Plan Review Details - Permit 14030223
Plan Review Stops For Permit 14030223
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-03-14 Cont ID  
Sent By jgomez Date 2014-03-14 Time 11:53 Rev Time 0.00
Received By jgomez Date 2014-03-14 Time 11:53 Sent To  
Notes
2014-03-14 11:59:233/14/14 TALKED TO ENGINEER MARK MESIANO. HE SAID THE
 RAS 117 CALCULATIONS ARE OK BASED ON THE TAS 105 TEST.
 JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-07 Cont ID  
Sent By jgomez Date 2014-03-07 Time 13:23 Rev Time 0.00
Received By jgomez Date 2014-03-07 Time 13:03 Sent To  
Notes
2014-03-07 13:35:41COMMERCIAL BUILDING, REROOF REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE FIELD WITHDRAWAL TEST (TAS 105) AS REQUIRED
 BY GENERAL LIMITATION #5 ON LAST PAGE OF NOA 13-0204.02
 SUBMITTED. SEC. 1609 OF 2010 FBC.
  
 2- ENGINEER TO PROVIDE RAS 117 CALCULATIONS USING THE
 FASTENER VALUE BASED ON THE RESULTS OF THE FIELD
 WITHDRAWAL TEST (TAS 105) AS REQUIRED BY ITEM #1 ABOVE.
 SEC. 1609 OF 2010 FBC.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION WAS
 UPDATED TO $81,090 AS REQUIRED BY SEC. 109.3 OF CITY
 AMENDMENTS TO FBC. THE PERMIT FEE BALANCE IS $1971.72.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-03-14 Cont ID  
Sent By jgomez Date 2014-03-14 Time 11:51 Rev Time 0.00
Received By jgomez Date 2014-03-14 Time 11:50 Sent To  
Notes
2014-03-14 11:51:18TAS 105 TEST RESULTS SUBMITTED. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-07 Cont ID  
Sent By jgomez Date 2014-03-07 Time 13:03 Rev Time 0.00
Received By jgomez Date 2014-03-07 Time 13:03 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved