Plan Review Details - Permit 14030103
Plan Review Stops For Permit 14030103
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-04-11 Cont ID  
Sent By jgomez Date 2014-04-11 Time 09:06 Rev Time 0.00
Received By jgomez Date 2014-04-11 Time 09:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-04-07 Cont ID  
Sent By jgomez Date 2014-04-07 Time 09:13 Rev Time 0.00
Received By jgomez Date 2014-04-07 Time 08:54 Sent To  
Notes
2014-04-07 09:12:54REROOF, THIRD BUILDING REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- STEEL DECK:
 A) FLAT ROOF ASSEMBLY SELECTED ON THE RAS 117
 CALCULATIONS SUBMITTED NOW DOESN'T MATCH ASSEMBLY SHOWN
 ON THE NOA 13-0424.13 SUBMITTED. REVISE AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 B) REVISE RAS 117 CALCULATIONS SUBMITTED. BASE SHEET
 FASTENING DOESN'T WORK FOR ROOF ZONES #2 AND #3 FOR THE
 CALCULATED DESIGN PRESSURES. SEC. 1609 FBC.
  
 2- WOOD DECK:
 A)REVISE RAS 117 CALCULATIONS. BASE SHEET FASTENING
 DOESN'T WORK FOR ROOF ZONES # 2 AND #3 FOR THE
 CALCULATED DESIGN PRESSURES. SEC. 1609 FBC. REVISE AS
 REQUIRED. (REPEAT COMMENT. NOT ADDRESSED).
  
 ***NOTES: ANY ROOF EQUIPMENT REMOVAL OR RETROFIT ROOF
 DRAINS REQUIRE SEPARATE PERMITS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-03-28 Cont ID  
Sent By jgomez Date 2014-03-28 Time 17:26 Rev Time 0.00
Received By jgomez Date 2014-03-28 Time 15:35 Sent To  
Notes
2014-03-28 16:01:57REROOF, SECOND BUILDING REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- STEEL DECK:
 A) PROVIDE COMPLETE RAS 117 CALCULATIONS USING THE
 RESULTS OF THE WITHDRAWAL TEST REPORT (TAS 105) AS
 REQUIRED BY GENERAL LIMITATION #6 ON LAST PAGE OF NOA
 13-0424.13 SUBMITTED. INFORMATION SUBMITTED ARE NOT RAS
 117 CALCULATIONS. SEC. 1609 OF 2010 FBC. ***NOTE:
 COORDINATE WITH ITEM #1(C) BELOW.
  
 B) CLARIFY WHY THE DESIGN PRESSURES FOR THE WOOD DECK
 ARE DONE BASED ON BUILDING EXPOSURE "D", WHILE THE
 DESIGN PRESSURES FOR THE STEEL DECK ARE DONE BASED ON
 BUILDING EXPOSURE "B". WHY TWO DIFFERENT BUILDING
 EXPOSURES ON THE SAME BUILDING?. REVISE AS REQUIRED.
 ***NOTE: ACCORDING TO SEC. 1609 THIS BUILDING IS
 LOCATED IN EXPOSURE"C".
  
 C) CAREFULLY READ THE SELECTED ASSEMBLY ON PAGE 14 OF
 NOA 13-0424.13 SUBMITTED. THIS ASSEMBLY REQUIRES THE
 INSULATION TO BE MECHANICALLY FASTENED. THE RAS 117
 CALCULATIONS APPLY TO THE INSULATION FASTENING.
 COORDINATE WITH ITEM #1(A) ABOVE. SEC. 1609 FBC.
  
  
 2- WOOD DECK:
 A)REVISE RAS 117 CALCULATIONS. BASE SHEET FASTENING
 DOESN'T WORK FOR ROOF ZONES # 2 AND #3 FOR THE
 CALCULATED DESIGN PRESSURES. PROVIDE THE RAS 117
 CALCULATIONS AND REVISE AS REQUIRED. COORDINATE WITH
 ITEM #1(B) ABOVE. SEC. 1609 FBC.
  
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL, LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT, AND ALL DESIGN
 PROFESSIONAL FEES. SEC. 109.3 CITY AMENDMENTS TO FBC.
 VALUATION WAS UPDATED TO $84,760 FOR 13,000 S.F. OF
 ROOF AREA =/- . THE PERMIT FEE BALANCE IS $2115.39.
  
 ***NOTES: ANY ROOF EQUIPMENT REMOVAL OR RETROFIT ROOF
 DRAINS REQUIRE SEPARATE PERMITS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-20 Cont ID  
Sent By jgomez Date 2014-03-19 Time 18:27 Rev Time 0.00
Received By jgomez Date 2014-03-19 Time 18:19 Sent To  
Notes
2014-03-19 18:27:33REROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- STEEL DECK:
 A) PROVIDE FASTENER WITHDRAWAL TEST (TAS 105) AS
 REQUIRED BY GENERAL LIMITATION #5 ON LAST PAGE OF NOA
 13-0424.13 SUBMITTED. SEC. 1609 OF 2010 FBC.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON PAGE 14 OF NOA
 13-0424.13 SUBMITTED.
  
 2- WOOD DECK:
 A) NOA 12-1003.05 SPECIFIED ON THE RAS 117 CALCULATIONS
 SUBMITTED DOESN'T MATCH THE NOA SUBMITTED. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION WAS
 UPDATED TO $86,820. THE PERMIT FEE BALANCE IS $2175.54.
  
 ***NOTES: ANY ROOF EQUIPMENT REMOVAL OR RETROFIT ROOF
 DRAINS REQUIRE SEPARATE PERMITS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-04-11 Cont ID  
Sent By jgomez Date 2014-04-11 Time 09:35 Rev Time 0.00
Received By jgomez Date 2014-04-10 Time 18:06 Sent To  
Notes
2014-04-10 18:06:23SENT TO J GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-04-07 Cont ID  
Sent By jgomez Date 2014-04-07 Time 08:54 Rev Time 0.00
Received By jgomez Date 2014-04-07 Time 08:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-03-28 Cont ID  
Sent By jgomez Date 2014-03-28 Time 15:35 Rev Time 0.00
Received By jgomez Date 2014-03-28 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-19 Cont ID  
Sent By jgomez Date 2014-03-19 Time 18:19 Rev Time 0.00
Received By jgomez Date 2014-03-19 Time 18:19 Sent To  
Notes
2014-03-04 18:11:05SENT TO R MCDOUGAL