Plan Review Details - Permit 14030587
Plan Review Stops For Permit 14030587
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-05-08 Cont ID  
Sent By shill Date 2014-05-08 Time 17:40 Rev Time 0.00
Received By shill Date 2014-05-08 Time 17:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-09 Cont ID  
Sent By shill Date 2014-04-09 Time 11:58 Rev Time 0.00
Received By shill Date 2014-04-09 Time 11:58 Sent To  
Notes
2014-04-09 12:14:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE OPENING 3 AND SHEET 12 OF THE PRODUCT APPROVAL.
 A SPAN OF 75" = 6.25', SO THE COLUMN 6' AND UNDER
 CANNOT BE USED. 7.5" ANCHOR SPACING REQUIRED. PLEASE
 CHECK ALL AS THIS APPLIES TO SEVERAL OPENINGS.
  
 2. SEE OPENING 5 AND SHEET 12 OF THE PRODUCT APPROVAL.
 A SPAN OF 108" = 9' SO THE COLUMN "SPANS UP TO 12'"
 SHOULD BE USED. 6" ANCHOR SPACING DOES NOT COMPLY WITH
 THE CONDITIONS STATED ON INSTALLATION SCHEDULE (62PSF,
 C2 CONNECTION TYPE, 108" SPAN, BLOCK BOTTOM SUBSTRATE),
 POWERS TAPPER FASTENER.
  
 3. PLEASE CHECK ALL AS THERE MAY BE SIMILAR ERRORS. AS
 ALWAYS, IF COMMENTS ARE NOT CLEAR OR YOU FEEL THAT I'VE
 MADE AN ERROR, PLEASE SCHEDULE AN APPOINTMENT WITH
 EITHER ME OR STEVE KENNEY, 561-805-6710. THE
 INSTALLATION SCHEDULE AND PRODUCT APPROVAL HAVE BEEN
 HIGHLIGHTED FOR OTHERS TO ASSIST YOU IN MY ABSENCE.
  
 4. AS ADVISED PREVIOUSLY, DESIGN PRESSURES WERE REDUCED
 WITH THE ADOPTION OF FBC 2010. AS OFFERED PREVIOUSLY,
 PLEASE ADVISE IF YOU WISH TO HAVE ASSISTANCE REGARDING
 THE NEW DESIGN PRESSURES IN RELATION TO THE
 INSTALLATION SCHEDULE.
  
  
  
  
  
  
  
 .

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-26 Cont ID  
Sent By shill Date 2014-03-26 Time 17:09 Rev Time 0.00
Received By shill Date 2014-03-26 Time 17:08 Sent To  
Notes
2014-03-26 17:13:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FASTENER PROPOSED IS NOT CLEAR. "TYPE OF ANCHOR
 SPECIFIED" STATES "2 1/4 X 1/4 POWERS TAPCON"
  
 IN THE COLUMN "SPECIFIC ANCHOR TYPE" IT STTATES:
  
 1/4 POWERS
 TAPCON
  
 ALL OTHER COLUMNS HAVE TWO SETS OF DATA; ONE FOR TOP,
 ONE FOR BOTTOM. SO, IT APPEARS THAT THIS IS TO MEAN
 POWERS TAPPER ON THE TOP, TAPCON ON THE BOTTOM. THE
 SHEETS WITH THE ANCHOR CHARTS WERE NOT SUBMITTED
 (PRODUCT APPROVAL INCOMPLETE) BUT IN OTHER REVIEWS
 CONTRACTOR WAS INFORMED THAT TAPCON SPACING NOT
 COMPLIANT.
  
 IF CONTRACTOR PROPOSES POWERS TAPPERS TOP AND BOTTOM,
 PLEASE CLARIFY AS TO WHY THE INSTALLATION SCHEDULE
 REFERS TO "TAPCONS" IN TWO PLACES.
  
 2. PRODUCT APPROVAL INCOMPLETE. PROVIDE ALL SHEETS SO A
 COMPLETE REVIEW CAN BE PERFORMED.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-05-08 Cont ID  
Sent By shill Date 2014-05-08 Time 17:40 Rev Time 0.00
Received By shill Date 2014-04-18 Time 17:24 Sent To  
Notes
2014-04-18 17:25:03INCOMING SENT TO SAMS DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-09 Cont ID  
Sent By shill Date 2014-04-09 Time 12:15 Rev Time 0.00
Received By shill Date 2014-04-09 Time 12:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-26 Cont ID  
Sent By rmcdouga Date 2014-03-26 Time 17:14 Rev Time 0.00
Received By shill Date 2014-03-14 Time 14:46 Sent To  
Notes
2014-03-14 14:46:47SENT TO MISC.1 BOX