Plan Review Details - Permit 14030171
Plan Review Stops For Permit 14030171
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-04-18 Cont ID  
Sent By jwitmer Date 2014-04-18 Time 13:04 Rev Time 0.00
Received By jwitmer Date 2014-04-18 Time 12:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-25 Cont ID  
Sent By jwitmer Date 2014-03-25 Time 17:59 Rev Time 0.00
Received By jwitmer Date 2014-03-25 Time 15:37 Sent To  
Notes
2014-03-25 17:59:00BUILDING PLAN REVIEW
 PERMIT: 14030171
 ADD: 1501 NORTHPOINT PKWY # 101
 CONT: ALONSO & ASSOCIATES
 TEL: (561)837-9820
  
 1ST REVIEW
 DATE: TUESDAY MARCH 25/2014
 ACTION: DENIED
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1) SHEET A1 THE MERCANTILE/ BUSSINESS OCCUPANCY HAS A
 COMBINED OCCUPANT LOAD OF 66 OCCUPANTS, BUT ONLY ONE
 MEANS OF EGRESS, THE MAIN ENTRY. 2010 FBC-B 1015.1 &
 TABLE 1015.1. THE PLANS INDICATE A 2ND MEANS OF EGRESS
 THROUGH THE EXISTING WAREHOUSE. THE BUSINESS AND
 MERCANTILE OCCUPANTS CAN NOT USE THIS AS A EXIT SINCE
 IT IS A MORE HAZARDOUS OCCUPANCY UNLESS A EXIT
 PASSAGEWAY IS BUILT (2HR) SEPERATING THE WAREHOUSE FROM
 THE EXIT PASSAGEWAY.
  
 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
 1. EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH
 ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE
 SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE
 ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H
 OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS
 TRAVEL TO AN EXIT.
 EXCEPTION: MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 ADJOINING OR INTERVENING ROOMS OR SPACES IN A GROUP H,
 S OR F OCCUPANCY WHEN THE ADJOINING OR INTERVENING
 ROOMS OR SPACES ARE THE SAME OR A LESSER HAZARD
 OCCUPANCY GROUP.
  
 2) THE E-1 SHEET SHOWS THE EXIT LIGHT IN THE BUSINESS/
 MERCANTILE OCCUPANCY SHOWING THE TENANTS THE EXIT
 TRAVEL THROUGH THE WAREHOUSE IS ACCEPTABLE. PLEASE
 PLACE THE EXIT LIGHT ON THE WAREHOUSE SIDE, THE
 OCCUPANTS FROM THE WAREHOUSE CAN USE THE DOOR LEADING
 INTO THE MERCANTILE/ BUSINESS OCCUPANCY AS A APPROVED
 EXIT.
 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
 1. EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH
 ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE
 SUCH ADJOINING ROOMS OR AREAS AND THE AREA SERVED ARE
 ACCESSORY TO ONE OR THE OTHER, ARE NOT A GROUP H
 OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS
 TRAVEL TO AN EXIT.
 EXCEPTION: MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 ADJOINING OR INTERVENING ROOMS OR SPACES IN A GROUP H,
 S OR F OCCUPANCY WHEN THE ADJOINING OR INTERVENING
 ROOMS OR SPACES ARE THE SAME OR A LESSER HAZARD
 OCCUPANCY GROUP 2010 FBC-B.
  
