Plan Review Details - Permit 14020825
Plan Review Stops For Permit 14020825 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2014-02-26 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-02-26 |
Time |
18:25 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2014-02-26 18:25:28 | ROUTED TO SW FOR ADDRESS PROCESSING |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
N |
Date |
2014-02-24 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-02-24 |
Time |
17:44 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-02-24 |
Time |
08:27 |
Sent To |
|
|
Notes |
2014-02-24 17:44:54 | ROUTED TO SANDY PER SH | 2014-02-24 08:27:40 | EMAILED JAMES JUDGE REGARDING AN ADDRESS FOR THIS FREE | | FLOATING AERATOR |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2014-02-26 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-02-26 |
Time |
18:21 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-02-26 |
Time |
17:44 |
Sent To |
AD |
|
Notes |
2014-02-26 18:23:54 | ELECTRICAL PROVISO: | | AS PER NEC 682.11 THIS SERVICE SHALL DISCONNECT (SHUNT | | TRIP) WHEN THE WATER LEVEL REACHES THE HEIGHT OF THE | | ESTABLISHED ELECTRICAL DATUM PLANE. | | REVIEWED BY MIKE ALBARRAN :(561) 805-6718 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-02-24 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-02-24 |
Time |
17:35 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-02-24 |
Time |
17:34 |
Sent To |
AD |
|
Notes |
2014-02-24 17:41:08 | THE FOLLOWING ITEMS ARE MISSING FROM THE SUBMITTED | | DRAWING FOR APPROVAL: | | 1. INDICATE THE PROPOSED LOCATION OF THE SERVICE IN | | RELATION AND COMPLIANCE WITH THE NEC 682 DATUM | | ELECTRICAL PLANE. | | 2. NEC 682.11 REQUIRES A SHUNT TRIP OR SIMILAR DEVICE | | TO SHUT DOWN THIS SERVICE SHOULD THE WATER RISE ABOVE | | THE ELECTRICAL DATUM PLANE. | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | CONTACT: | | MIKE ALBERTAN, ELECTRICAL PLANS EXAMINER, PX3353 | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | PH: (561) 805-6718, EMAIL: [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-03-06 |
|
|
Cont ID |
|
Sent By |
swurafti |
Date |
2014-03-06 |
Time |
08:45 |
Rev Time |
0.00 |
Received By |
swurafti |
Date |
2014-02-21 |
Time |
13:38 |
Sent To |
|
|
Notes |
2014-02-24 13:38:27 | SENT TO ELECTRICAL UNDER $5000 SHELF FOR REVIEW. JG. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |