Plan Review Details - Permit 14021021
Plan Review Stops For Permit 14021021
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-28 Cont ID  
Sent By jwitmer Date 2014-02-28 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2014-02-28 Time 09:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-02-28 Cont ID  
Sent By jwitmer Date 2014-02-28 Time 09:34 Rev Time 0.00
Received By jwitmer Date 2014-02-28 Time 09:34 Sent To  
Notes
2014-02-28 09:35:51PROVISO:
 2010 FBC-B 1013.5 MECHANICAL EQUIPMENT.
 2010 FBC-M 304.11 MECHANICAL EQUIPMENT
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS,
 ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT REQUIRE
 SERVICE
 ARE LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR
 OPEN SIDE
 OF A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS
 LOCATED MORE
 THAN 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE
 BELOW.
 THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE
 PASSAGE OF A
 SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL
 EXTEND NOT
 LESS THAN 30 INCHES (762 MM) BEYOND EACH END OF SUCH
 APPLIANCE,
 EQUIPMENT, FAN OR COMPONENT.