| BUILDING PLAN REVIEW |
| REVISION: 14030431 |
| PERMIT: 13100374 |
| ADD: 2921 N AUSTRALIAN AVE. |
| CONT: DB K INDUSTRIES |
| TEL: (561)827-4920 JAMES STINSON |
| |
| 1ST REVIEW |
| DATE: SAT. MARCH 22/ 2014 |
| ACTION: DENIED |
| |
| 1) SHOP DRAWING FOR HANDRAIL DOES NOT INDICATE WHERE |
| THE LANDING IS LOCATED. IT APPEARS EITHER A SECTION IS |
| INCORPORATED INTO THE ELEVATION DRAWING SHOWING THE |
| BOTTOM POST AND SLAB BEING CORED OR ANOTHER RISER, |
| PLEASE IDENTIFY WHAT IS BEING ILLUSTRATED. |
| |
| 2) THE SHOP DRAWING FOR A HANDRAIL WILL NEED TO COMPLY |
| WITH THE 2010 FL ACCESSIBILITY CODE 504.6 HANDRAILS. |
| STAIRS SHALL HAVE HANDRAILS COMPLYING WITH 505. |
| 505.2 WHERE REQUIRED. HANDRAILS SHALL BE PROVIDED ON |
| BOTH SIDES OF STAIRS AND RAMPS. |
| |
| 2A) 505.10 HANDRAIL EXTENSIONS. HANDRAIL GRIPPING |
| SURFACES SHALL EXTEND BEYOND AND IN THE SAME DIRECTION |
| OF STAIR FLIGHTS AND RAMP RUNS IN ACCORDANCE WITH |
| 505.10. |
| 2B) |
| 05.10.2 TOP EXTENSION AT STAIRS. AT THE TOP OF A STAIR |
| FLIGHT, HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE |
| LANDING FOR 12 INCHES (305 MM) MINIMUM BEGINNING |
| DIRECTLY ABOVE THE FIRST RISER NOSING. EXTENSIONS SHALL |
| RETURN TO A WALL, GUARD, OR THE LANDING SURFACE, OR |
| SHALL BE CONTINUOUS TO THE HANDRAIL OF AN ADJACENT |
| STAIR FLIGHT. |
| |
| 2C) 505.10.3 BOTTOM EXTENSION AT STAIRS. AT THE BOTTOM |
| OF A STAIR FLIGHT, HANDRAILS SHALL EXTEND AT THE SLOPE |
| OF THE STAIR FLIGHT FOR A HORIZONTAL DISTANCE AT LEAST |
| EQUAL TO ONE TREAD DEPTH BEYOND THE LAST RISER NOSING. |
| EXTENSION SHALL RETURN TO A WALL, GUARD, OR THE LANDING |
| SURFACE, OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN |
| ADJACENT STAIR FLIGHT. |
| |
| 3) PLEASE NOTE: THIS BUILDING IS BEING CONVERTED INTO A |
| FUNERAL HOME. THE OWNER HAS NOT APPLIED FOR A CHANGE OF |
| OCCUPANCY PERMIT. NOR WILL A CHANGE OF OCCUPANCY PERMIT |
| BE GRANTED. THIS IS A ZONING ISSUE ANGELLIA JONES VANN |
| MADE THE OWNER AWARE OF LAST YEAR. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |