Plan Review Details - Permit 14030705
Plan Review Stops For Permit 14030705
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-24 Cont ID  
Sent By jgomez Date 2014-04-24 Time 14:36 Rev Time 0.00
Received By jgomez Date 2014-04-24 Time 14:18 Sent To  
Notes
2014-04-24 15:14:04REVISION BUILDING REVIEW CHECKLIST.
  
 1- REVISED DRAWING IS STILL NOT ACCURATE. BEAM TO BE
 REPLACED IS A FULL LENGTH BEAM NOT SPLICED AS SHOWN ON
 DRAWING. PLANS SHOW A 24'-0" SECTION OF THE BEAM BEAM
 REPLACED. THIS IS NOT CORRECT. BEAM WAS REPLACED IN ITS
 ENTIRE LENGTH. ENGINEER TO VISIT JOB SITE AND REVISE
 WALL SECTION AND KEY MAP AS REQUIRED TO MATCH ACTUAL
 CONDITIONS. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-03-19 Cont ID  
Sent By jgomez Date 2014-03-19 Time 13:40 Rev Time 0.00
Received By jgomez Date 2014-03-19 Time 13:40 Sent To  
Notes
2014-03-19 13:42:563/19/14 MET WITH NICK BESSENROTH (CONTRACTOR) ON
 JOBSITE.
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- ENGINEER TO REVISE DRAWING SHOWING FULL LENGTH OF
 BEAM AND CONNECTORS AT BOTH ENDS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-24 Cont ID  
Sent By jgomez Date 2014-04-24 Time 14:18 Rev Time 0.00
Received By jgomez Date 2014-04-24 Time 14:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-19 Cont ID  
Sent By jgomez Date 2014-03-19 Time 13:43 Rev Time 0.00
Received By jgomez Date 2014-03-18 Time 17:25 Sent To  
Notes
***NONE***