Plan Review Details - Permit 14030562
Plan Review Stops For Permit 14030562
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-07-05 Cont ID  
Sent By jwitmer Date 2014-07-05 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2014-07-05 Time 09:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-06-06 Cont ID  
Sent By JWITMER Date 2014-06-06 Time 17:42 Rev Time 0.00
Received By jwitmer Date 2014-06-06 Time 16:58 Sent To  
Notes
2014-06-06 17:42:45BUILDING PLAN REVIEW
 PERMIT: 14030562
 ADD: 1875 PALM BCH LAKES # A09
 CONT: TO BE DETERMINED
 TEL: (561)373-3902 / KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: FRIDAY JUNE 06/2014
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) PB OUTLET MALLS:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 3A) COMPLIED.
  
 3B) NOTE TO DESIGNER!!!: CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED THREE OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 2ND REQUEST!!!THE PLANS, LIFE SAFETY SHEET A1.0 ARE
 INDICATING THEY ARE TAKING AREA INCREASES FOR FIRE
 SPRINKLERS, THE INDEX AND PLANS FAIL TO CONTAIN FIRE
 SPRINKLER & FIRE ALARM PLANS WITHIN THIS SET.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 (5) . FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERSFIRE SPRINKLER PLANS ARE A
 MUST, OVER 12,000 SQ FT. SHEET A1.0 INDICATE A AREA
 INCREASE OF 300% WITH
 FIRE SPRINKLERS, THERE ARE NO FIRE SPRINKLER PLANS
 LISTED IN THE INDEX NOR IS THERE A SEPARATE SET OF FIRE
 SPRINKLER PLANS SUBMITTED WITH THE 2ND SUBMITTAL.
  
 SECTION NOT MET: 2010 FBC-B F] 903.2.7 GROUP M. AN
 AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT
 BUILDINGS CONTAINING A GROUP M OCCUPANCY WHERE ONE OF
 THE FOLLOWING CONDITIONS EXISTS: 1. A GROUP M FIRE AREA
 EXCEEDS 12,000 SQUARE FEET (1115 M2).
  
 3C) COMPLIED.
  
 4) 2ND REQUEST, BUILDING EVALUATION IS STILL LOW. THE
 ICC TABLES PUT THE BUILDING TYPE IIB AT $115.47 SQ FT.
 THE SHELL'
 ROOF & FIRE SPRINKLERS TOTAL COST COMES TO $44.00 A
 SQUARE FOOT OR THE TENANT BUILD OUT WITH THE FIRE
 SPRINKLERS FOR THE TENANT BUILD OUT INCLUDED AT $71.00
 A SQUARE FOOT.
 THE TENANT BUILD OUT VALUE IS LOW AT $18.64 DOLLARS /
 SQ FT. W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF
 PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 5-7) COMPLIED.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-04-14 Cont ID  
Sent By jwitmer Date 2014-04-14 Time 16:58 Rev Time 0.00
Received By jwitmer Date 2014-04-14 Time 12:16 Sent To  
Notes
2014-04-14 15:47:34BUILDING PLAN REVIEW
 PERMIT: 14030562
 ADD: 1875 PALM BCH LAKES # A09
 CONT: TO BE DETERMINED
 TEL: (561)373-3902 / KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MONDAY APRIL 14/ 2014
 ACTION: DENIED
  
 1) THE PLANS DO NOT HAVE THE STAMP OF APPROVAL OR
 LETTER FROM NEW ENGLAND DEVELOPMENT PALM BEACH OUTLETS
 SKYE GROUP TENANT COORDINATOR THAT THE PLANS AAND
 DESIGN ARE APPROVED.
  
 2) PB OUTLET MALLS:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 3A) THE PLANS, LIFE SAFETY SHEET A1.0 DO NOT PROVIDE
 THE MINIMUM TYPE OF CONSTRUCTION, SHELL PERMIT IS TYPE
 IIB. 2010 FBC-B TABLE 503.
  
