 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 13, A CURRENT (WITHIN 12-MONTHS) WATER FLOW
 TEST IS REQUIRED.
  
 SUBMIT PRODUCT CUT-SHEETS FOR RISER EQUIPMENT AND
 SPRINKLERS TO BE INSTALLED.
  
 A HYDRAULIC SAFETY FACTOR OF 0.973 PSI IS INSUFFICIENT.
 DAILY FLUCTUATIONS IN THE WATER PRESSURE MAY RESULT IN
 A SPRINKLER SYSTEM THAT IS PRESSURE DEFICIENT TO
 OPERATE PROPERLY.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-08 Cont ID  
Sent By hmoser Date 2014-05-08 Time 08:01 Rev Time 0.00
Received By hmoser Date 2014-04-29 Time 16:44 Sent To  
Notes
2014-04-29 16:44:29TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-07 Cont ID  
Sent By hmoser Date 2014-04-07 Time 14:42 Rev Time 0.00
Received By hmoser Date 2014-03-10 Time 11:29 Sent To  
Notes
2014-03-10 11:30:02ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-05-08 Cont ID  
Sent By hmoser Date 2014-05-08 Time 08:01 Rev Time 0.00
Received By hmoser Date 2014-05-08 Time 07:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-04-07 Cont ID  
Sent By hmoser Date 2014-04-07 Time 14:42 Rev Time 0.00
Received By hmoser Date 2014-04-07 Time 14:41 Sent To  
Notes
2014-04-07 14:42:24PLAN DENIED SEE FIRE COMMENTS.