Plan Review Details - Permit 14030046
Plan Review Stops For Permit 14030046
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-03-28 Cont ID  
Sent By jwitmer Date 2014-03-28 Time 06:48 Rev Time 0.00
Received By jwitmer Date 2014-03-28 Time 05:57 Sent To  
Notes
2014-03-28 06:15:37BUILDING PLAN REVIEW
 MASTER BUILDING PERMIT: 13010504/ 2010 FBC
 EVERNIA PLACE AFFORDABLE SENIOR HOUSING
 POOL PERMIT: 14030046
 ADD: 631 EVERNIA STREET
 CONT: KAUFMAN LYNN
 TEL: (561)361-6700
 CONTACT: MAT HURLEY
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRIDAY MARCH 28/2014
 ACTION: BUILDING PROVISO
  
 1) SHEET SP-1.08 THE EQUIPMENT ROOM SHOWS THE USE OF A
 SHIPS LADDER 2010 FBC-B 424.1.5.4 DOES ALLOW THE USE OF
 A SHIPS LADDER PROVIDED:
 THE DESIGN ENGINEER WHO MUST CONSIDER ANTICIPATED
 WORKLOAD INCLUDING EQUIPMENT REMOVAL; AND THE LADDER
 SLOPE, TREAD HEIGHT AND WIDTH; AND CONSTRUCTION
 MATERIAL OF THE LADDER. PLEASE PROVIDE THE REQUIRED
 INFORMATION FOR THE PROPOSED SHIS LADDER. PLEASE
 PROVIDE A SHOP DRAWING FOR SHIPS LADDER REVIEWED BY THE
 DESIGNER OF RECORD BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT FOR REVIEW. JW
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-13 Cont ID  
Sent By jwitmer Date 2014-03-13 Time 12:15 Rev Time 0.00
Received By jwitmer Date 2014-03-13 Time 06:55 Sent To  
Notes
2014-03-13 12:15:37BUILDING PLAN REVIEW
 MASTER BUILDING PERMIT: 13010504/ 2010 FBC
 EVERNIA PLACE AFFORDABLE SENIOR HOUSING
 POOL PERMIT: 14030046
 ADD: 631 EVERNIA STREET
 CONT: KAUFMAN LYNN
 TEL: (561)361-6700
 CONTACT: MAT HURLEY
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY MARCH 13/2014
 ACTION: DENIED
  
 1) THE SUBMITTED POOL, POOL DECK, EQUIPMENT SHELTER
 HAVE NOT BEEN REVIEWED BY THE DESIGNER OF RECORD FOR
 THE PROJECT. THE PROPOSED POOL,
 POOL DECK & POOL EQUIPMENT & SHELTER SHALL BE SUBMITTED
 TO THE DESIGNER OF RECORD (SONG & ASSOCIATES) FOR
 REVIEWAND APPROVAL WITH A SHOP DRAWING STAMP, APPROVED
 ,OR APPRVOVED AS NOTED. THIS DESIGN IS THE WORK OF P.
 E. OLEFIA TABOADA. FL ADMIN. 61G1-23.015 .
  
 2) SHEET SP-1.08 THE EQUIPMENT ROOM SHOWS THE USE OF A
 SHIPS LADDER 2010 FBC-B 424.1.5.4 DOES ALLOW THE USE OF
 A SHIPS LADDER PROVIDED:
 THE DESIGN ENGINEER WHO MUST CONSIDER ANTICIPATED
 WORKLOAD INCLUDING EQUIPMENT REMOVAL; AND THE LADDER
 SLOPE, TREAD HEIGHT AND WIDTH; AND CONSTRUCTION
 MATERIAL OF THE LADDER. PLEASE PROVIDE THE REQUIRED
 INFORMATION FOR THE PROPOSED SHIS LADDER.
  
 3) SHEET SP-108 THE EQUIPMENT ROOM FAILS TO INDICATE
 COMPLIANCE WITH: 424.1.5.9 HOSE BIBBS. A HOSE BIBB WITH
 VACUUM BREAKER SHALL BE LOCATED IN THE EQUIPMENT ROOM
 OR AREA.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-04-02 Cont ID  
Sent By skennedy Date 2014-04-02 Time 12:31 Rev Time 0.00
Received By skennedy Date 2014-03-31 Time 15:42 Sent To  
Notes
2014-04-02 12:31:41SEE DHAYES REVIEWS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-03-31 Cont ID  
Sent By dhayes Date 2014-03-31 Time 15:42 Rev Time 0.00
Received By dhayes Date 2014-03-31 Time 15:41 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-03-24 Cont ID  
Sent By dhayes Date 2014-03-24 Time 11:39 Rev Time 0.00
Received By dhayes Date 2014-03-24 Time 11:38 Sent To  
Notes
2014-03-24 12:54:17ADDITIONAL INFORMATION IS REQUIRED FOR THE ELECTRICAL
 SYSTEM. PLEASE PROVIDE A RISER DIAGRAM AND PANEL
 SCHEDULE INDICATING OVERCURRENT PROTECTION, PIPE AND
 WIRE SIZES FOR THE POOL AND ALL ASSOCIATED EQUIPMENT. A
 LOAD CALCULATION INDICATING THE TOTAL CONNECTED LOAD AT
 THE POOL PANEL AND A CALCULATION AT THE SERVICE
 EQUIPMENT INDICATING THE CAPACITY TO FEED THIS NEW LOAD
 FROM THE EXISTING SWITCHGEAR. PLEASE SHOW THE LOCATION
 AND ELEVATION OF NEW AND/OR EXISTING POWER AND LIGHTING
 WITH RESPECT TO THE INSIDE EDGE OF THE POOL AND HOW IT
 IS BEING FED.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2014-03-13 Cont ID  
Sent By jwitmer Date 2014-03-13 Time 12:18 Rev Time 0.00
Received By jwitmer Date 2014-03-13 Time 12:18 Sent To  
Notes
2014-03-13 12:19:58SHEET SP-1.08 SWIMMING POOL SCHEDULE OF EQUIPMENT- NO
 GAS HEATER IS INDICATED NOR IS THERE ANY GAS ISOMETRIC
 PLAN OR OTHER INFORMATION INDICATING GAS TO BE SUPPLIED
 TO ANY POOL EQUIPMENT. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-02 Cont ID  
Sent By skennedy Date 2014-04-02 Time 12:31 Rev Time 0.00
Received By skennedy Date 2014-03-27 Time 05:56 Sent To  
Notes
2014-04-02 12:32:13ISSUED YESTERDAY?

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-26 Cont ID  
Sent By skennedy Date 2014-03-26 Time 11:06 Rev Time 0.00
Received By skennedy Date 2014-03-03 Time 18:52 Sent To  
Notes
2014-03-26 10:38:09TO STEVEN.
2014-03-03 18:52:55C29
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-03-13 Cont ID  
Sent By jwitmer Date 2014-03-13 Time 12:15 Rev Time 0.00
Received By jwitmer Date 2014-03-13 Time 06:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-03-26 Cont ID  
Sent By aaponte Date 2014-03-26 Time 10:37 Rev Time 0.00
Received By aaponte Date 2014-03-26 Time 10:37 Sent To  
Notes
2014-03-10 16:24:573/10/14