 3B) THE PLANS, LIFE SAFETY SHEET A1.0 ARE INDICATING
 THEY ARE TAKING AREA INCREASES FOR FIRE SPRINKLERS, THE
 INDEX AND PLANS FAIL TO CONTAIN FIRE SPRINKLER & FIRE
 ALARM PLANS WITHIN THIS SET.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 (5) . FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 RISER DIAGRAM
  
 3C) THE LIFE SAFETY PLANS DO NOT PROVIDE ANY DETAILS
 FOR COMPLIANCE WITH :
 2010 FBC- ACCESSIBILITY CODE.
 904.3 CHECK-OUT AISLES.
 CHECK-OUT AISLES SHALL COMPLY WITH 904.3.
 904.3.1 AISLE.
 AISLES SHALL COMPLY WITH 403.
 904.3.2 COUNTER.
 THE COUNTER SURFACE HEIGHT SHALL BE 38 INCHES (965 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. THE TOP OF
 THE COUNTER EDGE PROTECTION SHALL BE 2 INCHES (51 MM)
 MAXIMUM ABOVE THE TOP OF THE COUNTER SURFACE ON THE
 AISLE SIDE OF THE CHECK-OUT COUNTER
  
 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 4) THE TENANT BUILD OUT VALUE IS LOW AT $18.64 DOLLARS
 / SQ FT. W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF
 PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 5) SHEET A2.2 INDICATES THE USE OF A X-RAY MACHINE IN
 ROOM 128 THERE DOES NOT APPEAR TO BE ANY SHIELDING OF
 WALLS NOR IS THERE A DOOR. FBC-B 435.5.1. SHIELDING.
  
 6) SHEET A5.0 CURB DETAILS PLEASE SHOW COMPLIANCE WITH
 FBC-B 1509.7 MECHANICAL UNITS. ROOF MOUNTED MECHANICAL
 UNITS SHALL BE MOUNTED ON CURBS RAISED A MINIMUM OF 8
 INCHES (203 MM) ABOVE THE ROOF SURFACE, OR WHERE
 ROOFING MATERIALS EXTEND BENEATH THE UNIT,
  
 7) ALL ARCHITECTURAL SHEETS ARE COPIES OF THE ORIGINAL
 SIGNATURE, ALL SIGNATURES ARE IDENTICAL AND PIXOLATED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-06-05 Cont ID  
Sent By RLECKY Date 2014-06-05 Time 15:32 Rev Time 0.00
Received By dhayes Date 2014-06-05 Time 15:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-04-17 Cont ID  
Sent By rlecky Date 2014-04-17 Time 15:24 Rev Time 0.00
Received By rlecky Date 2014-04-17 Time 11:01 Sent To  
Notes
2014-04-17 15:24:0214030562
 1875 PALM BEACH LAKES BLVD. #A09
 PET?S MART
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22
  
 PROVIDE DEDICATED EQUIPMENT SPACES WITH SAFE WORKING
 CLEARANCE AND DIMENSIONS FOR THE SWITCH BOARDS AND
 PANEL BOARDS. 110.26
  
 PROVIDE SPECIFICATIONS AND LISTING FOR HILL PHOENIX
 ELECTRICAL EQUIPMENT SPECIFIED. VERIFY THIS EQUIPMENT
 IS MARKED AS SUITABLE FOR USE AS SERVICE EQUIPMENT. NEC
 110.3, 230.66
  
 PROVIDE DETAILS OF ALL ELECTRICAL SERVICES PROPOSED FOR
 THIS BUILDING (BUILDING ?A?). THE MASTER PLAN LIMITS
 THE NUMBER OF MAIN DISCONNECTS TO FOUR WHICH MUST BE
 GROUPED IN ONE LOCATION. NEC 230.2; 230.40; 230.70;
 230.71
  
 PROVIDE CALCULATIONS CLARIFYING THE SELECTION OF
 PRIMARY AND SECONDARY PROTECTION FOR TRANSFORMER ?T?.
 NEC 450.3(B)
  
 SHOW LOCATION OF THE MAIN DISCONNECTS FOR THE PANELS
 FED FROM TRANSFORMER (T1). VERIFY DISCONNECTS ARE
 GROUPED. VERIFY THE TAP CONDUCTORS ARE THE APPROPRIATE
 LENGTH. NEC 240.21, 450.3 (B); 240.4(F); 240.21(C)
  
 PANEL ?LA? REQUIRES A LARGER FEEDER. NEC 240.4; 240.6;
 T. 310.16
  
 PROVIDE SPECIFICATIONS AND LISTING FOR THE 400 AMP
 SERVICE RATED MAIN DISCONNECT. NEC 110.3
  
 PROVIDE SPECIFICATIONS FOR THE GENERATOR TRANSFER
 SWITCH. INCLUDE A GENERATOR DISCONNECT, LOAD
 CALCULATION, LOCATION SIGNAGE, GROUNDING AND FEEDER
 SIZE. NEC 215.5; 445.13; 445.18; 702.5; 702.8; 702.10
  
 PROVIDE SPECIFICATIONS AND LISTING FOR THE X-RAY
 EQUIPMENT AND DISCONNECT. NEC 110.3
  
 PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF ROOF TOP
 EQUIPMENT. NEC 210.8; 210.63
  
 SHOW THE LIGHTING BRANCH CIRCUITS ON THE LIGHTING FLOOR
 PLAN. NEC 210.11
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; 505.5.3; T
 505.5.3
  
 PROVIDE OR CONFIRM THAT THE INTERIOR AND EXTERIOR
 LIGHTING CONTROLS PROVIDED ARE IN ACCORDANCE WITH THE
 FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL
 BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. FBC ENERGY CONSERVATION 505.2
  
 PROVIDE LIGHTING CONTROLS ON THE SIGN CIRCUIT.
 AUTOMATIC CONTROLS SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS. FBC ENERGY
 CONSERVATION 505.2
  
 CONDUCTORS FOR DATA AND COMMUNICATIONS SYSTEMS LOCATED
 AT OR BELOW GRADE MUST BE LISTED AS SUITABLE FOR DAMP
 OR WET LOCATIONS. NEC 110.3, 110.8,
  
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE
 ALARM SYSTEMS, SECURITY, VOICE, DATA SYSTEMS, AND
 GENERATOR.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
 561-373-3701
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-06-05 Cont ID  
Sent By SCALDERO Date 2014-06-05 Time   Rev Time 0.00
Received By pleduc Date 2014-06-04 Time 16:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-03-31 Cont ID  
Sent By scaldero Date 2014-03-31 Time 11:41 Rev Time 0.00
Received By scaldero Date 2014-03-31 Time 11:37 Sent To  
Notes
2014-03-31 11:41:10PERMIT #14030562
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAIL COMMENT: ENGINEERED FIRE ALARM AND FIRE SPRINKLER
 CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  
 PROVISO COMMENTS:
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR. (REQUIRED ON ALL ENTRY DOORS,
 I.E., DOUBLE DOORS SHOULD HAVE 2 INDICATORS.)
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-05 Cont ID  
Sent By jwitmer Date 2014-07-05 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2014-07-03 Time 16:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-07 Cont ID  
Sent By jwitmer Date 2014-06-07 Time 06:24 Rev Time 0.00
Received By jwitmer Date 2014-05-12 Time 18:27 Sent To  
Notes
2014-05-13 18:27:44C25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-25 Cont ID  
Sent By skennedy Date 2014-04-25 Time 16:41 Rev Time 0.00
Received By skennedy Date 2014-03-14 Time 10:54 Sent To  
Notes
2014-03-15 10:44:59C04

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-05-28 Cont ID  
Sent By hmoser Date 2014-05-28 Time 14:15 Rev Time 0.00
Received By hmoser Date 2014-05-28 Time 14:14 Sent To  
Notes
2014-05-28 14:15:13PLAN REVIEW BY JS. PK1328
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-04-18 Cont ID  
Sent By hmoser Date 2014-04-18 Time 07:51 Rev Time 0.00
Received By hmoser Date 2014-04-16 Time 13:11 Sent To  
Notes
2014-04-18 07:51:28PLAN DENIED
 1) PROVIDE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS ON THE ELECTRIC UNIT HEATER.
 PER SECTION 107 FBC 2010
 2) REFER TO SECTION 604.8 LINING
 INSULATION. 2010 FBC (M)
 3) REFER TO SECTION 503.2.1 CALCULATION OF
 HEATING AND COOLING. FLORIDA ENERGY CODE 2010
 4) REFER TO SECTION 503.2.4.4 SHUTOFF
 DAMPER CONTROLS. FLORIDA ENERGY CODE 2010
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2014-06-07 Cont ID  
Sent By JWITMER Date 2014-06-07 Time 06:24 Rev Time 0.00
Received By jwitmer Date 2014-06-07 Time 06:09 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2014-04-14 Cont ID  
Sent By jwitmer Date 2014-04-14 Time 18:49 Rev Time 0.00
Received By jwitmer Date 2014-04-14 Time 18:00 Sent To  
Notes
2014-04-14 18:51:06MED-GAS/PLUMBING PLAN REVIEW
 PERMIT: 14030562
 ADD: 1875 PALM BCH LAKES # A09
 CONT: TO BE DETERMINED
 TEL: (561)373-3902 / KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MONDAY APRIL 14/ 2014
 ACTION: DENIED
  
 1) SHEET P1.1 PLEASE PROVIDE THE MANUFACTURERS SPEC
 SHEETS FOR THE FOLLOWING PLUMBING FIXTURES;
  
 1A) ) OXY 1-3 HJC VENDOR CUT SHEETS 2010 FBC-P 1201.1
 SCOPE.
 THE PROVISIONS OF THIS CHAPTER SHALL GOVERN THE DESIGN
 AND INSTALLATION OF PIPING AND STORAGE SYSTEMS FOR
 NONFLAMMABLE MEDICAL GAS SYSTEMS AND NONMEDICAL OXYGEN
 SYSTEMS. ALL MAINTENANCE AND OPERATIONS OF SUCH SYSTEMS
 SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION
 CODE.
 PLEASE PROVIDE A MED-GAS PLAN FOR THE OXYGEN UNDER A
 SEPERATE PERMIT. DETAILS CAN BE ONTHIS PLAN. REQUIRES A
 DIFFERNT PERMIT, BECAUSE OF THE INSPECTION CODES ARE
 DIFFERENT FROM THE PLUMBING.
  
 1B) SB1, SB2 & SB3 SCAVENGER VACCUUM UNIT , DROPS AND
 WET TABLE OUTLETS. PLEASE PROVIDE THE MANUFACTURERS CUT
 SHEETS ON THEASE PRODUCTS. 2010 FBC-P 713.4 OR 713.5.
 THE PLANS DO NOT PROVIDE A CLEAR VIEW OF THE SCAVENGER
 VACCUUM UNIT AND PIPING LAYOUT NOR DOES THE PLANS
 INDICATE WHERE THE VENT ON THE PUMP IS GOING TO VENT
 TO. THE EXHAUSTS FROM A VACUUM PUMP SERVING A VACUUM
 (FLUID SUCTION) SYSTEM SHALL DISCHARGE SEPARATELY TO
 OPEN AIR ABOVE THE ROOF. 713.6.
  
 2) SHEET P0.1 HEADING PB-7 2 /250 OXYGEN CYLINDERS
 PROVIDE DETAIL FOR SECURING TO WALL AND FOR THE
 MANIFOLD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-06-07 Cont ID  
Sent By JWITMER Date 2014-06-07 Time 06:24 Rev Time 0.00
Received By jwitmer Date 2014-06-07 Time 05:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-04-14 Cont ID  
Sent By jwitmer Date 2014-04-14 Time 18:49 Rev Time 0.00
Received By jwitmer Date 2014-04-14 Time 16:58 Sent To  
Notes
2014-04-14 17:47:04PLUMBING PLAN REVIEW
 PERMIT: 14030562
 ADD: 1875 PALM BCH LAKES # A09
 CONT: TO BE DETERMINED
 TEL: (561)373-3902 / KARI
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: MONDAY APRIL 14/ 2014
 ACTION: DENIED
  
 1) SHEET P1.1 PLEASE PROVIDE THE MANUFACTURERS SPEC
 SHEETS FOR THE FOLLOWING PLUMBING FIXTURES;
  
 1A) TRENCH DRAINS AND IN ACCORDANCE WITH 2010 FBC-P
 412.1 APPROVAL.
 TRENCH DRAINS SHALL COMPLY WITH ASME A112.6.3.
  
