Plan Review Details - Permit 14020720
Plan Review Stops For Permit 14020720
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-03-03 Cont ID  
Sent By shill Date 2014-03-03 Time 10:38 Rev Time 0.00
Received By shill Date 2014-03-03 Time 10:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-20 Cont ID  
Sent By shill Date 2014-02-20 Time 14:07 Rev Time 0.00
Received By shill Date 2014-02-20 Time 14:07 Sent To  
Notes
2014-02-20 14:44:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. INDICATE WHICH PROPOSED ASSEMBLY IS PROPOSED FBC
 1609, FBC 107.
  
 2. APPLICATION IS TO WATERPROOF WALLS AND INSTALL CAP
 FLASHING. WHAT MATERIAL WILL BE USED FOR EACH? IT IS
 NOT CLEAR WHETHER THE PROPOSED PRODUCT CAN BE USED ON
 AN VERTICAL APPLICAITON. PROVIDE MORE INFORMATION. A
 DETAIL MAY BE HELPFUL
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-03 Cont ID  
Sent By shill Date 2014-03-03 Time 10:38 Rev Time 0.00
Received By shill Date 2014-02-24 Time 11:09 Sent To  
Notes
2014-02-25 11:09:35RESUBMITTAL SENT TO SAMANTHA'S DESK FOR REVIEW. JG.