Plan Review Stops For Permit 14020988 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2014-02-27 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2014-02-27 |
Time |
07:56 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2014-02-27 |
Time |
07:55 |
Sent To |
|
|
Notes |
2014-02-27 07:55:56 | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE | | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | BUILDING STRUCTURES. | | | | TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | LOCATIONS. | | | | GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES | | SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET | | AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR | | ENCLOSURE. | | |
|
|