Plan Review Stops For Permit 14020950 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
8 |
Status |
P |
Date |
2014-08-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-04 |
Time |
16:23 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-04 |
Time |
16:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
F |
Date |
2014-07-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-07-31 |
Time |
18:07 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-07-31 |
Time |
17:55 |
Sent To |
|
|
Notes |
2014-07-31 18:26:45 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) ONLY ONE TRUSS PLACEMENT PLAN FOR THE MODEL 'F' | | GABLE WAS SUBMITTED. A MINIMUM OF TWO SETS IS REQUIRED. | | CITY AMENDMENTS 107.1 | | | | 2) NO TRUSS PLACEMENT PLANS FOR THE MODEL 'F' HIP ( | | ALTERNATE ROOF FRAMING PLAN) OR TRUSS DRAWINGS WERE | | SUBMITTED. SUBMIT TWO SETS OF SIGNED AND SEALED TRUSS | | PLACEMENT PLANS AND TRUSS DRAWINGS AS REQUIRED BY CITY | | AMENDMENTS 107.1 AND DCA RULE 9N-3. | | | | 3) THE TRUSS PLACEMENT PLANS AND DRAWINGS FOR THE MODEL | | 'F' HIP ( ALTERNATE ROOF FRAMING PLAN) FROM THE | | DELEGATED ENGINEER ARE REQUIRED TO BE REVIEWED AND | | APPROVED BY THE DESIGNER OF RECORD. CITY AMENDMENTS | | 107.3.4.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
F |
Date |
2014-06-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-06-19 |
Time |
10:19 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-06-19 |
Time |
10:19 |
Sent To |
|
|
Notes |
2014-06-19 10:25:11 | THE NEW TRUSS DRAWINGS NEED TO BE REVIEWED AND APPROVED | | BY THE ARCHITECT. THE ARCHITECT'S SHOP DRAWING REVIEW | | STAMP IS NOT ON THE DRAWINGS. CITY AMENTMENTS 107.3.4.1 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2014-05-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-05-22 |
Time |
09:33 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-05-22 |
Time |
09:33 |
Sent To |
|
|
Notes |
2014-05-22 10:36:16 | 2010 FBC | | | | TRUSS DRAWINGS FOR MODEL F - HIP AND GABLE ROOF OPTIONS | | ARE DENIED | | | | 1) THE TRUSS ENGINEER IS REQUIRED TO SIGN BY HAND THE | | LICENSEE'S HANDWRITTEN SIGNATURE ( FACSIMILES ARE NOT | | ACCEPTABLE ) ON ALL DRAWINGS, PLANS, REPORTS, OR | | DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND BEING | | FILED FOR PUBLIC RECORD. SEE FAC 61G15-23.002 THE | | SIGNATURE ON THE TRUSS COVER OR INDEX SHEET IS A | | FACSIMILE. | | | | 2) TWO SETS OF TRUSS DRAWINGS AND TRUSS LAYOUTS ARE | | REQUIRED TO BE SUBMITTED FOR PLANS THAT ARE BEING | | MASTERED PER CITY AMENDMENTS 107.1 ONE SET WILL BE | | FILED FOR PUBLIC RECORD AND THE OTHER SET WILL BE | | RETURNED TO THE CONTRACTOR FOR USE IN THE FIELD. | | | | 3) THE ITEMS THAT WERE NOTED BY THE ARCHITECT ON THE | | TRUSS DRAWINGS AND LAYOUTS WILL NEED TO BE CORRECTED | | BEFORE THEY WILL BE APPROVED BY THE BUILDING | | DEPARTMENT. CITY AMENDMENTS 107.2.1 AND FBCR 802.1.6 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2014-05-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-05-22 |
Time |
07:11 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-05-22 |
Time |
07:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2014-04-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-04-22 |
Time |
08:32 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-04-22 |
Time |
07:11 |
Sent To |
Z |
|
Notes |
2014-04-22 08:15:02 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE TRUSS PLACEMENT PLAN AND TRUSS DRAWING COVER | | SHEET THAT WERE SUBMITTED DO NOT HAVE THE ORIGINAL WET | | SIGNATURE OF THE ENGINEER AS REQUIRED BY FAC | | 61G15-23.002 FOR DOCUMENTS THAT ARE SUBMITTED FOR | | PUBLIC RECORD. | | | | 2) THE TRUSS PLACEMENT PLAN IS TOO SMALL. CITY | | AMENDMENT 107.2.1.4 TO THE FBC REQUIRES PLANS SUBMITTED | | FOR RECORD TO BE A MINIMUM 1/8 INCH SCALE. | | | | 3) THE TRUSS PLACEMENT PLAN THAT WAS SUBMITTED IS FOR | | THE ALTERNATE ROOF FRAMING PLAN. THERE ARE TWO | | DIFFERENT ROOF FRAMING PLANS SPECIFIED ON SHEET S-1 OF | | THE PLAN. THE FIRST ONE HAS A GABLE END AT THE BACK OF | | THE STRUCTURE AND THE ALTERNATE ONE HAS A HIP ROOF AT | | THE BACK. PLEASE SUBMIT BOTH TRUSS PACKAGES OR REVISE | | THE PLANS TO REMOVE THE GABLE OPTION. CITY AMENDMENTS | | 107.2.1 | | | | 4) THERE IS A DISCREPANCY BETWEEN THE STRUCTURAL ROOF | | FRAMING PLAN AND THE TRUSS PLACEMENT PLAN AND TRUSS | | DRAWINGS THAT WAS NOTED ON THE SHOP DRAWING REVIEW. THE | | STRUCTURAL ROOF PLANS SHOW THE HIP AND JACK TRUSSES AT | | THE FRONT BEARING ON THE FRONT WALL OF THE STRUCTURE | | AND THE TRUSS PLACEMENT PLAN AND TRUSS DRAWINGS HAVE | | THEM ATTACHED TO A HIP GIRDER TRUSS THAT WILL CARRY | | THIER LOAD AND TRANSFER IT TO THE SIDE WALLS. THE TRUSS | | ANCHORS SPECIFIED FOR THIS TRUSS ARE NOT ADEQUATE FOR | | THIS ADDITIONAL LOADING. THIS WILL NEED TO BE CORRECTED | | BEFORE THE MASTER PERMIT CAN BE APPROVED. CITY | | AMENDMENTS 107.2.1 AND FBC R802.1.6.5 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2014-03-11 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-03-11 |
Time |
18:24 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-03-11 |
Time |
18:24 |
Sent To |
|
|
Notes |
2014-03-11 18:25:30 | STILL NEED TRUSS PACKAGE AND PRODUCT APPROVALS, SEE | | PREVIOUS REVIEW COMMENTS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-02-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-02-25 |
Time |
18:25 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-02-25 |
Time |
18:25 |
Sent To |
|
|
Notes |
2014-02-25 18:31:50 | 2010 FBC / MASTER MODEL "F" | | | | DENIED BY BUILDING | | | | 1) SUBMIT TWO COPIES OF A GENERIC MODEL "F" SITE PLANS | | THAT INCLUDE SURFACE WATER DRAINAGE FOR THE MASTER. | | SITE SPECIFIC SITE PLANS WITH DRAINAGE SHOWN AND | | SURVEYS WILL BE REQUIRED FOR EACH PERMIT APPLIED FOR | | UNDER THE MASTER. FBC R401.3 ( NO SHEET A-0.1 WAS | | SUBMITTED.) | | | | 2) REVISE WIND DESIGN DATA ON SHEET S-2 TO REFERENCE | | THE 2010 FBC AND A WIND SPEED OF 170 MPH VULT/132 MPH | | VASD EXPOSURE C AND CHANGE ALL OTHER REFERENCES FROM | | THE 2007 BUILDING CODE TO THE 2010 FBC. FBC R 301.2.1 | | | | 3) ON SHEET S-2, REVISE NOTE 2, B TO REFERENCE ACI | | 315-08. THE 2008 EDITION IS THE ONE REFERENCED BY THE | | 2010 FBCR OR JUST SPECIFY THE CURRENT EDITION. FBCR | | CHAPTER 43 | | | | 4) SUBMIT TWO SETS OF TRUSS DRAWINGS AND LAYOUTS FOR | | ASCE7-10, 170 MPH AND EXPOSURE C THAT HAVE BEEN SIGNED | | AND SEALED BY THE TRUSS ENGINEER AND REVIEWED AND | | APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE | | MODEL "F" STRUCTURE HIP AND GABLE ROOF OPTIONS. FBC | | R802.1.6.1 THESE ARE REQUIRED TO BE SUBMITTED AND | | REVIEWED FOR THE MASTER. | | | | 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 8" WIDE | | CAST-CRETE LINTELS. THE FLORIDA COVER SHEET IS OKAY. | | NOA NO. 12020913 FOR THE 8" WIDE LINTELS WAS NOT | | SUBMITTED. THE ONE THAT WAS IS FOR THE 4, 6 AND 12" | | WIDE LINTELS. DCA RULE 9N-3 | | | | 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE | | STRUCTURAL CONNECTORS (IE TRUSS ANCHORS) AS REQUIRED BY | | DCA RULE 9N-3. | | | | 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY | | AMENDMENTS 107.3.4.1 | | | | 8) THE PLANS SHOW ONE AND A HALF BATHROOMS AND THE | | BUILDING INPUT SUMMARY REPORT HAS ZERO BATHROOMS. | | PLEASE CALRIFY WHY THERE IS A DIFFERENCE. CITY | | AMENDMENTS 107.2.1 | | | | 9) THE WINDOW SCHEDULE SPECIFIES 24 EH AND 2843 EH | | SINGLE HUNG WINDOWS. WHAT DOES EH MEAN? THE 24 EH | | SINGLE HUNG WINDOW IS SPECIFIED AS THE BEDROOM EGRESS | | WINDOWS. A 24-5 SH WINDOW IS WHICH IS 37" X 56" IS | | REQUIRED TO MEET EGRESS REQUIREMENTS. PLEASE CLARIFY. | | | | PLEASE SUBMIT A RESPONSE LETTER THAT DETAILS HOW EACH | | OF THE REVIEW COMMENTS WAS ADDRESSED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-02-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-02-25 |
Time |
18:26 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-02-25 |
Time |
18:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2014-04-22 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2014-04-22 |
Time |
11:47 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2014-04-22 |
Time |
10:36 |
Sent To |
|
|
Notes |
2014-04-22 11:47:38 | PROVISO | | | | 1. PER HPB CASE NO. 07-06, INFILL CONSTRUCTION IS | | LIMITED FOR HISTORIC PRESERVATION PURPOSES, TO THE | | NORTHWEST HISTORIC DISTRICT ONLY. INDIVIDUAL INFILL | | CONSTRUCTION PROJECTS MUST BE REVIEWED BY THE HISTORIC | | PRESERVATION BOARD FOR CONTEXTUAL COMPATIBILITY. | | | | QUESTIONS/COMMENTS, CONTACT FRIEDERIKE MITTNER, CITY | | HISTORIC PRESERVATION PLANNER, AT [email protected] OR | | (561) 822-1457. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-04-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-04-22 |
Time |
08:32 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-03-10 |
Time |
17:49 |
Sent To |
|
|
Notes |
2014-03-11 17:50:23 | SENT TO R MCDOUGAL |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2014-02-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-02-25 |
Time |
18:26 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-02-25 |
Time |
18:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2014-02-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-02-25 |
Time |
18:25 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-02-25 |
Time |
18:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2014-04-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-04-22 |
Time |
11:47 |
Rev Time |
|
Received By |
jroach |
Date |
2014-04-22 |
Time |
08:33 |
Sent To |
|
|
Notes |
2014-04-22 11:47:16 | PROVISO | | | | 1. MASTER PERMIT FOR STRUCTURE ONLY! EACH PROPERTY | | SHALL BE PERMITTED SEPARATELY AND SHALL PROVIDE | | SITE-SPECIFIC SITE PLANS, LANDSCAPE PLANS, ETC. | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL | | PLANNER, AT [email protected] OR (561) 822-1448. | | |
|
|