Plan Review Details - Permit 14021097
Plan Review Stops For Permit 14021097
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2015-01-21 Cont ID  
Sent By rmcdouga Date 2015-01-21 Time 13:48 Rev Time 0.00
Received By rmcdouga Date 2015-01-21 Time 11:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2015-01-05 Cont ID  
Sent By rmcdouga Date 2015-01-05 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2015-01-05 Time 07:55 Sent To  
Notes
2015-01-05 08:39:492010 FBC
 4TH REVIEW
 DENIED BY BUILDING
  
 1) THE INFORMATION LISTED ON THE ENERGY CALCULATION IS
 NOT CONSISTANT WITH THE EQUIPMENT SIZING CALCULATIONS
 OR THE EQUIPMENT SCHEDULE ON THE MECHANICAL PLANS. THE
 SEER AND BTUS FOR THE HEATING AND COOLING ARE
 DIFFERENT. PLEASE CORRECT. THE INFORMATION ON THE PLANS
 AND ENERGY FORMS ARE REQUIRED TO BE CONSISTENT. FBC
 R107.2.1
 THE RESULTS ON THE RESUMBMITTED EQUIPMENT SIZING
 CALCULATIONS WERE IMPROPERLY CHANGED.
 THE EQUIPMENT SIZING CALCULATIONS CAN NOT BE CHANGED BY
 SOMEONE CROSSING OUT THE RESULTS ON THE SUMMARY SHEET
 AND WRITING IN DIFFERENT RESULTS. THE CARRIER MODEL
 24ACC624A HAS A MAXIMUM SEER OF 16 AND THE ENERGY
 CALCULATION FORM LISTS R-17. THE ENERGY CALCULATION
 FORM LISTS THE WALL INSULATION AS R-5 AND SHEET A102 OF
 THE PLANS HAS R-4.2THE EQUIPMENT SIZING CALCULATIONS
 AND THE ENERGY CALCULATIONS WILL NEED TO BE RE-DONE
 USING THE SAME INPUT INFORMATION SO THAT THE REPORTS
 ARE CONSISTENT WITH EACH OTHER.
  
 2) THE PREPARER AND THE OWNER/AGENT ARE REQUIRED TO
 SIGN THE ENERGY CALC. FORM. FBC ENERGY CONSERVATION
 SECTION 103.2.3.2 THE NEW FORMS ARE REQUIRED TO BE
 SIGNED.
  
 3) MAKE SURE THAT THE CORRECT INFORMATION APPEARS IN
 THE EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN. FBC
 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-12-11 Cont ID  
Sent By rmcdouga Date 2014-12-11 Time 17:28 Rev Time 0.00
Received By rmcdouga Date 2014-12-11 Time 15:28 Sent To  
Notes
2014-12-11 18:20:382010 FBC
 3RD REVIEW
 DENIED BY BUILDING
  
 1) THE INFORMATION LISTED ON THE ENERGY CALCULATION IS
 NOT CONSISTANT WITH THE EQUIPMENT SIZING CALCULATIONS
 OR THE EQUIPMENT SCHEDULE ON THE MECHANICAL PLANS. THE
 SEER AND BTUS FOR THE HEATING AND COOLING ARE
 DIFFERENT. PLEASE CORRECT. THE INFORMATION ON THE PLANS
 AND ENERGY FORMS ARE REQUIRED TO BE CONSISTENT. FBC
 R107.2.1
  
 2) THE PREPARER AND THE OWNER/AGENT ARE REQUIRED TO
 SIGN THE ENERGY CALC. FORM. FBC ENERGY CONSERVATION
 SECTION 103.2.3.2
  
 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE NEW
 PGT IMPACT RATED SINGLE HUNG WINDOWS THAT ARE SPECIFIED
 ON PLAN SHEET A102 AS REQUIRED BY DCA RULE 9N-3.
 MIAMI-DADE NOAS AND FLORIDA PRODUCT APPROVALS ARE
 ACCEPTABLE.
  
 4) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 107.3.4.1
  
 5) IN ORDER TO SPEED PLAN REVIEW, PLEASE SUBMIT A
 RESPONSE LETTER THAT INDICATES HOW EACH OF THE REVIEW
 COMMENTS WAS ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-10-30 Cont ID  
Sent By rmcdouga Date 2014-10-30 Time 11:41 Rev Time 0.00
Received By rmcdouga Date 2014-10-30 Time 09:20 Sent To  
Notes
2014-10-30 11:41:102010 FBC
 2ND REVIEW
 DENIED BY BUILDING
  
 1) COMPLIED
  
 2) COMPLIED
  
 3) COMPLIED
  
 4) COMPLIED
  
 5) COMPLIED
  
 6)COMPLIED
  
 7) THE CITY AND PERMIT OFFICE ARE SPECIFIED AS RIVIERA
 BEACH ON THE ENERGY CALCULATION. THIS PROJECT IS
 LOCATED IN THE CITY OF WEST PALM BEACH (JURISDICTION
 NUMBER 604700). PLEASE CORRECT. FBC ENERGY CONSERVATION
 SECTION 103.2.1.1.1
 (THE ENERGY CALCULATIONS WILL NEED TO BE REDONE WITH
 THE CORRECT INFORMATION.)
  
 8) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY CALC.
 FORM. FBC ENERGY CONSERVATION SECTION 103.2.3.2
  
 9) THE ATTIC DUCT INSULATION IS LISTED AS R-13 ON THE
 ENERGY CALC. FORM AND THE MECHANICAL PLANS SPECIFY R-6.
 PLEASE CORRECT. FBC ENERGY CONSERVATION SECTION
 103.2.3.2 ( THE INFORMATION ON THE PLANS AND ENERGY
 FORMS ARE REQUIRED TO BE CONSISTENT. FBC R107.2.1
  
 10) THE ENERGY CALC. FORM SPECIFIES THAT THE EXTERIOR
 CONCRETE BLOCK WALLS HAVE R-13 INSULATION. PROVIDE A
 WALL SECTION THAT SHOWS THE TYPE OF INSULATION THAT
 WILL BE INSTALLED. CITY AMENDMENTS 107.2.1 & FBC ENERGY
 CONSERVATION SECTION 103.2.1.1.1 ( THE PLANS SPECIFY
 R-4.2 INSULATION ON THE EXTERIOR CONCRETE WALLS. )
  
 11) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE PGT
 & LAWSON SINGLE HUNG WINDOWS THAT ARE SPECIFIED ON PLAN
 SHEET A102 AND FOR THE STRUCTURAL MULLIONS AS REQUIRED
 BY DCA RULE 9N-3. MIAMI-DADE NOAS AND FLORIDA PRODUCT
 APPROVALS ARE ACCEPTABLE.
  
 12) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 107.3.4.1
  
 13) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR OPENING
 PROTECTION FROM LARGE MISSILE IMPACT. IF STORM PANELS
 ARE USED SUBMIT TWO COPIES OF THEIR PRODUCT APPROVALS,
 AN INSTALLATION SCHEDULE AND A KEY PLAN. DCA RULE 9N-3
 & CITY AMENDMENTS 107.2.1.
  
 14) IN ORDER TO SPEED PLAN REVIEW, PLEASE SUBMIT A
 RESPONSE LETTER THAT INDICATES HOW EACH OF THE REVIEW
 COMMENTS WAS ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-07-16 Cont ID  
Sent By rmcdouga Date 2014-07-16 Time 17:51 Rev Time 0.00
Received By rmcdouga Date 2014-07-16 Time 08:19 Sent To  
Notes
2014-07-16 15:47:332010 FBC
  
 DENIED BY BUILDING
  
 1) SPECIFY THE WIND DESIGN DATA ON THE PLANS. THIS
 STRUCTURE IS LOCATED IN 17O MPH VULT WIND SPEED AND
 EXPOSURE CATEGORY C. THE FBCR 301.2.1
  
 2) PROVIDE A STRUCTURAL DETAIL FOR THE CONCRETE BLOCK
 WALL IN-FILL AT THE KITCHEN WINDOW THAT SHOWS THE
 REINFORCING BAR SIZE AND LOCATION. CITY AMENDMENTS
 107.2.1.3 & FBCR 301.1
  
 3) THE TYPE OF CONSTRUCTION FOR THIS STRUCTURE IS V-B
 PER FBC TABLE 601. PLEASE CORRECT BUILDING TYPE ON
 SHEET A100.
  
 4) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR SMOKE ALARMS
 AND FBCR 315 FOR CARBON MONOXIDE ALARMS.
  
 5) SHOW THAT THE BATHROOM WINDOWS COMPLY WITH FBCR
 308.4 FOR SAFETY GLAZING IN HAZARDOUS LOCATIONS.
  
 6) THE WINDOW BUCK DETAIL ON SHEET A102 SPECIFIES 3/13"
 X 1-3/4" TAPCONS WITH A 1-1/4" MINIMUM WOOD EMBED. THE
 EXTERIOR WALLS ARE CONCRETE BLOCK NOT WOOD. THE LENGTH
 OF THE TAPCONS WILL NOT PROVIDE AN 1-1/4" EMBED DEPTH
 WHEN FASTENED THROUGH A 3/4" BUCK AND A 1/4" SHIM
 SPACE. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 AND FBCR
 612.10.2.1
  
 7) THE CITY AND PERMIT OFFICE ARE SPECIFIED AS RIVIERA
 BEACH ON THE ENERGY CALCULATION. THIS PROJECT IS
 LOCATED IN THE CITY OF WEST PALM BEACH (JURISDICTION
 NUMBER 604700). PLEASE CORRECT. FBC ENERGY CONSERVATION
 SECTION 103.2.1.1.1
  
 8) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY CALC.
 FORM. FBC ENERGY CONSERVATION SECTION 103.2.3.2
  
 9) THE ATTIC DUCT INSULATION IS LISTED AS R-13 ON THE
 ENERGY CALC. FORM AND THE MECHANICAL PLANS SPECIFY R-6.
 PLEASE CORRECT. FBC ENERGY CONSERVATION SECTION
 103.2.3.2
  
 10) THE ENERGY CALC. FORM SPECIFIES THAT THE EXTERIOR
 CONCRETE BLOCK WALLS HAVE R-13 INSULATION. PROVIDE A
 WALL SECTION THAT SHOWS THE TYPE OF INSULATION THAT
 WILL BE INSTALLED. CITY AMENDMENTS 107.2.1 & FBC ENERGY
 CONSERVATION SECTION 103.2.1.1.1
  
 11) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE PGT
 & LAWSON SINGLE HUNG WINDOWS THAT ARE SPECIFIED ON PLAN
 SHEET A102 AND FOR THE STRUCTURAL MULLIONS AS REQUIRED
 BY DCA RULE 9N-3. MIAMI-DADE NOAS AND FLORIDA PRODUCT
 APPROVALS ARE ACCEPTABLE.
  
 12) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 107.3.4.1
  
 13) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR OPENING
 PROTECTION FROM LARGE MISSILE IMPACT. IF STORM PANELS
 ARE USED SUBMIT TWO COPIES OF THEIR PRODUCT APPROVALS,
 AN INSTALLATION SCHEDULE AND A KEY PLAN. DCA RULE 9N-3
 & CITY AMENDMENTS 107.2.1.
  
 14) IN ORDER TO SPEED PLAN REVIEW, PLEASE SUBMIT A
 RESPONSE LETTER THAT INDICATES HOW EACH OF THE REVIEW
 COMMENTS WAS ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
2014-06-26 11:44:35SENT TO R07. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-10 Cont ID  
Sent By skennedy Date 2014-03-10 Time 08:55 Rev Time 0.00
Received By skennedy Date 2014-03-10 Time 08:55 Sent To  
Notes
2014-03-10 08:58:02IT APPEARS THIS IS A DEMOLITION REQUEST IN PREPARATION
 FOR A REMODEL. THE SCOPE IS UNCLEAR AS INFORMATION
 BEYOND THIS SCOPE IS INCLUDED. ADDITIONALLY, THE TITLE
 BLOCK INDICATES THE JOB ADDRESS IS IN MIAMI BEACH.
 CONTRACTOR TO RESUSSBMIT AND CLARIFY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-11 Cont ID  
Sent By rmcdouga Date 2014-12-11 Time 15:53 Rev Time 0.00
Received By rmcdouga Date 2014-12-11 Time 15:29 Sent To  
Notes
2014-12-11 15:54:09RED-LINED PLANS. APPROVED WITH EXCEPTIONS NOTED ON
 PLANS.
2014-12-04 09:59:38NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-07-17 Cont ID  
Sent By rmcdouga Date 2014-07-17 Time 11:02 Rev Time 0.00
Received By rmcdouga Date 2014-07-17 Time 11:02 Sent To  
Notes
2014-07-17 11:03:38RED-LINED PLANS. APPROVED WITH EXCEPTIONS NOTED ON
 PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2015-01-21 Cont ID  
Sent By rmcdouga Date 2015-01-21 Time 13:48 Rev Time 0.00
Received By rmcdouga Date 2015-01-16 Time 17:34 Sent To  
Notes
2015-01-16 17:35:21RE-SUBMITTAL SENT TO ZONING SHELF FOR LINDA LOUIE
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-01-05 Cont ID  
Sent By rmcdouga Date 2015-01-05 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2014-12-22 Time 06:20 Sent To  
Notes
2014-12-23 06:18:28SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-12-11 Cont ID  
Sent By rmcdouga Date 2014-12-11 Time 18:21 Rev Time 0.00
Received By rmcdouga Date 2014-12-03 Time 09:57 Sent To  
Notes
2014-12-04 09:57:52RE-SUBMITTAL SENT TO ZONING SHELF FOR LINDA LOUIE
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-10-30 Cont ID  
Sent By rmcdouga Date 2014-10-30 Time 11:41 Rev Time 0.00
Received By rmcdouga Date 2014-10-21 Time 11:14 Sent To  
Notes
2014-10-22 11:15:57RE-SUBMITTAL SENT TO ZONING SHELF FOR LINDA'S REVIEW.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-07-17 Cont ID  
Sent By rmcdouga Date 2014-07-17 Time 11:03 Rev Time 0.00
Received By rmcdouga Date 2014-06-25 Time 11:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-10 Cont ID  
Sent By skennedy Date 2014-03-10 Time 08:55 Rev Time 0.00
Received By skennedy Date 2014-02-28 Time 08:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-12-11 Cont ID  
Sent By rmcdouga Date 2014-12-11 Time 16:45 Rev Time 0.00
Received By rmcdouga Date 2014-12-11 Time 16:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-10-30 Cont ID  
Sent By rmcdouga Date 2014-10-30 Time 09:10 Rev Time 0.00
Received By rmcdouga Date 2014-10-30 Time 09:10 Sent To  
Notes
2014-10-30 09:10:062010 FBC
  
 DENIED BY MECHANICAL (2ND REVIEW) ( ITEMS 2 THROUGH 5
 FROM THE FIRST REVIEW WERE NOT ADDRESSED.)
  
 1) COMPLIED
  
 2) SPECIFY THE SIZE OF THE RETURN AIR TRANSFER DUCTS TO
 SHOW COMPLIANCE WITH FBCR M 1602.4 FOR BALANCED RETURN
 AIR.
  