 3) SHEET A-2 PLEASE PROVIDE ADDITIONAL INFORMATION:
 3A) THE PLANS INDICATE A NEW EXHIBITION ROOM WITH
 ABBRIVIATIONS, SD/1. FD/1, LS/1, FD/2, CW/1 FR/1 AND
 DH/1. NONE OF THESE ABBREVIATIONS ARE FOUND UNDER THE
 ABBREVIATION LIST FOUND ON SHEET 1 NOR ARE THERE
 SECTIONS OR DETAILS PROVIDING ADDITIONAL INFORMATION.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3B) SINCE THIS IS A EXHIBITION ROOM IT APPEARS THAT THE
 CUSTOMERS ARE SUPPOSE TO BE ABLE TO ENTER THE
 EXHIBITION ROOM. THE PLANS INDICATE THE FINISH FLOOR TO
 BE RAISED UP 2 INCHES BUT NO DETAILS TO WHAT IS RAISING
 UP THE FLOOR. SHEET A-1 INDICATED THIS BUILDING IS A
 TYPE I-B STRUCTURE, PLEASE PROVIDE DETAILS ON THE
 RAISED FLOOR, SEE 2010 FBC-B 603.1 WHERE FIRE RETARDANT
 TREATED MATERIALS MAY BE INSTALLED AS WELL AS 805 FOR
 WHERE COMBUSTIBLE MATERIALS CAN BE USED IN TYPE I & II
 CONSTRUCTION FLOORING AND SUBFLOOR CONSTRUCTION.
  
 3C) IT WOULD ALSO APPEAR THE CLIENTS CAN ENTER THE
 EXHIBITION ROOM PLEASE PROVIDE COMPLIANCE WITH VERTICAL
 ACCESSIBILITY. 2010 FBC- ACCESSIBILITY CODE 405.2 ALSO
 SEE TABLE 405.2 SLOPES FOR EXISTING SITES.
  
 3D) WALL LEGEND HAS HAND WRITTEN NOTES METAL STUDS, 603
 NO CONCEALED COMBUTIBLES AND PART FO THE STATEMENT
 STRUCK ABOUT THE USE OF WOOD STUDS. 603.1 ALLOWABLE
 MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
  
 3E) WITHIN THE SAME STATEMENT THE DESIGNER OF RECORD
 GIVES THE CONTRACTOR OPTIONS METAL OR WOOD. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 3F) THE UNISEX RESTROOM INDICATES THE USE OF A 32" WIDE
 DOOR. 2010 FBC-B 1008.1.1 SIZE OF DOORS. THE MINIMUM
 WIDTH OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE
 OCCUPANT LOAD THEREOF AND SHALL PROVIDE A CLEAR WIDTH
 OF 32 INCHES (813 MM). CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES
 (1.57 RAD).
  
 4) SHEET A-3 R-30 INSULATION IS LAYED DIRECTLY ON THE
 LAY-IN ACOUSTICAL CEILING. 2010 FBC- ENERGY 502.2.1.2
 CEILING INSULATION. INSULATION INSTALLED ON A SUSPENDED
 CEILING WITH REMOVABLE CEILING TILES SHALL NOT BE
 CONSIDERED PART OF THE MINIMUM THERMAL RESISTANCE OF
 THE ROOF INSULATION UNLESS THE ROOF/CEILING CAVITY IS
 SEALED FROM THE EXTERIOR ENVIRONMENT.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-04-18 Cont ID  
Sent By skennedy Date 2014-04-18 Time 11:13 Rev Time 0.00
Received By skennedy Date 2014-04-18 Time 11:13 Sent To  
Notes
2014-04-11 09:00:31NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-04-08 Cont ID  
Sent By rlecky Date 2014-04-08 Time 11:36 Rev Time 0.00
Received By rlecky Date 2014-04-08 Time 10:17 Sent To  
Notes
2014-04-08 11:37:24AUDITED PER FS 553.791

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2014-04-18 Cont ID  
Sent By skennedy Date 2014-04-18 Time 11:12 Rev Time 0.00
Received By skennedy Date 2014-04-18 Time 11:11 Sent To  
Notes
2014-04-18 11:12:40RESTAMP BY SAK OK'ED W/ PML.
2014-04-11 09:00:51NEW SHEETS SUBMITTED. JG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-03-12 Cont ID  
Sent By pleduc Date 2014-03-12 Time 11:18 Rev Time 0.00
Received By pleduc Date 2014-03-12 Time 09:27 Sent To E
Notes
2014-03-12 11:18:39THE PERMIT PLAN WAS REVIEWED AND APPROVED WITH THE
 FOLLOWING COMMENTS BY PETER LEDUC, FIRE MARSHAL, BUREAU
 OF FIRE PREVENTION, WEST PALM BEACH FIRE RESCUE.
  
 1. ANY AND ALL WORK ON THE FIRE ALARM OR SPRINKLER
 SYSTEM SHALL BE DONE BY ACERTIFIED CONTRACTOR. SEPARATE
 SHOP DRAWINGS COMPLIANT WITH THE NFPA CODE IS REQUIRED
 TO BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE
 PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 2. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-18 Cont ID  
Sent By jwitmer Date 2014-04-18 Time 13:04 Rev Time 0.00
Received By jwitmer Date 2014-04-09 Time 08:59 Sent To  
Notes
2014-04-11 09:00:13RESUBMITTAL SENT TO B14 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-04-08 Cont ID  
Sent By rlecky Date 2014-04-08 Time 11:37 Rev Time 0.00
Received By rlecky Date 2014-03-05 Time 10:30 Sent To  
Notes
2014-03-07 10:30:42SENT TO B4 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-03-25 Cont ID  
Sent By jwitmer Date 2014-03-25 Time 18:00 Rev Time 0.00
Received By jwitmer Date 2014-03-25 Time 15:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-04-18 Cont ID  
Sent By jwitmer Date 2014-04-18 Time 13:03 Rev Time 0.00
Received By jwitmer Date 2014-04-18 Time 12:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-03-28 Cont ID  
Sent By rregueir Date 2014-03-28 Time 13:22 Rev Time 0.00
Received By rregueir Date 2014-03-28 Time 13:22 Sent To  
Notes
2014-03-28 13:32:54AUDIT #: 1ST
 ACTION: DENIED
  
 FBC 2010 W/ 2012 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THIS IS AN AUDIT OF A PLAN SUBMITTED FOR PERMIT UNDER
 THE PROVISIONS OF FS 553.791. PLEASE ADDRESS THE
 FOLLOWING COMMENTS AND RESUBMIT:
  
 1. NO INFORMATION WAS PROVIDED REGARDING VENTILATION
 FOR THE NEWLY RECONFIGURED SPACES. PROVIDE VENTILATION
 CALCULATIONS WITH OCCUPANT LOADS BASED ON THE OCCUPANCY
 TYPES FOUND IN FBC-M TABLE 403.3 IN ACCORDANCE WITH
 FBC-EB 909.1.
  
 2. PAGE A-4 SHOWS THE RETURN AIR GRILL FOR AHU-1 BEING
 MOVED. THERE IS NOTHING ON THE PLANS SHOWING HOW
 BALANCED RETURN AIR IS TO BE ACHIEVED IN THE CONFERENCE
 ROOM. PROVIDE BALANCED RETURN PER FBC-M 601.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-04-18 Cont ID  
Sent By jwitmer Date 2014-04-18 Time 12:21 Rev Time 0.00
Received By jwitmer Date 2014-04-18 Time 12:21 Sent To  
Notes
2014-04-11 09:01:19NEW SHEETS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-03-25 Cont ID  
Sent By jwitmer Date 2014-03-25 Time 18:00 Rev Time 0.00
Received By jwitmer Date 2014-03-25 Time 17:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2014-04-14 Cont ID  
Sent By sgraham Date 2014-04-14 Time 15:58 Rev Time 0.00
Received By ajones Date 2014-04-14 Time 15:58 Sent To  
Notes
2014-04-14 11:42:234/14/14
2014-04-11 09:01:44NEW SHEETS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-03-12 Cont ID  
Sent By sgraham Date 2014-03-12 Time   Rev Time 0.00
Received By sgraham Date 2014-03-12 Time   Sent To B
Notes
***NONE***