Plan Review Details - Permit 14030309
Plan Review Stops For Permit 14030309
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2014-10-03 Cont ID  
Sent By jgomez Date 2014-10-03 Time 17:13 Rev Time 0.00
Received By jgomez Date 2014-10-03 Time 17:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2014-08-21 Cont ID  
Sent By jgomez Date 2014-08-21 Time 10:56 Rev Time 0.00
Received By jgomez Date 2014-08-21 Time 10:56 Sent To  
Notes
2014-08-21 10:56:50RESIDENTIAL (R3) REVISION FIFTH CHECKLIST:
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR THE "NEW DOOR TYPE A STEEL DOOR". NO
 PRODUCT APPROVAL WAS SUBMITTED THIS TIME.
  
  
 ***** PREVIOUS COMMENTS REGARDING SITE SPECIFIC DOOR
 PRODUCT APPROVAL:
  
 1- PRODUCT APPROVAL INFORMATION SUBMITTED FOR CUSTOM
 DOOR "A" NEED THE FOLLOWING INFORMATION FOR ROBERT
 BROWN (BUILDING OFFICIAL) APPROVAL (PRODUCT APPROVAL
 REQUIRED BY DCA RULE 9N-3):
 A) WHERE WAS EXISTING DOOR TAKEN FROM?. PLANS DON'T
 SHOW ANY DOOR TO BE REMOVED.
 B) SIGNED AND SEALED COMPLETE ENGINEER DOOR COMPARATIVE
 ANALYSIS.
 C) ENGINEER TO REVISE THE DESIGN LOAD PER PERMITTED
 DRAWINGS. -29.3 PSF DESIGN LOAD DOESN'T MATCH APPROVED
 DRAWINGS.
 D) ENGINEER TO PROVIDE COMPLETE INFORMATION FOR THE
 HISTORIC DOOR. WOOD TYPE, THICKNESS, GLASS: TYPE,
 THICKNESS, SIZES, ETC.
 E) ENGINEER TO PROVIDE COMPLETE HISTORIC DOOR JAMB
 SPECIFICATIONS AND ATTACHMENT TO THE STRUCTURE.
 F) ENGINEER TO PROVIDE COMPLETE DOOR OPENING FRAMING
 DETAILS AND SPECIFICATIONS.
  
 ***NOTE: ENGINEER TO CONTACT ROBERT BROWN (BUILDING
 OFFICIAL) TO COORDINATE PRODUCT APPROVAL REQUIRED
 INFORMATION. CALL (561)805-6652 OR E-MAIL
 [email protected].
  
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC. (REPEAT COMMENT).
  
  
 ***NOTE: PLEASE PROVIDE A RESPONSE LETTER ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-07-01 Cont ID  
Sent By jgomez Date 2014-06-24 Time 14:51 Rev Time 0.00
Received By jgomez Date 2014-06-24 Time 14:51 Sent To  
Notes
2014-06-24 14:51:41RESIDENTIAL (R3) REVISION COMMENTS.
 CODE: 2010 FBC.
  
 1- PRODUCT APPROVAL INFORMATION SUBMITTED FOR CUSTOM
 DOOR "A" NEED THE FOLLOWING INFORMATION FOR ROBERT
 BROWN (BUILDING OFFICIAL) APPROVAL (PRODUCT APPROVAL
 REQUIRED BY DCA RULE 9N-3):
 A) WHERE WAS EXISTING DOOR TAKEN FROM?. PLANS DON'T
 SHOW ANY DOOR TO BE REMOVED.
 B) SIGNED AND SEALED COMPLETE ENGINEER DOOR COMPARATIVE
 ANALYSIS.
 C) ENGINEER TO REVISE THE DESIGN LOAD PER PERMITTED
 DRAWINGS. -29.3 PSF DESIGN LOAD DOESN'T MATCH APPROVED
 DRAWINGS.
 D) ENGINEER TO PROVIDE COMPLETE INFORMATION FOR THE
 HISTORIC DOOR. WOOD TYPE, THICKNESS, GLASS: TYPE,
 THICKNESS, SIZES, ETC.
 E) ENGINEER TO PROVIDE COMPLETE HISTORIC DOOR JAMB
 SPECIFICATIONS AND ATTACHMENT TO THE STRUCTURE.
 F) ENGINEER TO PROVIDE COMPLETE DOOR OPENING FRAMING
 DETAILS AND SPECIFICATIONS.
  
 ***NOTE: ENGINEER TO CONTACT ROBERT BROWN (BUILDING
 OFFICIAL) TO COORDINATE PRODUCT APPROVAL REQUIRED
 INFORMATION. CALL (561)805-6652 OR E-MAIL
 [email protected].
  
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC. (REPEAT COMMENT).
  
 3- ENGINEER TO REVISE PLANS SHOWING:
 A) SAFETY GLASS FOR WINDOW ADJACENT TO THE SPA. SEC.
 R308.4(6).
 ***NOTE: 3M SAFETY & SECURITY WINDOW FILM SPECS WERE
 PROVIDED. ENGINEER TO REVISE PLANS SHOWING THE
 INSTALLATION OF THIS 3M FILM AS THE PROPOSED MEANS OF
 COMPLYIING WITH THE SAFETY GLASS REQUIREMENTS.
 SEC. 104.11 CITY AMENDMENTS TO FBC (ALTERNATIVE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION AND
 EQUIPMENT).
  
 B) SAFETY GLASS FOR WINDOW ADJACENT TO THE NEW STAIRWAY
 (TOP AND BOTTOM). SEC. R308.4.(7) AND SEC. R308.4(8).
 (***NOTE: SAME RESPONSE TO ITEM #3(A) ABOVE APPLIES).
  
 ***NOTE: PLEASE PROVIDE A RESPONSE LETTER ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-05-21 Cont ID  
Sent By albarran Date 2014-06-06 Time 09:44 Rev Time 0.00
Received By jgomez Date 2014-05-21 Time 17:01 Sent To  
Notes
2014-05-21 17:03:41RESIDENTIAL (R3) REVISION THIRD CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
  
 A) PROPOSED CUSTOM DOOR "A" SPECIFIED ON PLANS.
 (***NOTE: THE DOOR DOESN'T HAVE TO BE IMPACT BECAUSE OF
 THE 25% EXCEPTION ON SEC. 606.4 OF 2010 FBC-EXISTING
 BUILDING. ****NOTE***** GLAZING IN DOOR NEEDS TO COMPLY
 WITH THE SAFETY GLASS REQUIRED BY HAZARDOUS LOCATION
 SEC. R308.4(1). A PRODUCT APPROVAL IS STILL REQUIRED
 FOR ALL NEW DOORS. HISTORIC DOESN'T WAIVE THIS
 REQUIREMENT).
  
 *******RESPONSE TO INFORMATION SUBMITTED:
 (A) NO DOOR PRODUCT APPROVAL WAS SUBMITTED. ONLY
 INFORMATION FOR HURRICANE SHUTTERS WAS SUBMITTED.
  
 (B) PROVIDE FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA
 FOR THE HURRICANE SHUTTERS TO BE USED AS REQUIRED BY
 DCA RULE 9N-3. INFORMATION SUBMITTED IS NOT AN APPROVED
 PRODUCT APPROVAL. IF THERE IS NOT AN APPROVED FLORIDA
 OR MIAMI-DADE PRODUCT APPROVAL, THEN MANUFACTURER MAY
 APPLY FOR LOCAL PRODUCT APPROVAL. ( NOTE: SHUTTERS ARE
 NOT REQUIRED. SEE ITEM 1(A) ABOVE).
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC. (REPEAT COMMENT).
  
 3- FLAT ROOF ASSEMBLY: RAS 117 CALCULATIONS SUBMITTED
 NEED THE ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE WHEN SUBMITTING
 INFORMATION FOR PUBLIC RECORDS. COPIES ARE NOT ALLOWED.
  
 4- A)SPECIFY SAFETY GLASS FOR WINDOW ADJACENT TO THE
 SPA. SEC. R308.4(6).
 (***NOTE: HISTORIC DOESN'T WAIVE LIFE SAFETY ISSUES.
 THE LIFE SAFETY CONDITION WAS CREATED BY THE NEW
 ADDITION. PLEASE REVIEW SEC. 1104 AND SEC. 1105 OF THE
 2010 FBC-EXISTING BUILDING TO ADDRESS THE NEW LIFE
 SAFETY ISSUES).
  
 B) SPECIFY SAFETY GLASS FOR WINDOW ADJACENT TO THE NEW
 STAIRWAY (TOP AND BOTTOM). SEC. R308.4.(7) AND SEC.
 R308.4(8).
 (***NOTE: SAME RESPONSE TO ITEM #4(A) ABOVE APPLIES).
  
 *******RESPONSE TO INFORMATION SUBMITTED:
 (A) 3M SAFETY FILM INFORMATION SUBMITTED: NEED TO
 PROVIDE PROOF THAT FILM WAS TESTED IN ACCORDANCE WITH
 CPSC 16 CFR 1201 AS REQUIRED BY SEC. R308.3.1 OF 2010
 FBC-RESIDENTIAL.
  
 ***IMPORTANT: PLEASE CONFIRM WITH HISTORIC IF 3M SAFETY
 FILM IS ALLOWED.
  
  
  
 *******************NEW COMMENT:
  
 1- PROVIDE HURRICANE SHUTTERS COMPLETE INSTALLATION
 SCHEDULE. YOU MAY USE THE CITY SAMPLE OR PROVIDE ALL
 THE INFORMATION ON A DIFFERENT FORMAT AS LONG AS ALL
 THE REQUIRED INFORMATION IS PROVIDED. NEED THIS
 INFORMATION TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OS SEC. R301 OF 2010 FBC-RESIDENTIAL.
 (SHUTTERS ARE NOT REQUIRED. SEE ITEM 1(A) ABOVE.
  
  
 ***NOTE: PLEASE PROVIDE A RESPONSE LETTER ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-30 Cont ID  
Sent By jgomez Date 2014-04-30 Time 18:15 Rev Time 0.00
Received By jgomez Date 2014-04-30 Time 14:15 Sent To  
Notes
2014-04-30 15:58:08RESIDENTIAL (R3) REVISION SECOND CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) PROPOSED CUSTOM DOOR "A" SPECIFIED ON PLANS.
 (***NOTE: THE DOOR DOESN'T HAVE TO BE IMPACT BECAUSE OF
 THE 25% EXCEPTION ON SEC. 606.4 OF 2010 FBC-EXISTING
 BUILDING. A PRODUCT APPROVAL IS STILL REQUIRED FOR ALL
 NEW DOORS. HISTORIC DOESN'T WAIVE THIS REQUIREMENT).
  
 B) SIMPSON CONNECTOR A4 SPECIFIED ON ANCHOR SCHEDULE.
 FLORIDA PRODUCT APPROVAL FL 5550 IS NOT LISTED ON THE
 FLORIDA PRODUCT APPROVAL WEBSITE FOR THE 2010 CODE.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC.
 (***NOTE: ONLY THE FLAT ROOF NOA 13-0529.14 SUBMITTED
 WAS REVIEWED BY THE ENGINEER).
  
 3- FLAT ROOF INFORMATION SUBMITTED:
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) AS REQUIRED BY GENERAL LIMITATION #7 ON PAGE 19
 AND PAGE 27 OF NOA 13-0529.14 SUBMITTED. NEED THE
 CALCULATIONS TO MEET THE DESIGN PRESSURES OF SEC.
 R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
  
 4- A)SPECIFY SAFETY GLASS FOR WINDOW ADJACENT TO THE
 SPA. SEC. R308.4(6).
 (***NOTE: HISTORIC DOESN'T WAIVE LIFE SAFETY ISSUES.
 THE LIFE SAFETY CONDITION WAS CREATED BY THE NEW
 ADDITION. PLEASE REVIEW SEC. 1104 AND SEC. 1105 OF THE
 2010 FBC-EXISTING BUILDING TO ADDRESS THE NEW LIFE
 SAFETY ISSUES).
  
 B) SPECIFY SAFETY GLASS FOR WINDOWS ADJACENT TO THE NEW
 STAIRWAY (TOP AND BOTTOM). SEC. R308.4.(7) AND SEC.
 R308.4(8).
 (***NOTE: SAME RESPONSE TO ITEM #4(A) ABOVE APPLIES).
  
  
 ***NOTE: PLEASE PROVIDE A RESPONSE LETTER ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
2014-04-22 10:39:44R14
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-20 Cont ID  
Sent By JGOMEZ Date 2014-03-20 Time 15:15 Rev Time 0.00
Received By jgomez Date 2014-03-20 Time 15:01 Sent To  
Notes
2014-03-20 16:09:59REVISION, BUILDING REVIEW COMMENTS.
 CODE; 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) PROPOSED CUSTOM/IMPACT DOOR "A" SPECIFIED ON PLANS.
  
 B) PROPOSED CAST-CRETE 8F8-1B BEAM AS SHOWN ON
 FOUNDATION PLAN.
  
 C) FLAT ROOF.
 ***NOTE: CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED. AND, PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS IF THE APPROVED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 D) SIMPSON CONNECTOR A4 SPECIFIED ON ANCHOR SCHEDULE.
 FLORIDA PRODUCT APPROVAL FL11506 IS NOT LISTED ON THE
 FLORIDA PRODUCT APPROVAL WEBSITE FOR THE 2010 CODE.
  
 2- ENGINEER TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE SCREEN ENCLOSURE. OR PROVIDE
 COMPLETE INFORMATION UNDER A SEPARATE PERMIT. SEC.
 107.3.5.3 CITY AMENDMENTS.
  
 4- A) SPECIFY SIZES OF THE ROOF DRAIN SCUPPERS AND
 DOWNSPOUTS. SEC. R903.4.
  
 B) SPECIFY OVERFLOW DRAINS AND SCUPPERS SIZE AND
 LOCATION AS REQUIRED BY SEC. R903.4.1.
  
 5- SPECIFY HOW THE WATER FROM THE NEW ROOF IS GOING TO
 BE CONTROLLED SO IT DOESN'T GO TO THE NEIGHBOR'S
 PROPERTY. SEC. R401.3. THE WATER CAN'T BE DIVERTED TO
 THE NEIGHBORS PROPERTY.
  
 6- SPECIFY ROOF SLOPE. SEC. R905.11.
  
 7- PROVIDE HANDRAILS AS REQUIRED BY SEC. R311.7.7.
  
 8- A)SPECIFY SAFETY GLASS FOR WINDOW ADJACENT TO THE
 SPA. SEC. R308.4(6).
  
 B) SPECIFY SAFETY GLASS FOR WINDOW ADJACENT TO THE NEW
 STAIRWAY (TOP AND BOTTOM). SEC. R308.4.(7) AND SEC.
 R308.4(8).
  
 9- SPECIFY NEW PORCH ROOF CROSS VENTILATION. SEC. R806.
  
 10- A) CLARIFY WHERE IS SECTION 2/S-1 TAKEN AT?. AND B)
 REMOVE STAIRS ON EAST SIDE IF THEY ARE NOT GOING TO BE
 BUILT. DON'T CROSS OUT BY PEN. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 11- SHEET S-2:
 A) REVISE/CLARIFY INSTALLATION OF SIMPSON CONNECTOR A9
 (SIMPSON SP6) SPECIFIED ON SECTION 1/S-2. THIS IS AN
 STUD TO PLATE CONNECTOR, NOT JOIST CONNECTOR. OR
 PROVIDE COMPLETE ENGINEERING ANALYSIS SHOWING HOW THIS
 CONNECTOR WILL WORK AS PROPOSED. SEC. 107.2.1.3 CITY
 AMENDMENTS.
  
 B) SPECIFY HOW LONG ARE THE 1/2" J-BOLTS SPECIFIED ON
 SECTION 1/S-2 TO FASTEN THE 2X8 P.T. SILL TO THE 8"
 GROUT FILLED BOND BEAM OF THE STEM WALL. SEC. 107.2.1
 CITY AMENDMENTS.
  
 C) SPECIFY CONNECTORS AT THE ENDS OF 3-PLY VERSALAM LVL
 BEAMS SHOWN ON PLANS AT ALL THREE EXTERIOR WALLS AND
 THE INTERIOR BEAM HOLDING THE ROOF JOISTS. SEC. 107.2.1
 CITY AMENDMENTS.
  
 D) SPECIFY FINISH FLOOR DECKING AND FINISH CEILING AND
 FASTENING. SEC. 107.2.1 CITY AMENDMENTS.
  