 3) SPECIFY THE SIZE OF THE SUPPLY DUCT TO THE NEW
 BATHROOM. CITY AMENDMENTS 107.3.5.3
  
 4) THE BATHROOM EXHAUST DUCTS ARE REQUIRED TO DISCHARGE
 DIRECTLY TO THE OUTDOORS. FBCR M1507.2
  
 5) INDICATE HOW THE RETURN AIR WILL GET TO THE AIR
 HANDLER THAT IS LOCATED IN THE CLOSET. IF IT IS THROUGH
 THE BI-FOLD DOORS, SPECIFY THAT THEY WILL BE LOUVERED.
 FBCR M1602
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-07-16 Cont ID  
Sent By rmcdouga Date 2014-07-16 Time 13:33 Rev Time 0.00
Received By rmcdouga Date 2014-07-16 Time 08:18 Sent To  
Notes
2014-07-16 13:52:092010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN OF THE MECHANICAL SYSTEM IS
 REQUIRED ON THE PLANS. CITY AMENDMENTS 107.2.1
  
 2) SPECIFY THE SIZE OF THE RETURN AIR TRANSFER DUCTS TO
 SHOW COMPLIANCE WITH FBCR M 1602.4 FOR BALANCED RETURN
 AIR.
  
 3) SPECIFY THE SIZE OF THE SUPPLY DUCT TO THE NEW
 BATHROOM. CITY AMENDMENTS 107.3.5.3
  
 4) THE BATHROOM EXHAUST DUCTS ARE REQUIRED TO DISCHARGE
 DIRECTLY TO THE OUTDOORS. FBCR M1507.2
  
 5) INDICATE HOW THE RETURN AIR WILL GET TO THE AIR
 HANDLER THAT IS LOCATED IN THE CLOSET. IF IT IS THROUGH
 THE BI-FOLD DOORS, SPECIFY THAT THEY WILL BE LOUVERED.
 FBCR M1602
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-12-11 Cont ID  
Sent By rmcdouga Date 2014-12-11 Time 17:15 Rev Time 0.00
Received By rmcdouga Date 2014-12-11 Time 15:29 Sent To  
Notes
2014-12-04 09:59:11NEW SHEETS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-07-16 Cont ID  
Sent By rmcdouga Date 2014-07-16 Time 08:29 Rev Time 0.00
Received By rmcdouga Date 2014-07-16 Time 08:18 Sent To  
Notes
2014-07-16 08:58:12RED-LINED PLANS. APPROVED WITH EXCEPTIONS NOTED ON
 PLANS.

Review Stop Z ZONING
Rev No 5 Status P Date 2015-01-21 Cont ID  
Sent By llouie Date 2015-01-21 Time   Rev Time 0.00
Received By llouie Date 2015-01-20 Time   Sent To B
Notes
2015-01-20 10:15:59** ZONING FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) REPEAT COMMENT (7/2/14; 10/27/14; 12/5/14;
 12/23/14): THE VALUE OF THE CONSTRUCTION ($28,000)
 EXCEEDS 50 PERCENT OF THE STRUCTURE'S VALUE ($31,348 IN
 2013 AND $52,720 IN 2014) ACCORDING TO THE P.B.C.
 PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT TO
 SECTION 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED
 SHOWING MATERIAL TO BRING THE SITE INTO CONFORMITY.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  
 NOTE:
 - SPOKE TO MIGUEL ESPINOZA ON 1/20/15. INFORMED MR.
 ESPINOZA THAT A SEPARATE LANDSCAPE PERMIT IS REQUIRED
 FOR THE LANDSCAPE PLANS WHICH WERE LOCATED IN THE
 MASTER PERMIT. MR. ESPINOZA INFORMED LINDA LOUIE THAT
 HE WILL DROP BY CITY HALL TO FILE THE SEPARATE PAPER
 WORK FOR THE LANDSCAPE PERMIT.
  
 - SPOKE TO JOSE JARAMILLO, PROJECT ARCHITECT ON 12/23
 REGARDING LANDSCAPING REQUIREMENT; INFORMED MR.
 JARAMILLO THAT ZONING CANNOT PASS PERMIT UNTIL A
 LANDSCAPE PERMIT IS RECEIVED FOR THE PROJECT. MR.
 JARMILLO INFORMED LINDA LOUIE THAT HE IS WORKING ON THE
 LANDSCAPE PLANS AND WILL SUBMIT FOR THE LANDSCAPE
 PERMIT WHEN COMPLETED.

Review Stop Z ZONING
Rev No 4 Status F Date 2014-12-23 Cont ID  
Sent By llouie Date 2014-12-23 Time 16:41 Rev Time 0.00
Received By llouie Date 2014-12-23 Time 16:41 Sent To B
Notes
2014-12-23 16:45:55** ZONING FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) REPEAT COMMENT (7/2/14; 10/27/14; 12/5/14): THE
 VALUE OF THE CONSTRUCTION ($28,000) EXCEEDS 50 PERCENT
 OF THE STRUCTURE'S VALUE ($31,348 IN 2013 AND $52,720
 IN 2014) ACCORDING TO THE P.B.C. PROPERTY APPRAISER'S
 OFFICE; THEREFORE, PURSUANT TO SECTION 94-441(C)(2) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE
 LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL
 APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE
 ZLDR. IF THE SITE CONFORMS TO ARTICLE XIV, THEN TWO (2)
 COPIES OF A LANDSCAPE PLAN DEMONSTRATING COMPLIANCE
 SHALL BE INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE
 SITE DOES NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE
 ZONING APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  
 NOTE:
 - SPOKE TO JOSE JARAMILLO, PROJECT ARCHITECT ON 12/23
 REGARDING LANDSCAPING REQUIREMENT; INFORMED MR.
 JARAMILLO THAT ZONING CANNOT PASS PERMIT UNTIL A
 LANDSCAPE PERMIT IS RECEIVED FOR THE PROJECT. MR.
 JARMILLO INFORMED LINDA LOUIE THAT HE IS WORKING ON THE
 LANDSCAPE PLANS AND WILL SUBMIT FOR THE LANDSCAPE
 PERMIT WHEN COMPLETED.

Review Stop Z ZONING
Rev No 3 Status F Date 2014-12-05 Cont ID  
Sent By llouie Date 2014-12-05 Time 09:02 Rev Time 0.00
Received By llouie Date 2014-12-05 Time 09:02 Sent To B
Notes
2014-12-05 09:03:22** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) REPEAT COMMENT (7/2/14; 10/27/14): A NEW A/C UNIT
 HAS BEEN DETECTED IN THE FLOOR PLANS. PROVIDE AN
 UPDATED SURVEY OF THE PROPERTY AND ILLUSTRATE THE
 LOCATION OF THE A/C UNIT IN RELATIONSHIP TO THE
 PROPERTY LINE(S).
  
 2.) REPEAT COMMENT (7/2/14; 10/27/14): THE A/C UNIT
 SHALL NOT PROJECT MORE THAN 4 FT. INTO ANY SETBACK. THE
 SETBACK OF THE PROPOSED A/C UNIT CANNOT BE DETERMINED
 WITHOUT A SURVEY OF THE PROPERTY. (ZLDR S.94-305(B)(4))
  
 3.) REPEAT COMMENT (7/2/14; 10/27/14): THE VALUE OF THE
 CONSTRUCTION ($28,000) EXCEEDS 50 PERCENT OF THE
 STRUCTURE'S VALUE ($31,348 IN 2013 AND $52,720 IN 2014)
 ACCORDING TO THE P.B.C. PROPERTY APPRAISER'S OFFICE;
 THEREFORE, PURSUANT TO SECTION 94-441(C)(2) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE
 LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL
 APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE
 ZLDR. IF THE SITE CONFORMS TO ARTICLE XIV, THEN TWO (2)
 COPIES OF A LANDSCAPE PLAN DEMONSTRATING COMPLIANCE
 SHALL BE INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE
 SITE DOES NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE
 ZONING APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
 4.) REPEAT COMMENT (10/27/14): THE LATEST REVISION,
 SHOWING A DIFFERENT LOCATION FOR THE PROPOSED A/C UNIT
 IS NOT CONSISTENT WITHIN THE FLOOR PLANS; THERE SEEMS
 TO BE MORE THAN ONE (1) POSSIBLE LOCATION FOR THE A/C
 UNIT. PLEASE ADDRESS FOR CONSISTENCY.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2014-10-27 Cont ID  
Sent By llouie Date 2014-10-27 Time 16:12 Rev Time 0.00
Received By llouie Date 2014-10-27 Time 16:12 Sent To B
Notes
2014-10-27 16:13:30** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) REPEAT COMMENT (7/2/14): A NEW A/C UNIT HAS BEEN
 DETECTED IN THE FLOOR PLANS. PROVIDE AN UPDATED SURVEY
 OF THE PROPERTY AND ILLUSTRATE THE LOCATION OF THE A/C
 UNIT IN RELATIONSHIP TO THE PROPERTY LINE(S).
  
 2.) REPEAT COMMENT (7/2/14): THE A/C UNIT SHALL NOT
 PROJECT MORE THAN 4 FT. INTO ANY SETBACK. THE SETBACK
 OF THE PROPOSED A/C UNIT CANNOT BE DETERMINED WITHOUT A
 SURVEY OF THE PROPERTY. (ZLDR S.94-305(B)(4))
  
 3.) REPEAT COMMENT (7/2/14): THE VALUE OF THE
 CONSTRUCTION ($28,000) EXCEEDS 50 PERCENT OF THE
 STRUCTURE'S VALUE ($31,348 IN 2013 AND $52,720 IN 2014)
 ACCORDING TO THE P.B.C. PROPERTY APPRAISER'S OFFICE;
 THEREFORE, PURSUANT TO SECTION 94-441(C)(2) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE
 LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL
 APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE
 ZLDR. IF THE SITE CONFORMS TO ARTICLE XIV, THEN TWO (2)
 COPIES OF A LANDSCAPE PLAN DEMONSTRATING COMPLIANCE
 SHALL BE INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE
 SITE DOES NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE
 ZONING APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
 4.) THE LATEST REVISION, SHOWING A DIFFERENT LOCATION
 FOR THE PROPOSED A/C UNIT IS NOT CONSISTENT WITHIN THE
 FLOOR PLANS; THERE SEEMS TO BE MORE THAN ONE (1)
 POSSIBLE LOCATION FOR THE A/C UNIT. PLEASE ADDRESS FOR
 CONSISTENCY.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-07-02 Cont ID  
Sent By llouie Date 2014-07-02 Time 10:54 Rev Time 0.00
Received By llouie Date 2014-07-02 Time 10:54 Sent To  
Notes
2014-07-02 10:56:09** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) A NEW A/C UNIT HAS BEEN DETECTED IN THE PLANS.
 PROVIDE AN UPDATED SURVEY OF THE PROPERTY AND
 ILLUSTRATE THE LOCATION OF THE A/C UNIT IN RELATIONSHIP
 TO THE PROPERTY LINE(S).
  
 2.) THE A/C UNIT SHALL NOT PROJECT MORE THAN 4 FT. INTO
 ANY SETBACK. (ZLDR S.94-305(B)(4))
  
 3.) THE VALUE OF THE CONSTRUCTION ($28,000) EXCEEDS 50
 PERCENT OF THE STRUCTURE'S VALUE ($31,348) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT
 SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE SITE
 INTO CONFORMITY.
  
 PLEASE CALL LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
  
  
  
2014-07-01 16:40:127-1-14