 |
Plan Review Details - Permit 14030562
Plan Review Stops For Permit 14030562 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2014-07-05 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-07-05 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-07-05 |
Time |
09:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2014-06-06 |
|
|
Cont ID |
|
Sent By |
JWITMER |
Date |
2014-06-06 |
Time |
17:42 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-06-06 |
Time |
16:58 |
Sent To |
|
|
Notes |
2014-06-06 17:42:45 | BUILDING PLAN REVIEW | | PERMIT: 14030562 | | ADD: 1875 PALM BCH LAKES # A09 | | CONT: TO BE DETERMINED | | TEL: (561)373-3902 / KARI | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | 2ND REVIEW | | DATE: FRIDAY JUNE 06/2014 | | ACTION: DENIED | | | | 1) COMPLIED. | | | | 2) PB OUTLET MALLS: | | A LETTER FROM THE QUALIFIER OF BOTH THE SHELL | | CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT | | CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT | | PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT | | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK | | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY | | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE | | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND | | NOTARIZED. | | | | 3A) COMPLIED. | | | | 3B) NOTE TO DESIGNER!!!: CHAPTER 553.80(2)(B) FLORIDA | | STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A | | FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE | | REJECTED THREE OR MORE TIMES FOR REPEATED FAILURE TO | | CORRECT A CODE VIOLATION. | | | | 2ND REQUEST!!!THE PLANS, LIFE SAFETY SHEET A1.0 ARE | | INDICATING THEY ARE TAKING AREA INCREASES FOR FIRE | | SPRINKLERS, THE INDEX AND PLANS FAIL TO CONTAIN FIRE | | SPRINKLER & FIRE ALARM PLANS WITHIN THIS SET. | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | 107.3.5.1 COMMERCIAL BUILDINGS: | | (5) . FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: | | SCHEMATIC FIRE SPRINKLERSFIRE SPRINKLER PLANS ARE A | | MUST, OVER 12,000 SQ FT. SHEET A1.0 INDICATE A AREA | | INCREASE OF 300% WITH | | FIRE SPRINKLERS, THERE ARE NO FIRE SPRINKLER PLANS | | LISTED IN THE INDEX NOR IS THERE A SEPARATE SET OF FIRE | | SPRINKLER PLANS SUBMITTED WITH THE 2ND SUBMITTAL. | | | | SECTION NOT MET: 2010 FBC-B F] 903.2.7 GROUP M. AN | | AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT | | BUILDINGS CONTAINING A GROUP M OCCUPANCY WHERE ONE OF | | THE FOLLOWING CONDITIONS EXISTS: 1. A GROUP M FIRE AREA | | EXCEEDS 12,000 SQUARE FEET (1115 M2). | | | | 3C) COMPLIED. | | | | 4) 2ND REQUEST, BUILDING EVALUATION IS STILL LOW. THE | | ICC TABLES PUT THE BUILDING TYPE IIB AT $115.47 SQ FT. | | THE SHELL' | | ROOF & FIRE SPRINKLERS TOTAL COST COMES TO $44.00 A | | SQUARE FOOT OR THE TENANT BUILD OUT WITH THE FIRE | | SPRINKLERS FOR THE TENANT BUILD OUT INCLUDED AT $71.00 | | A SQUARE FOOT. | | THE TENANT BUILD OUT VALUE IS LOW AT $18.64 DOLLARS / | | SQ FT. W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF | | PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, | | MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS | | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID | | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE | | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. | | | | 108.3* BUILDING PERMIT VALUATION. | | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE | | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, | | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS | | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE | | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | CONGRESS. | | | | 5-7) COMPLIED. | | | | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-04-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-04-14 |
Time |
16:58 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-04-14 |
Time |
12:16 |
Sent To |
|
|
Notes |
2014-04-14 15:47:34 | BUILDING PLAN REVIEW | | PERMIT: 14030562 | | ADD: 1875 PALM BCH LAKES # A09 | | CONT: TO BE DETERMINED | | TEL: (561)373-3902 / KARI | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | 1ST REVIEW | | DATE: MONDAY APRIL 14/ 2014 | | ACTION: DENIED | | | | 1) THE PLANS DO NOT HAVE THE STAMP OF APPROVAL OR | | LETTER FROM NEW ENGLAND DEVELOPMENT PALM BEACH OUTLETS | | SKYE GROUP TENANT COORDINATOR THAT THE PLANS AAND | | DESIGN ARE APPROVED. | | | | 2) PB OUTLET MALLS: | | A LETTER FROM THE QUALIFIER OF BOTH THE SHELL | | CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT | | CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT | | PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT | | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK | | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY | | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE | | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND | | NOTARIZED. | | | | 3A) THE PLANS, LIFE SAFETY SHEET A1.0 DO NOT PROVIDE | | THE MINIMUM TYPE OF CONSTRUCTION, SHELL PERMIT IS TYPE | | IIB. 2010 FBC-B TABLE 503. | | | | 3B) THE PLANS, LIFE SAFETY SHEET A1.0 ARE INDICATING | | THEY ARE TAKING AREA INCREASES FOR FIRE SPRINKLERS, THE | | INDEX AND PLANS FAIL TO CONTAIN FIRE SPRINKLER & FIRE | | ALARM PLANS WITHIN THIS SET. | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | 107.3.5.1 COMMERCIAL BUILDINGS: | | (5) . FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: | | EARLY WARNING SMOKE EVACUATION SYSTEMS | | SCHEMATIC FIRE SPRINKLERS | | STANDPIPES | | PRE-ENGINEERED SYSTEMS | | RISER DIAGRAM | | | | 3C) THE LIFE SAFETY PLANS DO NOT PROVIDE ANY DETAILS | | FOR COMPLIANCE WITH : | | 2010 FBC- ACCESSIBILITY CODE. | | 904.3 CHECK-OUT AISLES. | | CHECK-OUT AISLES SHALL COMPLY WITH 904.3. | | 904.3.1 AISLE. | | AISLES SHALL COMPLY WITH 403. | | 904.3.2 COUNTER. | | THE COUNTER SURFACE HEIGHT SHALL BE 38 INCHES (965 MM) | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. THE TOP OF | | THE COUNTER EDGE PROTECTION SHALL BE 2 INCHES (51 MM) | | MAXIMUM ABOVE THE TOP OF THE COUNTER SURFACE ON THE | | AISLE SIDE OF THE CHECK-OUT COUNTER | | | | 904.4 SALES AND SERVICE COUNTERS. | | SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH | | 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE | | COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR | | SERVICE COUNTER TOP. | | | | 4) THE TENANT BUILD OUT VALUE IS LOW AT $18.64 DOLLARS | | / SQ FT. W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF | | PERMIT FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, | | MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS | | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID | | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE | | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. | | | | 108.3* BUILDING PERMIT VALUATION. | | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE | | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, | | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS | | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE | | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | CONGRESS. | | | | 5) SHEET A2.2 INDICATES THE USE OF A X-RAY MACHINE IN | | ROOM 128 THERE DOES NOT APPEAR TO BE ANY SHIELDING OF | | WALLS NOR IS THERE A DOOR. FBC-B 435.5.1. SHIELDING. | | | | 6) SHEET A5.0 CURB DETAILS PLEASE SHOW COMPLIANCE WITH | | FBC-B 1509.7 MECHANICAL UNITS. ROOF MOUNTED MECHANICAL | | UNITS SHALL BE MOUNTED ON CURBS RAISED A MINIMUM OF 8 | | INCHES (203 MM) ABOVE THE ROOF SURFACE, OR WHERE | | ROOFING MATERIALS EXTEND BENEATH THE UNIT, | | | | 7) ALL ARCHITECTURAL SHEETS ARE COPIES OF THE ORIGINAL | | SIGNATURE, ALL SIGNATURES ARE IDENTICAL AND PIXOLATED. | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR | | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE | | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. | | FL ADMIN CODE 61G16.003 ARCHITECTS | | | | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2014-06-05 |
|
|
Cont ID |
|
Sent By |
RLECKY |
Date |
2014-06-05 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-06-05 |
Time |
15:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-04-17 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2014-04-17 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2014-04-17 |
Time |
11:01 |
Sent To |
|
|
Notes |
2014-04-17 15:24:02 | 14030562 | | 1875 PALM BEACH LAKES BLVD. #A09 | | PET?S MART | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN | | DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22 | | | | PROVIDE DEDICATED EQUIPMENT SPACES WITH SAFE WORKING | | CLEARANCE AND DIMENSIONS FOR THE SWITCH BOARDS AND | | PANEL BOARDS. 110.26 | | | | PROVIDE SPECIFICATIONS AND LISTING FOR HILL PHOENIX | | ELECTRICAL EQUIPMENT SPECIFIED. VERIFY THIS EQUIPMENT | | IS MARKED AS SUITABLE FOR USE AS SERVICE EQUIPMENT. NEC | | 110.3, 230.66 | | | | PROVIDE DETAILS OF ALL ELECTRICAL SERVICES PROPOSED FOR | | THIS BUILDING (BUILDING ?A?). THE MASTER PLAN LIMITS | | THE NUMBER OF MAIN DISCONNECTS TO FOUR WHICH MUST BE | | GROUPED IN ONE LOCATION. NEC 230.2; 230.40; 230.70; | | 230.71 | | | | PROVIDE CALCULATIONS CLARIFYING THE SELECTION OF | | PRIMARY AND SECONDARY PROTECTION FOR TRANSFORMER ?T?. | | NEC 450.3(B) | | | | SHOW LOCATION OF THE MAIN DISCONNECTS FOR THE PANELS | | FED FROM TRANSFORMER (T1). VERIFY DISCONNECTS ARE | | GROUPED. VERIFY THE TAP CONDUCTORS ARE THE APPROPRIATE | | LENGTH. NEC 240.21, 450.3 (B); 240.4(F); 240.21(C) | | | | PANEL ?LA? REQUIRES A LARGER FEEDER. NEC 240.4; 240.6; | | T. 310.16 | | | | PROVIDE SPECIFICATIONS AND LISTING FOR THE 400 AMP | | SERVICE RATED MAIN DISCONNECT. NEC 110.3 | | | | PROVIDE SPECIFICATIONS FOR THE GENERATOR TRANSFER | | SWITCH. INCLUDE A GENERATOR DISCONNECT, LOAD | | CALCULATION, LOCATION SIGNAGE, GROUNDING AND FEEDER | | SIZE. NEC 215.5; 445.13; 445.18; 702.5; 702.8; 702.10 | | | | PROVIDE SPECIFICATIONS AND LISTING FOR THE X-RAY | | EQUIPMENT AND DISCONNECT. NEC 110.3 | | | | PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF ROOF TOP | | EQUIPMENT. NEC 210.8; 210.63 | | | | SHOW THE LIGHTING BRANCH CIRCUITS ON THE LIGHTING FLOOR | | PLAN. NEC 210.11 | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; 505.5.3; T | | 505.5.3 | | | | PROVIDE OR CONFIRM THAT THE INTERIOR AND EXTERIOR | | LIGHTING CONTROLS PROVIDED ARE IN ACCORDANCE WITH THE | | FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL | | BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME | | SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST | | 10 HOURS. FBC ENERGY CONSERVATION 505.2 | | | | PROVIDE LIGHTING CONTROLS ON THE SIGN CIRCUIT. | | AUTOMATIC CONTROLS SHALL BE CAPABLE OF RETAINING | | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER | | FOR A PERIOD OF AT LEAST 10 HOURS. FBC ENERGY | | CONSERVATION 505.2 | | | | CONDUCTORS FOR DATA AND COMMUNICATIONS SYSTEMS LOCATED | | AT OR BELOW GRADE MUST BE LISTED AS SUITABLE FOR DAMP | | OR WET LOCATIONS. NEC 110.3, 110.8, | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE | | ALARM SYSTEMS, SECURITY, VOICE, DATA SYSTEMS, AND | | GENERATOR. | | | | | | ROBERT LECKY | | ELECTRICAL PLANS REVIEW | | 561-373-3701 | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2014-06-05 |
|
|
Cont ID |
|
Sent By |
SCALDERO |
Date |
2014-06-05 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-06-04 |
Time |
16:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2014-03-31 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2014-03-31 |
Time |
11:41 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2014-03-31 |
Time |
11:37 |
Sent To |
|
|
Notes |
2014-03-31 11:41:10 | PERMIT #14030562 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FAIL COMMENT: ENGINEERED FIRE ALARM AND FIRE SPRINKLER | | CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL | | BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS BEEN | | ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP | | DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION | | DOCUMENTS) FOR A SUB-PERMIT. | | | | PROVISO COMMENTS: | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | WWW.KNOXBOX.COM. | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | BE SUBMITTED BY EMAIL ([email protected]) | | ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND | | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT | | 500 NORTH DIXIE HIGHWAY. | | | | ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A | | LOCK/UNLOCK INDICATOR. (REQUIRED ON ALL ENTRY DOORS, | | I.E., DOUBLE DOORS SHOULD HAVE 2 INDICATORS.) | | | | EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH | | SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL | | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN | | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE | | SPACED NOT MORE THAN 15 FEET ON CENTER. | | | | PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN | | STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE | | MAINTAINED AT ALL TIMES. | | | | AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY | | EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL | | EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED | | WITH RESPECT TO THEIR DUTIES UNDER THE PLAN. | | | | EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED | | IN THE USE OF PORTABLE FIRE EXTINGUISHERS. | | | | SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE | | FIRE ALARM AND SPRINKLER SYSTEM. | | | | WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT | | SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED | | AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE | | MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM | | SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD | | INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY | | BE NEEDED. | | | | SUE ELLEN CALDERON | | FIRE INSPECTOR & INVESTIGATOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 804-4751 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2014-07-05 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-07-05 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-07-03 |
Time |
16:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-06-07 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-06-07 |
Time |
06:24 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-05-12 |
Time |
18:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-04-25 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-04-25 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-03-14 |
Time |
10:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2014-05-28 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2014-05-28 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2014-05-28 |
Time |
14:14 |
Sent To |
|
|
Notes |
2014-05-28 14:15:13 | PLAN REVIEW BY JS. PK1328 | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2014-04-18 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2014-04-18 |
Time |
07:51 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2014-04-16 |
Time |
13:11 |
Sent To |
|
|
Notes |
2014-04-18 07:51:28 | PLAN DENIED | | 1) PROVIDE MANUFACTURER'S INSTALLATION | | INSTRUCTIONS ON THE ELECTRIC UNIT HEATER. | | PER SECTION 107 FBC 2010 | | 2) REFER TO SECTION 604.8 LINING | | INSULATION. 2010 FBC (M) | | 3) REFER TO SECTION 503.2.1 CALCULATION OF | | HEATING AND COOLING. FLORIDA ENERGY CODE 2010 | | 4) REFER TO SECTION 503.2.4.4 SHUTOFF | | DAMPER CONTROLS. FLORIDA ENERGY CODE 2010 | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | |
|
|
Review Stop |
MEDGAS |
MEDICAL GAS |
Rev No |
2 |
Status |
P |
Date |
2014-06-07 |
|
|
Cont ID |
|
Sent By |
JWITMER |
Date |
2014-06-07 |
Time |
06:24 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-06-07 |
Time |
06:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
MEDGAS |
MEDICAL GAS |
Rev No |
1 |
Status |
F |
Date |
2014-04-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-04-14 |
Time |
18:49 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-04-14 |
Time |
18:00 |
Sent To |
|
|
Notes |
2014-04-14 18:51:06 | MED-GAS/PLUMBING PLAN REVIEW | | PERMIT: 14030562 | | ADD: 1875 PALM BCH LAKES # A09 | | CONT: TO BE DETERMINED | | TEL: (561)373-3902 / KARI | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | 1ST REVIEW | | DATE: MONDAY APRIL 14/ 2014 | | ACTION: DENIED | | | | 1) SHEET P1.1 PLEASE PROVIDE THE MANUFACTURERS SPEC | | SHEETS FOR THE FOLLOWING PLUMBING FIXTURES; | | | | 1A) ) OXY 1-3 HJC VENDOR CUT SHEETS 2010 FBC-P 1201.1 | | SCOPE. | | THE PROVISIONS OF THIS CHAPTER SHALL GOVERN THE DESIGN | | AND INSTALLATION OF PIPING AND STORAGE SYSTEMS FOR | | NONFLAMMABLE MEDICAL GAS SYSTEMS AND NONMEDICAL OXYGEN | | SYSTEMS. ALL MAINTENANCE AND OPERATIONS OF SUCH SYSTEMS | | SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION | | CODE. | | PLEASE PROVIDE A MED-GAS PLAN FOR THE OXYGEN UNDER A | | SEPERATE PERMIT. DETAILS CAN BE ONTHIS PLAN. REQUIRES A | | DIFFERNT PERMIT, BECAUSE OF THE INSPECTION CODES ARE | | DIFFERENT FROM THE PLUMBING. | | | | 1B) SB1, SB2 & SB3 SCAVENGER VACCUUM UNIT , DROPS AND | | WET TABLE OUTLETS. PLEASE PROVIDE THE MANUFACTURERS CUT | | SHEETS ON THEASE PRODUCTS. 2010 FBC-P 713.4 OR 713.5. | | THE PLANS DO NOT PROVIDE A CLEAR VIEW OF THE SCAVENGER | | VACCUUM UNIT AND PIPING LAYOUT NOR DOES THE PLANS | | INDICATE WHERE THE VENT ON THE PUMP IS GOING TO VENT | | TO. THE EXHAUSTS FROM A VACUUM PUMP SERVING A VACUUM | | (FLUID SUCTION) SYSTEM SHALL DISCHARGE SEPARATELY TO | | OPEN AIR ABOVE THE ROOF. 713.6. | | | | 2) SHEET P0.1 HEADING PB-7 2 /250 OXYGEN CYLINDERS | | PROVIDE DETAIL FOR SECURING TO WALL AND FOR THE | | MANIFOLD. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2014-06-07 |
|
|
Cont ID |
|
Sent By |
JWITMER |
Date |
2014-06-07 |
Time |
06:24 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-06-07 |
Time |
05:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2014-04-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-04-14 |
Time |
18:49 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-04-14 |
Time |
16:58 |
Sent To |
|
|
Notes |
2014-04-14 17:47:04 | PLUMBING PLAN REVIEW | | PERMIT: 14030562 | | ADD: 1875 PALM BCH LAKES # A09 | | CONT: TO BE DETERMINED | | TEL: (561)373-3902 / KARI | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | 1ST REVIEW | | DATE: MONDAY APRIL 14/ 2014 | | ACTION: DENIED | | | | 1) SHEET P1.1 PLEASE PROVIDE THE MANUFACTURERS SPEC | | SHEETS FOR THE FOLLOWING PLUMBING FIXTURES; | | | | 1A) TRENCH DRAINS AND IN ACCORDANCE WITH 2010 FBC-P | | 412.1 APPROVAL. | | TRENCH DRAINS SHALL COMPLY WITH ASME A112.6.3. | | | | 1B) IT-1 GOOSE NECK W/ 8'-0" VINYL HOSE 2010 FBC-P | | 424.6 HOSE-CONNECTED OUTLETS. | | FAUCETS AND FIXTURE FITTINGS WITH HOSE-CONNECTED | | OUTLETS SHALL CONFORM TO ASME A112.18.3M OR CSA B125. | | | | 1C) OXY 1-3 HJC VENDOR CUT SHEETS 2010 FBC-P 1201.1 | | SCOPE. | | THE PROVISIONS OF THIS CHAPTER SHALL GOVERN THE DESIGN | | AND INSTALLATION OF PIPING AND STORAGE SYSTEMS FOR | | NONFLAMMABLE MEDICAL GAS SYSTEMS AND NONMEDICAL OXYGEN | | SYSTEMS. ALL MAINTENANCE AND OPERATIONS OF SUCH SYSTEMS | | SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION | | CODE. | | PLEASE PROVIDE A MED-GAS PLAN FOR THE OXYGEN UNDER A | | SEPERATE PERMIT. DETAILS CAN BE ONTHIS PLAN. REQUIRES A | | DIFFERNT PERMIT, BECAUSE OF THE INSPECTION CODES ARE | | DIFFERENT FROM THE PLUMBING. | | | | 1D) SB1, SB2 & SB3 SCAVENGER VACCUUM UNIT , DROPS AND | | WET TABLE OUTLETS. PLEASE PROVIDE THE MANUFACTURERS CUT | | SHEETS ON THEASE PRODUCTS. 2010 FBC-P 713.4 OR 713.5. | | THE PLANS DO NOT PROVIDE A CLEAR VIEW OF THE SCAVENGER | | VACCUUM UNIT AND PIPING LAYOUT NOR DOES THE PLANS | | INDICATE WHERE THE VENT ON THE PUMP IS GOING TO VENT | | TO. THE EXHAUSTS FROM A VACUUM PUMP SERVING A VACUUM | | (FLUID SUCTION) SYSTEM SHALL DISCHARGE SEPARATELY TO | | OPEN AIR ABOVE THE ROOF. 713.6. | | | | 2) SHEET P0.1 HEADING PB-7 2 /250 OXYGEN CYLINDERS | | PROVIDE DETAIL FOR SECURING TO WALL AND FOR THE | | MANIFOLD. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] |
|
|
Review Stop |
POLICE |
POLICE |
Rev No |
1 |
Status |
N |
Date |
2014-04-25 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-04-25 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2014-05-27 |
|
|
Cont ID |
|
Sent By |
ESCHNEID |
Date |
2014-05-27 |
Time |
16:47 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2014-05-27 |
Time |
16:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2014-04-02 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2014-04-02 |
Time |
09:16 |
Rev Time |
1.00 |
Received By |
eschneid |
Date |
2014-04-02 |
Time |
09:16 |
Sent To |
|
|
Notes |
2014-04-02 13:05:41 | FAILED | | | | PROVIDE RESPONSES IN WRITING. | | | | 1) THE PALM BEACH OUTLETS MANAGEMENT APPROVAL STAMP IS | | NOT PROVIDED ON THE PLANS. | | | | 2) WHAT IS THE PLAN/LOCATION FOR THE DOG WALK FOR PETS | | UNDER VETERINARY CARE? | | | | 3) BASED ON EXPERIENCE AT THE OKEECHOBEE BOULEVARD | | PET'S MART LOCATION, PLEASE PROVIDE A NARRATIVE ON HOW | | THE DOG POOP FROM DOGS BROUGHT TO THE STORE WILL BE | | CLEANED UP FROM THE LANDSCAPE ISLANDS AND SIDEWALKS IN | | FRONT OF THE STORE. THE INSTALLATION OF DISPOSAL BAG | | STATIONS SHALL BE STATED ON THE PLANS. | | | | 4) THE NEW TRASH CAN/ASH DISPOSAL SHOWN FOR OUTSIDE THE | | STORE SHALL BE THE SAME STYLE AS THOSE PROVIDED BY THE | | PALM BEACH OUTLETS FOR THE REMAINDER OF THE IN-LINE | | RETAIL ALONG I-95. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | 2014-03-28 09:49:55 | 3/28/14 |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |