Plan Review Details - Permit 14020991
Plan Review Stops For Permit 14020991
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-03-14 Cont ID  
Sent By rmcdouga Date 2014-03-14 Time 13:34 Rev Time 0.00
Received By rmcdouga Date 2014-03-14 Time 13:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-27 Cont ID  
Sent By rmcdouga Date 2014-02-27 Time 16:15 Rev Time 0.00
Received By rmcdouga Date 2014-02-26 Time 14:37 Sent To  
Notes
2014-02-27 16:48:032010 FBC
  
 DENIED BY BUILDING
  
 1) THE APPLICATION SPECIFIES THAT 1100 SQUARE FEET OF
 THE THE BUILDING IS BEING RE-ROOFED. THE BUILDING
 SKETCH THAT I DOWNLOADED FROM THE PROPERTY APPRAISER'S
 WEBSITE INDICATES THE MAIN HOUSE IS 1531 SQFT WHICH
 INCLUDES A SCREENED PORCH, AN ENCLOSED PORCH AND A
 CARPORT. THERE IS ALSO A DETACHED GARAGE OF 216 SQFT.
 PLEASE PROVIDE A SKETCH WITH DIMENSIONS SHOWING THE
 WHICH AREAS THAT WILL BE RE-ROOFED TO MAKE UP 1100
 SQFT. CITY AMENDMENTS 107.2.1 AND 107.2.1.3
  
 2) THE PERMIT APPLICATION SPECIFES THAT ROOF SYSTEM NO.
 W-33 WILL BE USED. ON THE PRODUCT APPROVAL THAT WAS
 SUBMITTED, THE W-33 SYSTEM IS CROSSED OUT AND THE W-32
 SYSTEM IS CHECKED. THE W-32 SUSTEM HAS A MAXIMUM DESIGN
 PRESSURE OF -75 PSF WHICH IS TOO LOW FOR THE CORNER
 AREAS FOR THIS PROJECT. PLEASE CLARIFY. CITY AMENDMENTS
 107.2.1.2
  
 3) PLEASE NOTE THAT THE BASE SHEET FASTENERS REQUIRED
 FOR BOTH SYSTEM NO. W-32 AND W-33 ARE DRILL-TEC SCREWS
 WITH METAL PLATES AS SPECIFIED IN NOTE 2 ON PAGE 2 OF
 60 FROM THE PRODUCT APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-14 Cont ID  
Sent By rmcdouga Date 2014-03-14 Time 13:34 Rev Time 0.00
Received By rmcdouga Date 2014-03-13 Time 16:13 Sent To  
Notes
2014-03-13 16:13:18TO RM DESK
  