 12- SHEET S-3:
 A) REVISE EXPOSURE . BUILDING EXPOSURE IS "C" NOT "B".
 SEC. R301.2.1.4.3
  
 B) REVISE DESIGN PRESSURES FOR ALL ROOF ZONES. ALSO,
 REVISE THE DOORS/WINDOWS DESIGN PRESSURES. SEC.
 R301.2.1.4.3.
  
 C) REVISE EXISTING BUILDING CODE NOTE: THIS IS NOT
 ALTERATION LEVEL 2. THIS IS AN ADDITION. SEC. 407 OF
 2010 FBC-EXISTING BUILDING.
  
  
 ***NOTE: PLEASE PROVIDE A RESPONSE LETTER ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-06-06 Cont ID  
Sent By albarran Date 2014-06-06 Time 09:18 Rev Time 0.00
Received By albarran Date 2014-05-22 Time 14:05 Sent To I
Notes
2014-06-06 09:38:25IT WAS NOT UNTIL YESTERDAY AFTERNOON THAT THE EC CAME
 IN TO THE OFFICE TO CORRECT THE PLANS. THE CORRECTED
 PLANS WERE STAMPED AND PROCESSED.
2014-05-22 14:48:16UPON THE THIRD REVIEW, THERE IS STILL ELECTRICAL
 VIOLATIONS AND DISCREPANCIES. I CONTACTED THE
 ELECTRICAL CONTRACTOR TO DISCUSS THESE ITEMS AND HE
 WILL STOP IN 5/23/14 TO CLARIFY THESE ISSUES.
2014-05-19 18:05:34RETURNED TO SMALL DENIED "R" FILE IS INCOMPLETE

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-04-22 Cont ID  
Sent By albarran Date 2014-04-22 Time 10:37 Rev Time 0.00
Received By albarran Date 2014-04-22 Time 10:16 Sent To B
Notes
2014-04-22 10:39:18NO ELECTRICAL SHEET OR SPECS OF ANY KIND WERE SUBMITTED
 FOR APPROVAL. BELOW IS A COPY OF THE NOTES FROM THE
 PREVIOUS REVIEW WHICH HAS BEEN IGNORED.
  
 ELECTRICAL REVIEW WAS DENIED DUE TO THE FOLLOWING:
 1.ELECTRICAL DRAWINGS COMPLYING WITH ALL OF THE
 REQUIREMENTS OF THE NEC SHALL BE SUBMITTED FOR REVIEW
 AND ACCEPTANCE.
 THE NEC HAS SPECIFIC OUTLET, SWITCHING AND LIGHTING
 PLACEMENT REQUIREMENTS THAT HAVE TO BE COMPLIED WITH.
 THERE ARE SPECIFIC REQUIREMENTS ASSOCIATED WITH THE SPA
 AS WELL THAT COME INTO PLAY AND SHALL BE ADDRESSED.
 LITERATURE ON THE PROPOSED SPA SHALL ACCOMPANY THE
 SUBMITTAL.
 NEC 680.43(B) HAS LIMITATIONS ON THE CEILING FAN ABOVE
 THE SPA.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-03-11 Cont ID  
Sent By MALBERAN Date 2014-03-11 Time 16:11 Rev Time 0.00
Received By albarran Date 2014-03-11 Time 15:52 Sent To B
Notes
2014-03-11 16:22:17ELECTRICAL REVIEW WAS DENIED DUE TO THE FOLLOWING:
 1.ELECTRICAL DRAWINGS COMPLYING WITH ALL OF THE
 REQUIREMENTS OF THE NEC SHALL BE SUBMITTED FOR REVIEW
 AND ACCEPTANCE.
 THE NEC HAS SPECIFIC OUTLET, SWITCHING AND LIGHTING
 PLACEMENT REQUIREMENTS THAT HAVE TO BE COMPLIED WITH.
 THERE ARE SPECIFIC REQUIREMENTS ASSOCIATED WITH THE SPA
 AS WELL THAT COME INTO PLAY AND SHALL BE ADDRESSED.
 LITERATURE ON THE PROPOSED SPA SHALL ACCOMPANY THE
 SUBMITTAL.
 NEC 680.43(B) HAS LIMITATIONS ON THE CEILING FAN ABOVE
 THE SPA.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2014-10-03 Cont ID  
Sent By fmittner Date 2014-10-03 Time 11:21 Rev Time 0.00
Received By fmittner Date 2014-10-03 Time 11:21 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2014-08-12 Cont ID  
Sent By fmittner Date 2014-08-12 Time 11:21 Rev Time 0.00
Received By fmittner Date 2014-08-12 Time 11:21 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2014-04-30 Cont ID  
Sent By fmittner Date 2014-04-30 Time 11:32 Rev Time 0.00
Received By fmittner Date 2014-04-30 Time 11:32 Sent To  
Notes
2014-04-17 14:47:45NEW SHEETS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-03-10 Cont ID  
Sent By fmittner Date 2014-03-10 Time 16:33 Rev Time 0.00
Received By fmittner Date 2014-03-10 Time 16:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2014-10-03 Cont ID  
Sent By jgomez Date 2014-10-03 Time 17:12 Rev Time 0.00
Received By jgomez Date 2014-10-03 Time 17:11 Sent To  
Notes
2014-10-03 17:12:34RECEIVED RE-SUBMITAL FROM HISTORIC. JG.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-08-21 Cont ID  
Sent By jgomez Date 2014-08-21 Time 14:32 Rev Time 0.00
Received By jgomez Date 2014-08-12 Time 17:57 Sent To  
Notes
2014-08-12 17:57:49TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-06-25 Cont ID  
Sent By jgomez Date 2014-06-24 Time 11:43 Rev Time 0.00
Received By jgomez Date 2014-06-19 Time 14:26 Sent To  
Notes
2014-06-24 14:27:18REVISION RESUBMITTAL SENT TO JULIO'S DESK FOR REVIEW.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-06-06 Cont ID  
Sent By albarran Date 2014-06-06 Time 09:44 Rev Time 0.00
Received By albarran Date 2014-05-15 Time   Sent To PC
Notes
2014-06-06 09:44:49PROCESSED AND SENT TO READY RACK
  
2014-05-16 08:37:30SENT TO J. GOMEZ FOR REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2014-04-30 Cont ID  
Sent By jgomez Date 2014-04-30 Time 18:15 Rev Time 0.00
Received By jgomez Date 2014-04-17 Time 14:51 Sent To  
Notes
2014-04-17 14:51:59RESUBMITTAL SENT TO R14 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-20 Cont ID  
Sent By jgomez Date 2014-03-20 Time 17:44 Rev Time 0.00
Received By jgomez Date 2014-03-10 Time 11:21 Sent To  
Notes
2014-03-11 11:21:46SENT TO ELECTRCAL BOX.

Review Stop Z ZONING
Rev No 5 Status P Date 2014-10-03 Cont ID  
Sent By fmittner Date 2014-10-03 Time 11:21 Rev Time 0.00
Received By fmittner Date 2014-10-03 Time 11:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2014-08-12 Cont ID  
Sent By fmittner Date 2014-08-12 Time 11:21 Rev Time 0.00
Received By fmittner Date 2014-08-12 Time 11:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2014-05-09 Cont ID  
Sent By dmalone Date 2014-05-09 Time 13:59 Rev Time 0.00
Received By dmalone Date 2014-05-08 Time 13:58 Sent To  
Notes
2014-05-09 13:59:17LANDSCAPE PERMIT APPLICATION RCVD 5/8/14. PERMIT
 14050276 ISSUED 5/9/14.
 SEE CONDITIONAL APPROVAL LETTER LINKED TO BLDG 7 CO
 (14030350,55,67,78,86,95,400). PRIOR TO ISSUANCE OF CO,
 MUST PASS FINAL IRRIGATION AND LANDSCAPE INSPECTIONS.
 DM 5/9/14
 X1562

Review Stop Z ZONING
Rev No 2 Status P Date 2014-04-30 Cont ID  
Sent By fmittner Date 2014-04-30 Time 11:33 Rev Time 0.00
Received By fmittner Date 2014-04-30 Time 11:33 Sent To  
Notes
2014-04-21 15:15:044/21/14
2014-04-17 14:47:16NEW SHEETS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-03-10 Cont ID  
Sent By fmittner Date 2014-03-10 Time 16:33 Rev Time 0.00
Received By fmittner Date 2014-03-10 Time 16:33 Sent To  
Notes
***NONE***