PUT ON THE CERTIFICATE OF OCCUPANCY
 UNTIL THIS REVISION IS SUBMITTED AND APPROVED. SEPARATE
 FIRE SPRINKLER PLANS WILL ALSO NEED TO BE SUBMITTED BY
 THE ENGINEER OF RECORD AND REVIEWED BY THE DESIGNER OF
 RECORD WITH THIER SHOP DRAWING STAMP OF APPROVAL,
 APPROVED OR APPROVED WITH COMMENTS.
  
 107.2.1.1 FIRE PROTECTION SYSTEM SHOP DRAWINGS. SHOP
 DRAWINGS FOR THE FIRE PROTECTION SYSTEM(S) SHALL BE
 SUBMITTED TO INDICATE CONFORMANCE WITH THIS CODE AND
 THE CONSTRUCTION DOCUMENTS AND SHALL BE APPROVED PRIOR
 TO THE START OF SYSTEM INSTALLATION. SHOP DRAWINGS
 SHALL CONTAIN ALL INFORMATION AS REQUIRED BY THE
 REFERENCED INSTALLATION STANDARDS IN CHAPTER 9.
  
 3RD REQUEST. MON. DEC. 08/2014 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (5) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
  
 THE COVERSHEET A0.0 INDICATES THIS BUILDING TO BE FIRE
 SPRINKLERED, BUT THERE IS NO MENTION OF A FIRE
 SPRINKLER PLAN IN THE INDEX OF DRAWINGS NOR ANYWHERE
 ELSE IN THE PLANS. TRAVEL DISTANCES ARE SHOWN FOR
 NON-SPRINKLERED BUILDING.
 2010 EXST BLDG CODE 904.1 GENERAL.
 FIRE PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY
 WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE
 OF OCCUPANCY CLASSIFICATION.
 912.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 912.2.1 AND 912.2.2.
  
 EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2010 FBC-B F] 903.2.1.2 GROUP A-2.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED FOR
 GROUP A-2 OCCUPANCIES WHERE ONE OF THE FOLLOWING
 CONDITIONS EXISTS:
 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2);
 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE;
  
 EXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION
 APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT
 THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A
 FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED.
  
 BUILDING PROVISO:
 10C) FRONT ENTRY REDESIGN:
 10C)(1) MISSING PRODUCT APPROVALS 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:(31)(A) EXTERIOR DOORS.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-10-08 Cont ID  
Sent By jwitmer Date 2014-10-08 Time 08:15 Rev Time 0.00
Received By jwitmer Date 2014-10-08 Time 06:04 Sent To  
Notes
2014-10-08 08:15:40BUILDING PLAN REVIEW
 PERMIT: 14030818
 ADD: 526 CLEMATIS ST 1ST FLOOR & 2ND FLOOR- CHANGE OF
 OCCUPANY/INTERIOR & EXTERIOR
 CONT: JM PROPERTIES OF WEST PALM BEACH, INC
 TEL: (561)756-5744
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BLDG TYPE III-B SPRINKLERED
  
 2ND REVIEW
 DATE: WEDNESDAY 08/ 2014
 ACTION: DENIED
  
 THE LAST RENOVATIONS TO THIS BUILDING UNDER PERMIT
 03060274, FIRST FLOOR MERCANTILE AND THE 2ND FLOOR R2
 APARTMENTS, THIS REVIEW WILL BE CONSIDERED A CHANGE IN
 OCCUPANCY AND CHAPTER 9 OF THE EXISITNG BUILDING CODE.
 901.3 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
  
 1) THE COVERSHEET A0.0 INDICATES THE OCCUPANCY AS A A2
 NIGHTCLUB SINCE THERE IS NO KITCHEN SHOWN ON THE PLANS.
 SHEET A1.2 LIST OCCUPANT LOADS FOR EACH FLOOR EXAMPLE
 THE 2ND FLOOR LIST CUSTOMER AREA 992 SQ. FT./ 198
 OCCUPANTS + 32 +16+ 8 +6 +10. PLEASE PROVIDE WHERE THE
 ADDITIONAL
 OCCUPANT LOADS ARE TAKEN FROM, INDICATE THE AREA AND
 LOADING FACTOR.
 2010 FBC-B 1004.2 INCREASED OCCUPANT LOAD.
 THE OCCUPANT LOAD PERMITTED IN ANY BUILDING, OR PORTION
 THEREOF, IS PERMITTED TO BE INCREASED FROM THAT NUMBER
 ESTABLISHED FOR THE OCCUPANCIES IN TABLE 1004.1.1,
 PROVIDED THAT ALL OTHER REQUIREMENTS OF THE CODE ARE
 ALSO MET BASED ON SUCH MODIFIED NUMBER AND THE OCCUPANT
 LOAD DOES NOT EXCEED ONE OCCUPANT PER 7 SQUARE FEET
 (0.65 M2) OF OCCUPIABLE FLOOR SPACE. WHERE REQUIRED BY
 THE BUILDING OFFICIAL, AN APPROVED AISLE, SEATING OR
 FIXED EQUIPMENT DIAGRAM SUBSTANTIATING ANY INCREASE IN
 OCCUPANT LOAD SHALL BE SUBMITTED. WHERE REQUIRED BY THE
 BUILDING OFFICIAL, SUCH DIAGRAM SHALL BE POSTED.
  
 2) 2ND REQUEST. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (5) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
  
 THE COVERSHEET A0.0 INDICATES THIS BUILDING TO BE FIRE
 SPRINKLERED, BUT THERE IS NO MENTION OF A FIRE
 SPRINKLER PLAN IN THE INDEX OF DRAWINGS NOR ANYWHERE
 ELSE IN THE PLANS. TRAVEL DISTANCES ARE SHOWN FOR
 NON-SPRINKLERED BUILDING.
 2010 EXST BLDG CODE 904.1 GENERAL.
 FIRE PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY
 WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE
 OF OCCUPANCY CLASSIFICATION.
 912.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 912.2.1 AND 912.2.2.
  
 EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2010 FBC-B F] 903.2.1.2 GROUP A-2.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED FOR
 GROUP A-2 OCCUPANCIES WHERE ONE OF THE FOLLOWING
 CONDITIONS EXISTS:
 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2);
 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE;
  
 EXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION
 APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT
 THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A
 FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED.
  
 3) COMPLIED, NEW INSWING FOLDING DOOR SYSTEM SHOWN ON
 PLANS.
  
  
 4) SEMI-COMPLIED. THE (2) EXISTING SWING DOORS NEED TO
 SHOW THEY DO NOT SWING OUT OVER THE PROPERTY LINE AND
 IN COMPLIANCE WITH 2010 FBC-B
 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN
 HEIGHT. PROVIDE A SITE PLAN AND OR SURVEY SHOWING CODE
 COMPLIANCE.
  
 5) 2ND REQUEST. THE PLANS DO NOT HAVE ANY DETAILS AS
 FAR AS THE SILL FOR THE FOLDING DOOR SYSTEM, PLEASE
 PROVIDE COMPLIANCE WITH 2010 FL ACCESS CODE 404.2.5
 THRESHOLDS.
 THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH
 (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES IN
 LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND 303.
  
 6) SEMI-COMPLIED. SHEET A1.1 THE FRONT STAIR IS AN
 UNENCLOSED EXIT STAIRWAY AND TAKING THE EXEMPTION# 3 IN
 SECTION 1016.1. PLEASE PROVIDE THE WIDTH BOTH STAIRS
 AND THE ALLOWABLE OCCUPANT LOADS EACH STAIR WILL
 ACCEPT. 2010 FBC-B 1005.1.
  
 7) SHEET A1.1 THE ELEVATOR MACHINE ROOM 2010 FBC-B
 3006.4. PLEASE NOTE THE CEILING OF THIS ROOM WILL NEED
 TO BE FIRE RATED AS WELL IT WILL ABUT THE FRAMING
 MEMBERS OF THE STAIRWELL. 2010 FBC-B 1022.1 & 707
 HORIZONTAL ASSEMBLIES. DOOR RATING 3/4 HR FIRE BARRIER
 TABLE 715.4.
  
 8-9) COMPLIED.
  
 10) STRUCTURAL SHEET S-1:
  
 10A) STRUCTURAL SHEET ELEVATOR DETAIL IS MISSING THE
 FOLLOWING :
 10A)(1) TB- HEIGTH NOT PROVIDED. NOTE TO MATCH
 EXISTING, NOTE THIS IS A (2) STORY SHAFT AND THERE IS
 NO DETAIL AS TO HOW THE TOP OF THE SHAFT FINISHES,
 BELOW THE ROOF OR ABOVE THE ROOF. 2010 FBC-B 708.12
 10A)(2) COMPLIED.
 10A)(3) ELEVATOR DOES NOT SHOW A PIT OR RECESS FOR THE
 FLOOR OF THE ELEVATOR CAB TO BE LEVEL WITH THE FLOOR.
 10)(4) THE ELEVATOR SHAFT DOES NOT CONTINUE THROUGH THE
 SECOND FLOOR.
 10)(5) SHAFT ENCLOSURE, 2010 FBC-B 708.12 ENCLOSURE AT
 THE TOP. A SHAFT ENCLOSURE THAT DOES NOT EXTEND TO THE
 UNDERSIDE OF THE ROOF SHEATHING, DECK OR SLAB OF THE
 BUILDING SHALL BE ENCLOSED AT THE TOP WITH CONSTRUCTION
 OF THE SAME FIRE-RESISTANCE RATING AS THE TOPMOST FLOOR
 PENETRATED BY THE SHAFT, BUT NOT LESS THAN THE
 FIRE-RESISTANCE RATING REQUIRED FOR THE SHAFT
 ENCLOSURE.
  
  
 10B)COMPLIED.
  
 10C) FRONT ENTRY REDESIGN:
 10C)(1) MISSING PRODUCT APPROVALS 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:(31)(A) EXTERIOR DOORS.
  
 10C)(2) MISSING DIMENSIONS, NO INFORMATION FOR VERTICAL
 NOR HORIZONTAL STEEL FRAMING MEMBERS, PRODUCT APPROVALS
 WILL NEED TO BE DECIDED TO BE ABLE TO PRODUCE THE
 SIZING OF THE ROUGH OPENING. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 107.2.1.3 ADDITIONAL DATA.
 THE BUILDING OFFICIAL MAY REQUIRE DETAILS,
 COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA NECESSARY
 TO DESCRIBE THE CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATIONS. ALL DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA REQUIRED BY THE BUILDING OFFICIAL TO
 BE PREPARED BY AN ARCHITECT OR ENGINEER SHALL BE
 AFFIXED WITH THEIR OFFICIAL SEAL, SIGNATURE AND DATE AS
 STATE LAW REQUIRES.
 SHEET S-1 INDICATES A DETAIL FOR THE FRONT ENTRY SHEET
 S-2 DETAIL # 7. THIS DETAIL INDICATES THE INSTALATION
 OF A W 16X31 BEAM TO AC1540 C CHANNEL.
 IN THIS SAME DETAIL AT THE BOTTOM OF THE DETAIL HERE
 APPEARS TO BE A BOX BEAM, THERE IS NO INFORMATION ON
 THE SIZE OF THIS BEAM OR HOW IT IS TO INSTALLED, IT
 APPEARS THIS THIS THE STRUCTURAL MEMBER (HEADER) FOR
 THE FOLDING DOOR SYSTEM.
  
 10D) NEW COMMENT: THE NEW FRONT ENTRY CONFIGURATION NOW
 CONSIST OF A SINGLE SWING DOOR AND A FOLDING DOOR
 SYSTEM THAT HAS INCORPARATED A SWING DOOR AS PART OF
 THE FOLDING DOOR SYSTEM. PLEASE NOTE THAT BOTH OF THE
 FRONT SWING DOORS WILL BE REQUIRED AS PART OF THE
 EGRESS DOORS SINCE A 3'-0" DOOR WILL ALLOW 170
 OCCUPANTS. PLEASE PROVIDE COMPLIANCE WITH 1008.1.10
 PANIC AND FIRE EXIT HARDWARE, HOW WILL THIS REQUIREMENT
 WORK AS PART OF THE FOLDING DOOR SYSTEM?
  
 11) COMPLIED.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-16 Cont ID  
Sent By jwitmer Date 2014-04-16 Time 07:11 Rev Time 0.00
Received By jwitmer Date 2014-04-15 Time 16:30 Sent To  
Notes
2014-04-15 18:59:58BUILDING PLAN REVIEW
 PERMIT: 14030818
 ADD: 526 CLEMATIS ST 1ST FLOOR CHANGE OF OCCUPANY/
 EXTERIOR ALTERATIONS
 CONT: JM PROPERTIES OF WEST PALM BEACH, INC
 TEL: (561)756-5744
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BLDG TYPE III-B SPRINKLERED
  
 1ST REVIEW
 DATE: TUESDAY APRIL 16/ 2014
 ACTION: DENIED
  
 THE LAST RENOVATIONS TO THIS BUILDING UNDER PERMIT
 03060274, FIRST FLOOR MERCANTILE AND THE 2ND FLOOR R2
 APARTMENTS, THIS REVIEW WILL BE CONSIDERED A CHANGE IN
 OCCUPANCY AND CHAPTER 9 OF THE EXISITNG BUILDING CODE.
 901.3 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
  
 1) THE COVERSHEET A0.0 INDICATES THE 1ST FLOOR
 OCCUPANCY CLASSIFICATION AS A A-3, THE PLANS APPEAR TO
 BE A NIGHTCLUB OR BAR / TAVERN WHICH IS A A2 OCCUPANCY,
 SEE 2010 FBC-B 303.1.
  
 2) THE COVERSHEET A0.0 INDICATES THIS BUILDING TO BE
 FIRE SPRINKLERED, BUT THERE IS NO MENTION OF A FIRE
 SPRINKLER PLAN IN THE INDEX OF DRAWINGS NOR ANYWHERE
 ELSE IN THE PLANS. TRAVEL DISTANCES ARE SHOWN FOR
 NON-SPRINKLERED BUILDING.
 2010 EXST BLDG CODE 904.1 GENERAL.
 FIRE PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY
 WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE
 OF OCCUPANCY CLASSIFICATION.
 912.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 912.2.1 AND 912.2.2.
  
 EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2010 FBC-B F] 903.2.1.2 GROUP A-2.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED FOR
 GROUP A-2 OCCUPANCIES WHERE ONE OF THE FOLLOWING
 CONDITIONS EXISTS:
 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2);
 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE;
  
 EXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES A FIRE ALARM AND DETECTION SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION
 APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT
 THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A
 FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED.
  
 3) SHEET A1.1 SHOWS NEW OUT SWING ENTRY DOORS PLEASE
 PROVIDE A SURVEY WITH THE DISTANCE FROM THE BUILDING TO
 THE PROPERTY LINE AT THE CLEMATIS OR FRONT OF THE
 BUILDING. 2010 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE
 AND BELOW 8 FEET IN HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE
 PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1
 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 4) SHEET A1.1 FRONT ENTRY AREA THERE IS A DISCREPANCY
 IN THE PLANS. THE 1ST FLOOR PLAN AND LIFE SAFETY PLAN
 SHOW TWO SWING ENTRY DOORS AND THE EXTERIOR FOLDING
 DOOR SYSTEM FOLDING OVER AND STCKING ALL THE WAY TO THE
 EAST OF THE OPENING, WHERE AS THE STRUCTURAL SHEET S1
 SHOWS THE DOORS SPLITTING IN THE CENTER AND FOLDING
 EACH WAY. THE FOLDING DOOR SYSTEM THAT SPLITS IN THE
 MIDDLE WILL NOT ALLOW AN ACCESSIBLE ENRY AT THE SWING
 DOOR SINCE THERE WILL NOT BE 18 INCHES CLEAR AT THE
 LATCH SIDE OF THE DOOR 2010 FL ACCESS CODE 404.2.4.1 &
 FIGURE 404.2.4.1(A).
  
 5) THE PLANS DO NOT HAVE ANY DETAILS AS FAR AS THE SILL
 FOR TTHE FOLDING DOOR SYSTEM, PLEASE PROVIDE COMPLIANCE
 WITH 2010 FL ACCESS CODE 404.2.5 THRESHOLDS.
 THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH
 (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES IN
 LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND 303.
  
 6) SHEET A1.1 THE FRONT EXIT ENCLOSURE BOTH 1ST FLOOR &
 2ND FLOOR LANDINGS SHOW THE ELEVATOR LOCATED IN THE
 EXIT ENCLOSURE. PLEASE REVIEW 2010 FBC-B 1022.3 &
 1022.4.
 2010 FBC-B 1022.3
 EXIT ENCLOSURE OPENING PROTECTIVES SHALL BE IN
 ACCORDANCE WITH THE REQUIREMENTS OF SECTION 715.
  
 OPENINGS IN EXIT ENCLOSURES OTHER THAN UNPROTECTED
 EXTERIOR OPENINGS SHALL BE LIMITED TO THOSE NECESSARY
 FOR EXIT ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED
 SPACES AND FOR EGRESS FROM THE ENCLOSURE.
  
 ELEVATORS SHALL NOT OPEN INTO AN EXIT ENCLOSURE.
  
 2010 FBC-B 1022.4 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 VENTILATION OR PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING
 THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT
 EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 713.
 THERE SHALL BE NO PENETRATIONS OR COMMUNICATION
 OPENINGS, WHETHER PROTECTED OR NOT, BETWEEN ADJACENT
 EXIT ENCLOSURES.
  
 6A)(1) 2010 FBC-B 707.3.2 EXIT ENCLOSURES. THE
 FIRE-RESISTANCE RATING OF THE FIRE BARRIER SEPARATING
 BUILDING AREAS FROM AN EXIT SHALL COMPLY WITH SECTION
 1022.1.
  
 6A)(2) 2010 FBC-B 708.5 CONTINUITY. SHAFT ENCLOSURES
 SHALL BE CONSTRUCTED AS FIRE BARRIERS IN ACCORDANCE
 WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 712, OR BOTH, AND SHALL HAVE
 CONTINUITY IN ACCORDANCE WITH SECTION 707.5 FOR FIRE
 BARRIERS OR SECTION 712.4 FOR HORIZONTAL ASSEMBLIES AS
 APPLICABLE.
  
 6A)(3) 2010 FBC-B 707.5 CONTINUITY. FIRE BARRIERS SHALL
 EXTEND FROM THE TOP OF THE FOUNDATION OR FLOOR/CEILING
 ASSEMBLY BELOW TO THE UNDERSIDE OF THE FLOOR OR ROOF
 SHEATHING, SLAB OR DECK ABOVE AND SHALL BE SECURELY
 ATTACHED THERETO. SUCH FIRE BARRIERS SHALL BE
 CONTINUOUS THROUGH CONCEALED SPACES, SUCH AS THE SPACE
 ABOVE A SUSPENDED CEILING. SHEET A3.1 DETAIL A1 SHOWS A
 DETAIL FOR A 1 HR FIRE RATED WALL, BUT THE DETAIL DOES
 NOT INDICATE HOW IT WILL DEAL WITH A WOOD FLOOR TRUSS
 SYSTEM, OR HOW THE FIRE RATING MAY OCCUR AROUND
 HEADERS, AND WOOD BUILT UP FLOOR TRUSS GIRDERS.
  
 7) SHEET A1.1 LIFE SAFETY PLAN IS MISSING THE RATING OF
 WALLS AND DOORS:
 7A) THE FRONT AND REAR STAAIRWELLS DO NOT INDICATTE A 1
 HOUR FIRE RATED WALL ALL THE WAY AROUND THE ENCLOSURE,
 2010 FBC-B 1022.1 AND THE REQUIRED FIRE RATED DOORS PER
 2010 FBC-B 715 & TABLE 715.4 1 HOUR RATED DOORS .
  
 7B) THE ELEVATOR MACHINE ROOM 2010 FBC-B 3006.4. PLEASE
 NOTTE THE CEILING OF THIS ROOM WILL NEED TO BE FIRE
 RATED AS WELL IT WILL ABUT THE FRAMING MEMBERS OF THE
 STAIRWELL. 2010 FBC-B 1022.1 & 707 HORIZONTAL
 ASSEMBLIES. DOOR RATING 3/4 HR FIRE BARRIER TABLE
 715.4.
  
 8) UNDER THE 03060274 PERMIT THE STAIR ENCLOSURE AND
 ELEVATOR WERE A DIFFERENT CONFIGURATION, THE PLANS DO
 NOT IDENTIFY ANY CHANGES TO THE FLOOR FRAMING
 RECONFIGURATION? ADDITIONAL INFORMATION IS REQUIRED,
 107.2.1.3. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION.
  
 9) SHEET A2.1 HAS (3) AREAS WHERE WHITE OUT HAS BEEN
 USED ON THE PLANS. 107.2.1.4 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 2012. QUALITY OF BUILDING
 PLANS. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. OTHER THAN THE
 RECONFIGURATION OF THE EXIT ENCLOSURE SHOWS NO WORK TO
 BE COMPLETED UNDERTHIS PERMIT.
  
  
  
 10) STRUCTURAL SHEET S-1:
  
 10A) STRUCTURAL SHEET ELEVATOR DETAIL IS MISSING THE
 FOLLOWING :
 10A)(1) TB- HEIGTH NOT PROVIDED.
 10A)(2) B-24 THE HEIGHT OF THE BEAM TOP OR BOTTOM OF
 BEAM NOT PROVIDED
 10A)(3) ELEVATOR DOES NOT SHOW A PIT OR RECESS FOR THE
 FLOOR OF THE ELEVATOR CAB TO BE LEVEL WITH THE FLOOR.
 10)(4) THE ELEVATOR SHAFT DOES NOT CONTINUE THROUGH THE
 SECOND FLOOR.
 10)(5) SHAFT ENCLOSURE, 2010 FBC-B 708.12 ENCLOSURE AT
 THE TOP. A SHAFT ENCLOSURE THAT DOES NOT EXTEND TO THE
 UNDERSIDE OF THE ROOF SHEATHING, DECK OR SLAB OF THE
 BUILDING SHALL BE ENCLOSED AT THE TOP WITH CONSTRUCTION
 OF THE SAME FIRE-RESISTANCE RATING AS THE TOPMOST FLOOR
 PENETRATED BY THE SHAFT, BUT NOT LESS THAN THE
 FIRE-RESISTANCE RATING REQUIRED FOR THE SHAFT
 ENCLOSURE.
  
  
 10B) STEEL COLUMNS & W 16X31 BEAM
  
 10B)(1) PLANS CALL FOR 5X5X5/16 OR 5 INCH DIA X ).258
 STEEL COLUMNS. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION 2012 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
 10B)(2) PLANS DO NOT PROVIDE THE SIZE FOR THE COLUMN
 BASE PLATE NOR TOP PLATE, THICKNESS, MATERIAL NOR THE
 BOLT LOCATION IN THE PLATE OR IF WELDED. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION, 2010 EDITION 2012 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH DRAWINGS
 AND SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE
 FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES.
  
 10B)(3) NEW BATHROOM BEARING WALL DETAIL.DETAIL # 2
 ONLY SHOWS THE BOTTOM OF THE STUD WALL DOES NOT
 INDICATE IF A SINGLE TOP PLATE IS REQUIRED OR IF DOUBLE
 TOP PLATE WILL BE REQUIRED? THE OTHER ISSUE IS WILL A
 STIFFNEER BE REQUIRED AS IN DETAIL # 3 FOR THE NEW
 CARRYING W 16X31 STEEL BEAM? IF SO WHAT TYPE OF
 MATERIALS AND NAILING PATTERN.
  
 10C) FRONT ENTRY REDESIGN:
 10C)(1) MISSING PRODUCT APPROVALS 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:(31)(A) EXTERIOR DOORS.
  
 10C)(2) MISSING DIMENSIONS, NO INFORMATION FOR VERTICAL
 NOR HORIZONTAL STEEL FRAMING MEMBERS, PRODUCT APPROVALS
 WILL NEED TO BE DECIDED TO BE ABLE TO PRODUCE THE
 SIZING OF THE ROUGH OPENING. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 107.2.1.3 ADDITIONAL DATA.
 THE BUILDING OFFICIAL MAY REQUIRE DETAILS,
 COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA NECESSARY
 TO DESCRIBE THE CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATIONS. ALL DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA REQUIRED BY THE BUILDING OFFICIAL TO
 BE PREPARED BY AN ARCHITECT OR ENGINEER SHALL BE
 AFFIXED WITH THEIR OFFICIAL SEAL, SIGNATURE AND DATE AS
 STATE LAW REQUIRES.
  
  
 11) SHEET A3.1 DEATIL # 4 INDICATES THE INSTALATION OF
 DROP CEILINGS, NOTE # 6 INDICATES THE TYPE OF FASTENERS
 TO BE USED IF THE INSTALATION IS FOR CONCRETE DECKS BUT
 NOT FOR WOOD FRAMED TRUSSES WITH METAL HI HAT FRAMING
 BETWEEN THE 5/8 INCH DRYWALL AND FLOOR TRUSS. 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.2.1.3
 ADDITIONAL DATA.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-04-07 Cont ID  
Sent By dhayes Date 2015-04-07 Time 12:53 Rev Time 0.00
Received By dhayes Date 2015-04-07 Time 12:53 Sent To  
Notes
2015-04-07 12:55:574/7/15
 PROJECT: 525 CLEMATIS
 PERMIT#: 14030818
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 4TH ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION.
  
 1) ATOMIC TIMER IS NOT APPROVED FOR LIGHTING CONTROL AS
 DEFINED IN THE FBC 505.2 REVISE PLANS AND INSTALLATION
 FOR AN APPROVED LIGHTING CONTROL METHOD. FBC - E 505.2
  
 2) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. NEC 408.4. REVISE PANEL
 SCHEDULE TO COMPLY.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
2015-04-01 09:23:40NEW DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-12-17 Cont ID  
Sent By dhayes Date 2014-12-17 Time 15:51 Rev Time 0.00
Received By dhayes Date 2014-12-17 Time 14:17 Sent To  
Notes
2014-12-17 15:50:1312/17/2014
 PROJECT: 525 CLEMATIS
 PERMIT#: 14030818
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION.
  
 1) ATOMIC TIMER IS NOT APPROVED FOR LIGHTING CONTROL AS
 DEFINED IN THE FBC 505.2 REVISE PLANS AND INSTALLATION
 FOR AN APPROVED LIGHTING CONTROL METHOD
  
 2) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. NEC 408.4. REVISE PANEL
 SCHEDULE TO COMPLY.
  
 3) PROVIDE A COMPREHENSIVE AS BUILT REVISION FOR
 ELECTRICAL LOAD SUMMARY CALCULATION BASED ON NEC
 ARTICLE 220,
  
 4) REVISE THE ELECTRICAL SERVICE RISER DIAGRAM WITH
 SIZES OF ALL CONDUIT AND WIRE,
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-09-30 Cont ID  
Sent By rlecky Date 2014-09-30 Time 13:46 Rev Time 0.00
Received By rlecky Date 2014-09-30 Time 13:27 Sent To  
Notes
2014-09-30 13:48:1114030818
 526 CLEMATIS ST.
 INTERIOR RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS. MANY OF THESE COMMENTS WERE PREVIOUSLY
 PROVIDED ( 4/3/14) ON THE FIRST REVIEW.
  
  
 VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A
 FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL
 CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. SHOW THE FAULT CURRENT RATING OF THE MAIN
 DISCONNECTS AND PANELBOARDS. NEC 110.9
  
 PROVIDE A SUMMARY LOAD CALCULATION. NEC 220.14; 220.40
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.22, 110.16, 110.22
  
 ON THE ELECTRIC PLAN SHOW ALL REQUIRED ACCESS AND SAFE
 WORKING CLEARANCES FOR THE ELECTRICAL SERVICE, MAIN
 DISCONNECTS AND PANEL BOARDS. NEC 110.26
  
 ON THE PANEL SCHEDULE INCLUDE THE SHOW WINDOW LIGHTING
 AND A SIGN CIRCUIT. NEC 210.62, 408.4, 600.5
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF SINKS IN THE
 BAR MUST BE GFCI PROTECTED. NEC 210.8
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 PROVIDE LIGHTING CONTROLS FOR ENERGY CONSERVATION SO
 THAT THE INTERIOR AND EXTERIOR LIGHTING CONTROLS
 PROVIDED FUNCTION IN ACCORDANCE WITH THE FLORIDA ENERGY
 CODE. EXTERIOR AUTOMATIC CONTROLS SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. VERIFY THE
 LIGHTING AND SIGN TIME CLOCKS HAVE BATTERY BACKUP. FBC
 ENERGY CONSERVATION 505.2
  
 ON THE ELECTRIC PLAN PROVIDE A LIGHTING SCHEDULE
 SHOWING FIXTURE SELECTION. INCLUDE EXIT LIGHTING WITH
 BATTERY BACKUP. FBC, ENERGY CONSERVATION 502.3.8; FBC
 1011
  
 ADD THE EXIT LIGHTING CIRCUIT TO THE LIGHTING PANEL.
 NEC 408.4
  
 PROVIDE GFCI PROTECTED RECEPTACLES ON THE ROOF TO
 SERVICE THE MECHANICAL EQUIPMENT ON THE ROOF. NEC
 210.8(B), 210.63
  
 REVISE ELECTRICAL RISER PLAN TO SHOW PANEL ?EV?. SHOW
 FEEDER SIZE FOR PANEL ?B?. PROVIDE OVER CURRENT
 PROTECTION FOR PANEL ?A?. SHOW LOCATION OF PANEL ?A?.
 NEC 215.5
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE
 ELEVATOR, ALARM SYSTEMS, SECURITY AND DATA SYSTEMS.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-04-03 Cont ID  
Sent By rlecky Date 2014-04-03 Time 14:13 Rev Time 0.00
Received By rlecky Date 2014-04-03 Time 12:06 Sent To  
Notes
2014-04-03 14:23:1914030818
 526 CLEMATIS ST.
 INTERIOR RENOVATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 SHOW THE LOCATION OF ALL ELECTRICAL SERVICES WITH MAIN
 DISCONNECTS WHICH ARE SERVING THIS LOCATION. INCLUDE AN
 ELECTRICAL DEMOLITION PLAN FOR THE ANY EXISTING SERVICE
 OR INTERIOR ELECTRIC BEING RENOVATED. NEC 230.2,
 230.71, 230.72
  
 SHOW THE FEEDERS AND LOCATION FOR ALL MECHANICAL
 EQUIPMENT CIRCUITS AND DISCONNECTS. NEC 215.5
  
 VERIFY THE EXISTING OCCUPANCY AND PANEL SCHEDULE
 INCLUDE THE SHOW WINDOW LIGHTING AND A SIGN CIRCUIT.
 NEC 210.62; 600.5
  
 VERIFY THE ELECTRICAL SERVICE MAINS SERVING THIS
 BUILDING ARE SIX OR LESS AND GROUPED IN ONE LOCATION.
 NEC 230.2, 230.71, 230.72
  
 SHOW ALL METERS, GROUNDING, MAIN DISCONNECTS, FEEDERS
 AND PANEL BOARDS FOR THE BUILDING SERVICE INCLUDING ALL
 OTHER EXISTING OCCUPANCIES REQUIRING ELECTRICAL
 SERVICE.
 NEC 215.5, 230.2, 230.71, 230.72
  
 VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A
 FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL
 CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 VERIFY THE ELECTRICAL SERVICE LOAD IS NOT LESS THAN THE
 SUM OF ALL LOADS AS REQUIRED. NEC 215.5; 220.40
  
 PROVIDE A SUMMARY LOAD CALCULATION. NEC 220.14; 220.40
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.22, 110.16, 110.22
  
 ON THE ELECTRIC PLAN VERIFY AND SHOW ALL REQUIRED
 ACCESS AND SAFE WORKING CLEARANCES FOR THE ELECTRICAL
 SERVICE, MAIN DISCONNECT, ELEVATOR CONTROLLERS,
 ELEVATOR DISCONNECTS AND ALL PANELBOARDS. INCLUDE THE
 SECOND FLOOR. NEC 110.26; 620.5
  
 INCLUDE THE REQUIRED ELEVATOR BRANCH CIRCUITS ON THE
 PANEL SCHEDULE AND IN THE LOAD CALCULATION. NEC 110.22;
 408.4; 620.23, 620.24
  
 REVISE THE ELECTRIC PANEL DIRECTORY SO THAT ALL
 CIRCUITS ARE IDENTIFIED AS TO THEIR SPECIFIC PURPOSE OR
 USE. INCLUDE ALL CIRCUITS FEEDING THE SECOND FLOOR. NEC
 408.4
  
 ADD THE EXIT LIGHTING CIRCUIT TO THE LIGHTING PANEL.
 NEC 408.4
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF SINKS IN THE
 BAR MUST BE GFCI PROTECTED. NEC 210.8
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 VERIFY THE REQUIRED GFCI PROTECTED RECEPTACLE IS
 AVAILABLE TO SERVICE THE MECHANICAL EQUIPMENT. NEC
 210.8(B)
  
 ON THE ELECTRIC PLAN PROVIDE A LIGHTING SCHEDULE
 SHOWING FIXTURE SELECTION INCLUDING EXIT LIGHTING WITH
 BATTERY BACK UP. FBC, ENERGY CONSERVATION 502.3.8; FBC
 1011
  
 INDICATE THE LOCATION OF THE ELEVATOR PANELBOARD. NEC
 215.5
  
 SHOW REQUIRED RECEPTACLES IN ELEVATOR EQUIPMENT ROOMS
 AND PITS WITH GFCI PROTECTION. NEC 620.23, 620.85
  
 A SEPARATE BRANCH CIRCUIT SHALL SUPPLY ELEVATOR CAR
 LIGHTS. NEC 620.22
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE
 ELEVATOR, ALARM SYSTEMS, SECURITY AND DATA SYSTEMS.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-05-08 Cont ID  
Sent By cranford Date 2015-05-08 Time 10:59 Rev Time 0.00
Received By mgonzale Date 2015-05-08 Time 10:47 Sent To  
Notes
2015-06-09 16:05:33SANITATION REQUIREMENTS:
  
 AFTER MEETING WITH THE DEVELOPER HE HAS AGREED TO
 OBTAIN A SEPARATE PERMIT FOR DUMPSTER AREA. ON THAT
 PERMIT HE WILL ADDRESS THE LOCATIONS OF THE DUMPSTERS
 INTENDED TO BE SERVICE BY THE CITY OF WEST PALM BEACH
 SANITATION DEPARTMENT. DUMPSTER MUST BE EASILY
 ACCESSIBLE BY THE CITY EQUIPMENT AND MANPOWER. THE
 MAXIMUM SIZE PROVIDED BY THE CITY BASED ON THE AREA
 DESCRIBED BY THE DEVELOPER IS 3 CU YD. DUMPSTER WHICH
 DEVELOPER AGREES TO ROLL OUT AND MAKE ACCESSIBLE. A
 HOLD WILL BE PLACED FOR INSPECTIONS ON THIS PERMIT
 UNTIL DUMPSTER PERMIT HAS BEEN APPLIED FOR.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  
  
  
  
  
2015-05-08 10:58:221. DEMONSTRATE THAT THE PROPOSED DUMPSTER LOCATION IS
 ACCESSIBLE TO THE SOLID WASTE TRUCKS (35 FT LONG, 15 FT
 HIGH). IF IT IS INTENDED FOR DEVELOPER'S STAFF TO ROLL
 FULL TRASH BINS INTO THE ALLEY, THE LOCATION MUST NOT
 WILL IMPEDE TRAFFIC FLOW WHILE THE BINS ARE IN THE
 ALLEY OR COMPLETELY BLOCK TRAFFIC WHEN THE SOLID WASTE
 TRUCKS ARE COLLECTING THE GARBAGE. SECTION 74-35(A)(5)
 OF THE CODE OF ORDINANCES.
  
 2. PROVIDE CALCULATIONS VERIFYING THAT THE PROPOSED
 SIZE AND QUANTITY OF TRASH BINS IS APPROPRIATE FOR THE
 WASTE YARDAGE ANTICIPATED TO BE GENERATED BY NEW USES
 IN THE BULDING.
  
 3. WILL FOOD BE PREPARED OR SERVED IN THE BUILDING? IF
 SO, PLEASE INDICATE THE LOCATION OF THE GREASE TRAP
 INTERECEPTOR AND SUBMIT FOR A SEPARATE INTERCEPTOR
 PERMIT.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-05-06 Cont ID  
Sent By pleduc Date 2015-05-06 Time   Rev Time 0.00
Received By pleduc Date 2015-05-06 Time 09:13 Sent To  
Notes
2015-05-06 09:47:59THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 ADD EXIT SIGNS WHERE HAND DRAWN ON PLAN TO PROVIDE
 CLEAR DIRECTION OF EXIT PATH.
  
 FIRE INSPECTOR SHALL FIELD VERIFY ON FIRE INSPECTION.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-04-02 Cont ID  
Sent By pleduc Date 2014-04-02 Time 2:02 Rev Time 0.00
Received By pleduc Date 2014-04-02 Time 12:50 Sent To E
Notes
2014-04-02 13:44:06THE PERMIT PLAN WAS REVIEWED AND APPROVED WITH THE
 FOLLOWING COMMENTS BY PETER LEDUC, FIRE MARSHAL, BUREAU
 OF FIRE PREVENTION, WEST PALM BEACH FIRE RESCUE.
  
 1. A FIRE SPRINKLER AND FIRE ALARM SYSTEM IS REQUIRED
 FOR THIS PROJECT.
  
 2. ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO
 BE COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR
 AND SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS,
 ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY
 THE FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE
 SYSTEM.
  
 3. ALL FIRE ALARM SYSTEM WORK SHALL BE DONE BY A
 CERTIFIED FIRE ALARM CONTRACTOR AND COMPLY WITH NFPA
 72. A SEPARATE SHOP DRAWING IS REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
  
 4. CURRENT LIFE SAFETY SYSTEMS, SPRINKLER AND/OR FIRE
 ALARM, SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION
 PERIOD.
  
 5. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 6. NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.
  
 7. TWO (2) ADDITIONAL EXIT SIGNS ARE REQUIRED AS
 INDICATED DUE TO THE PROPOSED EXIT SIGNS BEING NOT
 VISIBLE FROM THE OCCUPIED AREAS THEY SERVE.
  
 8. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2015-05-05 Cont ID  
Sent By fmittner Date 2015-05-05 Time 16:18 Rev Time 0.00
Received By fmittner Date 2015-05-05 Time 16:18 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2014-10-10 Cont ID  
Sent By fmittner Date 2014-10-10 Time 14:25 Rev Time 0.00
Received By fmittner Date 2014-10-10 Time 14:25 Sent To  
Notes
2014-10-10 14:47:09MUST HAVE SEPARATE AWNINGS ON FACADE.....NOT PART OF
 THIS SCOPE.....WILL REVIEW FROM AWNING CONTRACTOR
2014-10-10 14:26:15C13

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-03-21 Cont ID  
Sent By aaponte Date 2014-03-21 Time 09:18 Rev Time 0.00
Received By aaponte Date 2014-03-21 Time 09:18 Sent To  
Notes
2014-03-21 09:19:34PROVISO: AWNINGS SHALL BE SEPARATED INTO TWO, ONE OVER
 DOOR AND ONE OVER MAIN STOREFRONT WINDOWS.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2015-05-14 Cont ID  
Sent By jwitmer Date 2015-05-14 Time 14:28 Rev Time 0.00
Received By jwitmer Date 2015-05-12 Time 15:23 Sent To  
Notes
2015-05-13 15:24:04PLANS WITH COUNTY IMPACT FEES STAMP SENT TO JIM WITMER
 FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-05-06 Cont ID  
Sent By pleduc Date 2015-05-06 Time   Rev Time 0.00
Received By pleduc Date 2015-03-31 Time 09:21 Sent To  
Notes
2015-04-01 09:22:33RE-SUBMITTAL SENT TO C10 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-03-13 Cont ID  
Sent By shill Date 2015-03-13 Time 12:38 Rev Time 0.00
Received By shill Date 2015-02-05 Time 07:26 Sent To  
Notes
2015-02-06 07:30:32C10

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-12-29 Cont ID  
Sent By hmoser Date 2014-12-29 Time 13:20 Rev Time 0.00
Received By hmoser Date 2014-11-19 Time 16:24 Sent To  
Notes
2014-11-24 16:25:19RE-SUBMITTAL SENT TO C10 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-15 Cont ID  
Sent By tklarge Date 2014-10-15 Time 08:50 Rev Time 0.00
Received By tklarge Date 2014-09-29 Time 16:57 Sent To  
Notes
2014-09-29 16:58:19RE-SUBMITTAL SENT TO C13 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-24 Cont ID  
Sent By hmoser Date 2014-04-24 Time 13:13 Rev Time 0.00
Received By hmoser Date 2014-03-21 Time 10:47 Sent To  
Notes
2014-03-24 10:52:49INCOMING SENT TO C-05. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status N Date 2015-05-14 Cont ID  
Sent By jwitmer Date 2015-05-14 Time 14:25 Rev Time 0.00
Received By jwitmer Date 2015-05-14 Time   Sent To  
Notes
2015-05-14 14:26:11P. B. C. IMPACT FEES
 PLANS STAMPED NO FEES DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2015-04-25 Cont ID  
Sent By jwitmer Date 2015-04-25 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2015-04-25 Time 14:14 Sent To  
Notes
2015-04-25 13:59:40IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2014-12-08 Cont ID  
Sent By jwitmer Date 2014-12-08 Time 13:19 Rev Time 0.00
Received By jwitmer Date 2014-12-08 Time 13:19 Sent To  
Notes
2014-12-08 13:19:30BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-10-08 Cont ID  
Sent By jwitmer Date 2014-10-08 Time 08:16 Rev Time 0.00
Received By jwitmer Date 2014-10-08 Time 08:16 Sent To  
Notes
2014-10-08 08:16:47BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-04-16 Cont ID  
Sent By jwitmer Date 2014-04-16 Time 07:12 Rev Time 0.00
Received By jwitmer Date 2014-04-16 Time 07:12 Sent To  
Notes
2014-04-16 07:12:21BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2017-05-10 Cont ID  
Sent By hmoser Date 2017-05-10 Time 13:40 Rev Time 0.00
Received By hmoser Date 2017-05-10 Time 13:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-03-10 Cont ID  
Sent By HMOSER Date 2015-03-10 Time 13:48 Rev Time 0.00
Received By hmoser Date 2015-03-10 Time 10:43 Sent To  
Notes
2015-03-10 13:47:57PASS PROVISO
 1) REFER TO SECTION 304.1 GENERAL. PERVADE THE
 MANUFACTURER'S
 INSTALLATION INSTRUCTIONS ON THE AIR CONDITIONING
 EQUIPMENT
 BY FINAL INSPECTION. (AND CLOTHS DRYER)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2014-12-29 Cont ID  
Sent By hmoser Date 2014-12-29 Time 13:20 Rev Time 0.00
Received By hmoser Date 2014-12-29 Time 10:10 Sent To  
Notes
2014-12-29 13:20:23PLAN DENIED
 1) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S
 2010 FBC (M) DOORS ARE PART OF PLENUM.
 2) REFER TO SECTION 301.12 WIND RESISTANCE. PROVIDE
 A DETAIL FROM THE ENGINEER ON CURB TIEDOWN TO ROOF,
 CONDENSER STAND TIE DOWN TO ROOF, RTU TIEDOWN TO
 CURB, CONDENSER TIEDOWN TO STAND ON MECHANICAL PLAN.
 3) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM, 606.3
 INSTALLATION, 606.4.1 SUPERVISION FBC (M) 2010
 4) REFER TO SECTION 304.1 GENERAL 2010 FBC (M)
  
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-10-08 Cont ID  
Sent By rbergsma Date 2014-10-08 Time   Rev Time 0.50
Received By rbergsma Date 2014-10-08 Time   Sent To  
Notes
2014-10-08 14:19:31PREVIOUS MECHANICAL COMMENTS WERE NOT ADDRESSED
 ALSO -------- THE M-1 SHEETS IN TWO OF THE PLANS
 SUBMITTED ARE TO LIGHT TO READ
 AND THE THIRD M-2 IS DIFFERENT THAN THE OTHER TWO M-2
 'S
  
 CORRECT AND RESUBMIT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-04-24 Cont ID  
Sent By hmoser Date 2014-04-24 Time 13:12 Rev Time 0.00
Received By hmoser Date 2014-04-24 Time 12:38 Sent To  
Notes
2014-04-24 13:12:43MECHANICAL PLAN DENIED
 1) PROVIDE ENERGY CALCULATION WITH THE
 PLAN PER SECTION 503.2.1 CALCULATION
 OF HEATING AND COOLING LOADS. 2010
 FLORIDA ENERGY CODE.
 2) PROVIDE A DETAIL FROM THE ENGINEER
 ON THE CURB TO ROOF TIEDOWN AND CONDENSER
 TO CURB TIEDOWN .
 PROVIDE TYPE OF FASTENERS SIZE AND HOW FAR APART
 PER SECTION 303.12 WIND RESISTANCE 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 5 Status P Date 2015-04-23 Cont ID  
Sent By tklarge Date 2015-04-23 Time 13:32 Rev Time 0.00
Received By tklarge Date 2015-04-23 Time 11:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2015-02-15 Cont ID  
Sent By TKLARGE Date 2015-02-15 Time 04:34 Rev Time 0.00
Received By tklarge Date 2015-02-13 Time 11:05 Sent To  
Notes
2015-02-15 04:32:33PLEASE CONTACT ME AT 561-805-6692 TO MAKE AN
 APPOINTMENT TO COME IN AND REVIEW THE WATER AND
 SANITARY RISERS. THERE ARE TOO MANY CODE ISSUES TO LIST
 IN A CODE REVIEW.THANK YOU. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2014-11-27 Cont ID  
Sent By tklarge Date 2014-11-27 Time 09:28 Rev Time 0.00
Received By tklarge Date 2014-11-27 Time 07:59 Sent To  
Notes
2014-11-27 09:28:371)TABLE 403.1 FOOTNOTE "G" OF 2010 FL. PLUMBING CODE
 REQUIRES A UNISEX BATHROOM IN ASSEMBLY OCCUPANCIES
 WHERE AN AGGREGATE OF SIX OR MORE MALE AND FEMALE WATER
 CLOSETS ARE REQUIRED IN ACCORDANCE WITH THE 2010 FPC
 SEC.403.5. SHOW THE REQUIRED UNISEX TOILET ROOM ON THE
 PLANS AND PROVIDE A SANITARY AND WATER RISER FOR
 REVIEW. 2ND REQUEST. THE UNISEX TOILET ROOM SHALL
 COMPLY WITH THE FL. ACCESSIBILITY CODE.
 2) SUBMIT AN ENLARGED RESTROOM FLOOR PLAN FOR THE FIRST
 FLOOR. SHOW ALL REQUIRED FLOOR SPACE FOR THE
 HANDICAPPED FIXTURES. THE RESTROOMS SHALL FULLY COMPLY
 WITH THE 2010 FL. ACCESSIBILITY CODE.THE TOILET
 COMPARTMENTS SHALL COMPLY WITH FAC SEC.604.8.1.6.SINCE
 THIS IS A CHANGE OF OCCUPANCY. 2ND REQUEST.
 3) SHT. P-2 - THE FIRST FLOOR SANITARY PLAN IS DRAWN
 VERY LIGHT AND IS DIFFICULT TO READ. SUBMIT A PLAN THAT
 IS CLEAR IN DETAIL AND LEGIBLE. WPB AMEND. TO 2001 FBC
 SEC. 107.2.1. 2ND REQUEST.
 4) THE RESTROOMS ON THE 2ND FLOOR SHALL FULLY COMPLY
 WITH THE FL. ACCESSIBILITY CODE. THE TOILET
 COMPARTMENTS SHALL COMPLY WIT FAC SEC.604.8.1.6.SHOW
 ALL THE REQUIRED CLEAR FLOOR SPACE PER FAC SEC. 306 &
 604.3.2ND REQUEST.
 5) SHT. P-4 - THE 2ND FLOOR SANITARY ISOMETRIC FOR THE
 WOMEN'S RESTROOM #205 HAS A DRY VENT FOR THE P-1
 FIXTURE. EVERY DRY VENT CONNECTING TO A HORIZONTAL
 DRAIN SHALL COMPLY WITH THE 2010 FPC SEC.905.3. 2ND
 REQUEST.
 6) THE FLOOR DRAINS ON THE FIRST FLOOR SANITARY
 ISOMETRIC ARE NOT VENTED. PROVIDE THE PROPER SIZE VENTS
 PER THE FPC SEC.906.1, 901.2. 2ND REQUEST.
 7) THE P-5 FIXTURE SHALL BE PROPERLY TRAPPED. FPC
 1002.1. 2ND REQUEST.
 8) THE SINGLE FLOOR DRAIN IN THE BAR AREA (#209) IS NOT
 VENTED.FPC SEC.906.1.2ND REQUEST.
 9)THE NUMBER OF WATER CLOSETS BEING WET VENTED IN THE
 FIRST AND SECOND FLOOR RESTROOMS EXCEEDS THE NUMBER
 PERMITTED BY FPC SEC. 909. ALSO, URINALS ARE NOT
 PERMITTED ON THE HORIZONTAL WET VENTS. 2ND REQUEST.
 10) SHT. P-3 - THE 2ND FLOOR DOMESTIC (WATER PLAN) IS
 DRAWN VERY LIGHT AND IS DIFFICULT TO READ. SUBMIT A
 PLAN THAT IS CLEAR IN DETAIL AND LEGIBLE. WPB AMEND. TO
 2001 FBC SEC. 107.2.1.
 11) THE RESPONSE NARRATIVE FROM ELLIS & GRITTER
 ADDRESSES COMMENTS FROM THE APRIL REVIEW NOT THE
 NOVEMBER REVIEW.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-11-27 Cont ID  
Sent By tklarge Date 2014-10-14 Time 07:59 Rev Time 0.00
Received By tklarge Date 2014-10-14 Time 14:47 Sent To  
Notes
2014-10-14 15:04:381) NEITHER THE COVERSHEET NOR ANY OF THE PLUMBING
 SHEETS PROVIDE THE REQUIRED MINIMUM FIXTURE COUNT PER
 THE 2010 FBC-PLUMBING, TABLE 403.1.
 2) FOOTNOTE "G" OF TABLE 403.1 OF THE 2010
 FBC-PLUMBING, REQUIRES A UNISEX BATHROOM IN MERCANTILE
 AND ASSEMBLY OCCUPANCIES WHERE AN AGGREGATE OF SIX OR
 MORE MALE AND FEMALE WATER CLOSETS ARE REQUIRED.
 3) SUBMIT AN ENLARGED RESTROOM FLOOR PLAN FOR THE THE
 FIRST FLOOR.
 4) THE RESTROOMS ON THE SECOND FLOOR SHALL COMPLY WITH
 THE FLORIDA ACCESSIBILITY CODE FOR BUILING
 CONSTRUCTION.
 5) SHT. P-2 - THE 1ST FLOOR SANITARY PLAN IS ILLEGIBLE.
 SUBMIT A PLAN THAT IS CLEAR IN DETAIL. WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 6) THE 2ND FLOOR SANITARY ISOMETRIC HAS DRY VENTS FOR
 THE P-1 FIXTURES. EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE PER THE 2010 FPC SEC.905.3.
 7) THE FLOOR DRAINS ON THE FIRST FLOOR ARE NOT VENTED.
 FPC SEC.906.1. 901.2.
 8) THE SANITARY LINE FOR FIXTURE P-1 ON THE FIRST FLOOR
 CONNECTS TO NOTHING. CLARIFY.
 9) P-5 FIXTURES REQUIRE TRAPS.
 10) THE SINGLE FLOOR DRAIN IN THE BAR AREA ON THE
 SECOND FLOOR IS NOT VENTED. FPC SEC.906.1
 11) THE NUMBER OF WATER CLOSETS BEING WET VENTED IN THE
 SECOND FLOOR RESTROOMS EXCEEDS THE NUMBER PERMITTED BY
 SEC.909 OF THE FPC. ALSO, URINALS ARE NOT PERMITTED ON
 A WET VENT.
 12) BASED ON THE SHOWN OCCUPANT LOAD, THE MINIMUM
 NUMBER OF REQUIRED PLUMBING FIXTURES ARE AS FOLLOWS:
 A) 7 WATER CLOSETS, 4 LAVS FOR THE MALES
 B) 7 WATER CLOSETS, 4 LAVS FOR THE FEMALES
 C) 1 SERVICE SINK
 D) 2 DRINKING FOUNTAINS
 13) CITY RECORDS ( PERMIT #03060274 ) SHOW THE SECOND
 FLOOR OF THIS BUILDING AS APARTMENTS, WHICH IS AN R-2
 OCCUPANCY. THIS WILL BE CONSIDERED A CHANGE OF
 OCCUPANCY AND MUST COMPLY WITH CHAPT.9 , SECS. 902-913
 OF THE 2010 FBC, EXISTING BUILDING CODE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-04-16 Cont ID  
Sent By jwitmer Date 2014-04-16 Time 08:44 Rev Time 0.00
Received By jwitmer Date 2014-04-16 Time 07:26 Sent To  
Notes
2014-04-16 08:44:54PLUMBING PLAN REVIEW
 PERMIT: 14030818
 ADD: 526 CLEMATIS ST 1ST FLOOR CHANGE OF OCCUPANY/
 EXTERIOR ALTERATIONS
 CONT: JM PROPERTIES OF WEST PALM BEACH, INC
 TEL: (561)756-5744
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BLDG TYPE III-B SPRINKLERED
  
 1ST REVIEW
 DATE: WED. APRIL 16/ 2014
 ACTION: DENIED
  
 THE LAST RENOVATIONS TO THIS BUILDING UNDER PERMIT
 03060274, FIRST FLOOR MERCANTILE AND THE 2ND FLOOR R2
 APARTMENTS, THIS REVIEW WILL BE CONSIDERED A CHANGE IN
 OCCUPANCY AND CHAPTER 9 OF THE EXISITNG BUILDING CODE.
 901.3 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
  
 1) THE COVERSHEET A0.0 INDICATES THE 1ST FLOOR
 OCCUPANCY CLASSIFICATION AS A A-3, THE PLANS APPEAR TO
 BE A NIGHTCLUB OR BAR / TAVERN WHICH IS A A2 OCCUPANCY,
 SEE 2010 FBC-B 303.1.
  
 2) NEITHER THE COVERSHEET NOR ANY OF THE PLUMBING
 SHEETS PROVIDE THE REQUIRED MINIMUM FIXTURE COUNT PER
 2010 FBC-P TABLE 403.1.
  
 3) THE PLANS DO NOTSTATE IF THIS TENANCY IS TO BE A
 RESTARAUNT OR A NIGHTCLUB. IF TO BE CONSIDERED A
 RESTARAUNT NO KITCHEN APPLIANCES HAVE BEEN SHOWN
 ALTHOUGH A 3 COMPARTMENT SINK IS SHOWN, PLEASE PROVIDE
 WHAT YPES OF FOOD WILL BE PREPARED. IF A RESTARAUNT
 THEN A SEPARATE PERMIT FOR A GREASE INTERCEPTOR WOULD
 BE REQUIRED. 2010 FBC-P 1003.3.1 GREASE INTERCEPTORS
 AND AUTOMATIC GREASE REMOVAL DEVICES REQUIRED. THE
 STORAGE ROOM APPEARS TO BE SET UP FOR A FUTURE KITCHEN
 WITH HOT AND COLD DOMESTIC WATER AND FLOOR DRAINS?
  
 4) SHEET P3 SANITARY & DOMESTIC ISOMETRIC
  
 4A) FLOOR DRAINS IN RESTROOM & STORAGE ROOM ARE MISSING
 TRAP PRIMERS. 2010 FBC-P 1002.4 TRAP SEALS. EACH
 FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS THAN
 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 MM),
 OR DEEPER FOR SPECIAL DESIGNS RELATING TO ACCESSIBLE
 FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO LOSS BY
 EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE
 TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A
 TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR
 ASSE 1044.
  
 4B) FLOOR DRAINS AND TRAP PRIMER SEALS AND VENTING ARE
 MISSING ON THE SANITARY ISOMETRIC FOR THE STORAGE
 SUPPLY ROOM. 2010 FBC-P 905.3, & 1002.4.
  
 4C) THE URINAL IN THE MENS RESTROOM DOES NOT SHOW ANY
 VENT, NOTE WET VENT SYSTEMS ARE ONLY FOR RESIDENTIAL 1
 & 2 FAMILY USAGE. WOULD REQUIRE A INDIVIDUAL VENT.
 2010 FBC-P 908.1, 909.1 AND BOAF INFORMAL
 INTERPRETATION REPORT # 6090, THESE INTERPRETATIONS ARE
 THE RESULT OF INPUT PROVIDED BY THE BOAF CODE
 DEVELOPMENT COMMITTEE, THE FLORIDA DEPARTMENT OF
 BUSINESS & PROFESSIONAL REGULATION (DBPR), THE
 INTERNATIONAL CODE COUNCIL (ICC) AND
 SUBJECT-MATTER-EXPERTS IN THE CONSTRUCTION
 INDUSTRY/PROFESSIONS.
  
 4D) IN THE MENS RESTROOM THE LAV, URINAL NOR FLOOR
 DRAIN PROVIDE THE TRAP AND PIPE SIZES, 2010 FBC-P TABLE
 709.1.
  
 4E) IN THE FRONT BAR AREA WHERE THE 3 COMPARTMENT SINK,
 HAND SINK AND FLOOR SINK ARE SHOWN ON THE SANITARY
 ISOMETRIC, NONE OF THE BRANCH LINES AND TRAPS ARE
 SIZED, 2010 FBC-P TABLE 709.1.
  
 4F) THE SANITARY ISOMETRIC DOES NOT PROVIDE WHAT SIZE
 ANY OF THE VENTS ARE AND IF REVENTED AND WHICH VENT IS
 GOING THROUGH TO THE ROOF? 2010 FBC-B 903.1.2.
  
 4G) SHEET P2 SHOWS HOT AND COLD WATER BEING BROUGHT
 OVER INTO THE STORAGE ROOM BUT THEY ARE NOT SHOWWN ON
 THE DOMESTIC WATER ISOMETRIC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 5) SHEET P4:
  
 5A) PIPE HANGER DETAILS SHOW I BEAM OR BAR JOIST HANGER
 AND ANCHORS FOR CONCRETE DECKS THE FLOOR SYSTEM IS WOOD
 TRUSS SYSTEM PLEASE SUPPLY THE APPROPRIATE DETAILS FOR
 THE INSTALATION. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 DISCREPANCY IN DETAILS, CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
 2010 FBC-P ;
 308.3 MATERIALS.
 HANGERS, ANCHORS AND SUPPORTS SHALL SUPPORT THE PIPING
 AND THE CONTENTS OF THE PIPING. HANGERS AND STRAPPING
 MATERIAL SHALL BE OF APPROVED MATERIAL THAT WILL NOT
 PROMOTE GALVANIC ACTION.
  
 308.4 STRUCTURAL ATTACHMENT.
 HANGERS AND ANCHORS SHALL BE ATTACHED TO THE BUILDING
 CONSTRUCTION IN AN APPROVED MANNER.
  
 308.5 INTERVAL OF SUPPORT.
 PIPE SHALL BE SUPPORTED IN ACCORDANCE WITH TABLE 308.5.
  
 5B) WATER HEATER RACK MOUNTING DETAIL, PLEASE PROVIDE
 INFORMATION ON THE RACK, RACK CARRYING CAPACITY AND
 TYPE OF ANCHORS TO BE USED AND TYPE OF MATERIAL THE
 ANCHORS WILL FASTENING INTO. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. .
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-05-05 Cont ID  
Sent By aaponte Date 2015-05-05 Time 09:09 Rev Time 0.00
Received By aaponte Date 2015-05-05 Time 09:09 Sent To  
Notes
2015-05-05 09:23:36PROVISO: DUMPSTER SHALL BE ENCLOSED AND SCREENED
 ACCORDING TO CITY CODE.
 2. ALCOHOL LICENSE FOR A BAR/CLUB IS SUBJECT TO CITY
 COMMISSION APPROVAL.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 2 Status P Date 2014-10-10 Cont ID  
Sent By aaponte Date 2014-10-10 Time 13:42 Rev Time 0.00
Received By aaponte Date 2014-10-10 Time 13:42 Sent To  
Notes
2014-10-10 13:47:55PROVISO: DUMPSTER SHALL BE ENCLOSED AND SCREENED.
 ALCOHOL LICENSE IS SUBJECT TO CITY COMMISSION APPROVAL.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-03-27 Cont ID  
Sent By aaponte Date 2014-03-27 Time 08:55 Rev Time 0.00
Received By aaponte Date 2014-03-27 Time 08:55 Sent To  
Notes
2014-03-27 12:14:521. PLEASE PROVIDE A SURVEY OF THE PROPERTY.
 2. DOORS CANNOT OPEN INTO THE SETBACK AREA OR ROW.
 PLEASE INDICATE THE PROPERTY LINE ON FLOOR PLANS.
 3. DUMPSTER SHALL BE ENCLOSED AND SCREENED SECTION
 94-444(B).
 4. DUMPSTER LOCATION REQUIRES APPROVAL FROM THE
 SANITATION SUPERINTENDENT. PLEASE CONTACT FERDINAND
 RIVERA AT 822-2076.
 5. BASED ON SUBMITTED DRAWINGS THE PROPOSED BUSINESS
 SEEMS TO BE A BAR. THAT USE IS NOT CURRENTLY PERMITTED
 AT 526 CLEMATIS STREET, THERE ARE ALREADY TWO ALCOHOLIC
 BEVERAGE ESTABLISHMENTS IN THE APPLICABLE BLOCK.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.