 1B) IT-1 GOOSE NECK W/ 8'-0" VINYL HOSE 2010 FBC-P
 424.6 HOSE-CONNECTED OUTLETS.
 FAUCETS AND FIXTURE FITTINGS WITH HOSE-CONNECTED
 OUTLETS SHALL CONFORM TO ASME A112.18.3M OR CSA B125.
  
 1C) OXY 1-3 HJC VENDOR CUT SHEETS 2010 FBC-P 1201.1
 SCOPE.
 THE PROVISIONS OF THIS CHAPTER SHALL GOVERN THE DESIGN
 AND INSTALLATION OF PIPING AND STORAGE SYSTEMS FOR
 NONFLAMMABLE MEDICAL GAS SYSTEMS AND NONMEDICAL OXYGEN
 SYSTEMS. ALL MAINTENANCE AND OPERATIONS OF SUCH SYSTEMS
 SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION
 CODE.
 PLEASE PROVIDE A MED-GAS PLAN FOR THE OXYGEN UNDER A
 SEPERATE PERMIT. DETAILS CAN BE ONTHIS PLAN. REQUIRES A
 DIFFERNT PERMIT, BECAUSE OF THE INSPECTION CODES ARE
 DIFFERENT FROM THE PLUMBING.
  
 1D) SB1, SB2 & SB3 SCAVENGER VACCUUM UNIT , DROPS AND
 WET TABLE OUTLETS. PLEASE PROVIDE THE MANUFACTURERS CUT
 SHEETS ON THEASE PRODUCTS. 2010 FBC-P 713.4 OR 713.5.
 THE PLANS DO NOT PROVIDE A CLEAR VIEW OF THE SCAVENGER
 VACCUUM UNIT AND PIPING LAYOUT NOR DOES THE PLANS
 INDICATE WHERE THE VENT ON THE PUMP IS GOING TO VENT
 TO. THE EXHAUSTS FROM A VACUUM PUMP SERVING A VACUUM
 (FLUID SUCTION) SYSTEM SHALL DISCHARGE SEPARATELY TO
 OPEN AIR ABOVE THE ROOF. 713.6.
  
 2) SHEET P0.1 HEADING PB-7 2 /250 OXYGEN CYLINDERS
 PROVIDE DETAIL FOR SECURING TO WALL AND FOR THE
 MANIFOLD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop POLICE POLICE
Rev No 1 Status N Date 2014-04-25 Cont ID  
Sent By skennedy Date 2014-04-25 Time 16:41 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2014-05-27 Cont ID  
Sent By ESCHNEID Date 2014-05-27 Time 16:47 Rev Time 0.50
Received By eschneid Date 2014-05-27 Time 16:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-04-02 Cont ID  
Sent By eschneid Date 2014-04-02 Time 09:16 Rev Time 1.00
Received By eschneid Date 2014-04-02 Time 09:16 Sent To  
Notes
2014-04-02 13:05:41FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 1) THE PALM BEACH OUTLETS MANAGEMENT APPROVAL STAMP IS
 NOT PROVIDED ON THE PLANS.
  
 2) WHAT IS THE PLAN/LOCATION FOR THE DOG WALK FOR PETS
 UNDER VETERINARY CARE?
  
 3) BASED ON EXPERIENCE AT THE OKEECHOBEE BOULEVARD
 PET'S MART LOCATION, PLEASE PROVIDE A NARRATIVE ON HOW
 THE DOG POOP FROM DOGS BROUGHT TO THE STORE WILL BE
 CLEANED UP FROM THE LANDSCAPE ISLANDS AND SIDEWALKS IN
 FRONT OF THE STORE. THE INSTALLATION OF DISPOSAL BAG
 STATIONS SHALL BE STATED ON THE PLANS.
  
 4) THE NEW TRASH CAN/ASH DISPOSAL SHOWN FOR OUTSIDE THE
 STORE SHALL BE THE SAME STYLE AS THOSE PROVIDED BY THE
 PALM BEACH OUTLETS FOR THE REMAINDER OF THE IN-LINE
 RETAIL ALONG I-95.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2014-03-28 09:49:553/28/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved