Plan Review Stops For Permit 14020863 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2014-02-26 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-02-26 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-02-26 |
Time |
16:34 |
Sent To |
|
|
Notes |
2014-02-26 16:34:52 | SPOKE WITH ARCHITECT - HE WILL COORDINATE WITH OWNER TO | | OBTAIN EC | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-02-25 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-02-25 |
Time |
18:00 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-02-25 |
Time |
18:00 |
Sent To |
|
|
Notes |
2014-02-25 18:03:18 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PLEASE PROVIDE AN ELEVATION CERTIFICATE FOR THIS | | JOB. THE BUILDING PERMIT IN 2001 WAS ISSUED WITH THE | | CONDITION THAT THIS BE PROVIDED. IT DOES NOT APPEAR | | THAT ONE WAS PROVIDED AT THAT TIME. | | | | PLANS APPEAR CODE COMPLIANT. THE "FAIL" WILL BE CHANGED | | TO "PASS" UPON RECEIPT OF THE ELEVATION CERTIFICATE VIA | | EMAIL. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2014-04-21 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-04-21 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-04-21 |
Time |
12:39 |
Sent To |
I |
|
Notes |
2014-04-21 13:27:01 | I VOIDED THE ORIGINAL SHEETS E0.1, E2.1 & E3.1 AND | | REPLACED THEM WITH THE RESPECTIVE REVISED SHEETS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2014-04-09 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-04-09 |
Time |
16:03 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-04-08 |
Time |
18:30 |
Sent To |
|
|
Notes |
2014-04-09 12:43:10 | TODAY I MADE A SECOND ATTEMPT TO REACH DUANE MILLAR. | | LEFT VM AND ALSO TRIED DIALING 0. GOT VOICE MAIL AS | | WELL. RETURNED PLANS TO BIN WHILE WAITING FOR RESPONSE. | 2014-04-08 19:03:25 | ERRORS AND DISCREPANCIES WERE NOTED ON THE RISER | | DIAGRAM AND PANEL SCHEDULES. I CALLED DUANE AND LEFT A | | MESSAGE FOR A CALL BACK. | | | | COMMENTS 1 & 2 PROPERLY ADDRESSED MY PRIOR CONCERNS, | | BUT THERE IS AN ISSUE WITH #3. | | 1. THE RISER DIAGRAM DOES NOT REFLECT ANY NEW WORK AS | | IDENTIFIED BY THE LEGEND, YET THIS EQUIPMENT IS BEING | | RELOCATED. PREVIOUSLY I ASKED FOR CONDUCTOR SIZING AND | | IT WAS NOT PROVIDED. ACCORDING TO THE RISER DIAGRAM | | PANEL "HB" IS FED FROM A 400 AMP DISCONNECT. OUT OF | | PANEL "HB" VIA A 175 AMP OCPD IS FED A 112 KVA | | TRANSFORMER SERVING PANEL "LBA" W/A 400 AMP MAIN | | BREAKER AND A CONNECTED LOAD OF ONLY 70 AMP. | | | | WHAT ARE THE CONDUCTOR SIZES FOR THESE FEEDERS? | | | | 2. THE PANEL SCHEDULE FOR "HB" DOES NOT REFLECT THE | | OVER CURRENT DEVICE FOR THE TRANSFORMER AS INDICATED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-03-05 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-03-05 |
Time |
18:13 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-03-05 |
Time |
17:52 |
Sent To |
|
|
Notes |
2014-03-21 12:03:06 | THE MISSING PAGES WERE PRESENTED FOR REVIEW AND | | FOLLOWING ARE THE ITEMS NEEDING FURTHER ATTENTION: | | 1. AS PER FBC- 1006.2.1(2), EMERGENCY LIGHTING IS | | REQUIRED IN THE BATHROOMS, WORK ROOMS AND ANY OTHER | | ROOM NOT HAVING WINDOWS. | | 2. WILL THE EXISTING ELECTRICAL PANELS & TRANSFORMER BE | | RELOCATED TO THE LOCATION INDICATED ON THE PLANS, OR | | WILL THEY BE RELOCATED FROM THERE TO A A NEW LOCATION. | | PLEASE CLARIFY. | | 3. PROVIDE AN ELECTRICAL RISER DIAGRAM INDICATING | | CONDUCTOR SIZING AND WIRING METHOD. | 2014-03-05 18:15:55 | THE ELECTRICAL REVIEW FAILED DUE TO AN INCOMPLETE SET | | OF ELECTRICAL PLAN SUBMISSION. PROVIDE THE REMAINDER OF | | THE ELECTRICAL SHEETS FOR THE NEXT REVIEW. | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | CONTACT: | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | PH: (561) 805-6718, EMAIL: [email protected] | | | | RETURNED FILE TO BIN FOR FURTHER REVIEWS |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2014-03-04 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-03-04 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-03-04 |
Time |
11:00 |
Sent To |
|
|
Notes |
2014-03-04 12:07:51 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | BEACH FIRE RESCUE. | | | | 1. SEPARATE SHOP DRAWINGS FOR THE FIRE ALARM IS | | REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE | | FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION. | | | | 2. THE CENTRAL DOUBLE DOORS ARE REQUIRED TO SWING IN | | THE PATH OF TRAVEL; REQUIRING THEM TO BE REVERSED AS | | SHOWN. | | | | 3. IF NOT EXISTING, THREE (3) ADDITIONAL EXITS LIGHTS | | ARE REQUIRED TO BE INSTALLED AT LOCATIONS HIGHLIGHTED. | | | | 4. IF NOT EXISTING, EMERGENCY LIGHTING IS REQUIRED AT | | EACH EXIT, EITHER CONBINATION EXIT/EMERGENCY OR | | SEPARATE EMERGENCY. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2014-04-21 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-04-21 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2014-04-21 13:31:34 | CALLED CHANDLER CONSTRUCTION AND SPOKE W/CHELSEY |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
P |
Date |
2014-04-21 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-04-21 |
Time |
13:22 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-04-18 |
Time |
17:22 |
Sent To |
I |
|
Notes |
2014-04-21 13:24:50 | VOIDED ORIGINAL PAGES E0.1. E2.1 & E3.1 AND REPLACED | | WITH RESPECTIVE REVISED SHEETS. | 2014-04-18 17:23:09 | INCOMING SENT TO MIKES DESK. JW |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-04-18 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-04-09 |
Time |
17:21 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-04-04 |
Time |
09:29 |
Sent To |
|
|
Notes |
2014-04-08 09:29:45 | TO MA DESK | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-03-21 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-03-21 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-02-24 |
Time |
14:01 |
Sent To |
|
|
Notes |
2014-02-24 14:02:21 | SENT TO B13 SHELF FOR REVIEW. JG. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2014-03-19 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-03-19 |
Time |
15:58 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-03-19 |
Time |
15:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2014-03-19 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-03-19 |
Time |
15:58 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-03-19 |
Time |
15:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2014-03-03 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2014-03-03 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2014-03-03 |
Time |
15:06 |
Sent To |
|
|
Notes |
|
|