Plan Review Details - Permit 14020586
Plan Review Stops For Permit 14020586
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-05-11 Cont ID  
Sent By skennedy Date 2014-05-11 Time 12:17 Rev Time 0.00
Received By skennedy Date 2014-05-11 Time 12:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-25 Cont ID  
Sent By skennedy Date 2014-04-25 Time 11:31 Rev Time 0.00
Received By skennedy Date 2014-04-25 Time 11:31 Sent To  
Notes
2014-04-25 11:59:29AS INDICATED PREVIOUSLY IN THE PLUMBING REVIEW COMMENT
 OF 3/14/14, PROVIDE DETAILS FOR THE CONSTRUCTION OF
 WALLS AND A DOOR FOR AFFORDING PRIVACY TO THE BATHROOM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-16 Cont ID  
Sent By skennedy Date 2014-03-16 Time 11:38 Rev Time 0.00
Received By skennedy Date 2014-03-16 Time 11:38 Sent To  
Notes
2014-03-16 11:34:11FBC 107.3.4 - PRODUCT APPROVALS FOR THOSE PRODUCTS
 WHICH ARE REGULATED BY DCA RULE 9N-3 ARE TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-05-11 Cont ID  
Sent By skennedy Date 2014-05-11 Time 12:17 Rev Time 0.00
Received By skennedy Date 2014-05-11 Time 12:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-04-25 Cont ID  
Sent By skennedy Date 2014-04-25 Time 11:59 Rev Time 0.00
Received By skennedy Date 2014-04-25 Time 11:59 Sent To  
Notes
2014-04-25 12:02:22NO CIRCUIT IS SHOW FOR MECHANICAL EXHAUST WHICH MUST BE
 PROVIDED FOR THE BATH.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-03-16 Cont ID  
Sent By skennedy Date 2014-03-16 Time 11:24 Rev Time 0.00
Received By skennedy Date 2014-03-14 Time 15:51 Sent To  
Notes
2014-03-16 11:39:17MINIMUM PLAN REVIEW CRITERIA. FBC- 107.3.5.3 ?
  
 PROVIDE LOAD CALCULATIONS BASED ON THE NEW ACTUAL
 CONNECTED LOAD. CALCULATIONS INDICATE 2 SMALL APPLIANCE
 KITCHEN CIRCUITS. THIS SHOULD BE REMOVED AS A KITCHEN
 MAY NOT BE PERMITTED WITHIN THE STRUCTURE. THE LOAD
 CALCULATIONS SHOULD INDUCATE THE EXISTING SERVICE IS
 ADEQUATE TO ACCOMODATE THE NEW, ALTHOUGH SMALL,
 PROPOSED LOAD. NOTE INDICATES GFI FOR BATH AREA, NO GFI
 TO SERVICE BATH IS PROVIDED.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-05-11 Cont ID  
Sent By skennedy Date 2014-05-11 Time 12:18 Rev Time 0.00
Received By skennedy Date 2014-05-01 Time 07:20 Sent To  
Notes
2014-05-01 07:20:33INCOMING S. KENNEDY'S DESK . JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-25 Cont ID  
Sent By skennedy Date 2014-04-25 Time 12:05 Rev Time 0.00
Received By skennedy Date 2014-04-16 Time 09:58 Sent To  
Notes
2014-04-17 09:59:02TO SAK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-16 Cont ID  
Sent By skennedy Date 2014-03-16 Time 11:41 Rev Time 0.00
Received By skennedy Date 2014-02-14 Time 10:57 Sent To  
Notes
2014-02-15 10:58:18R02

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2014-05-11 Cont ID  
Sent By skennedy Date 2014-05-11 Time 12:17 Rev Time 0.00
Received By skennedy Date 2014-05-11 Time 12:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-04-25 Cont ID  
Sent By skennedy Date 2014-04-25 Time 12:02 Rev Time 0.00
Received By skennedy Date 2014-04-25 Time 12:02 Sent To  
Notes
2014-04-25 12:03:07SEE PREVIOUS COMMENT WHICH WAS NOT ADDRESS IN
 RESUBMITTAL.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-03-16 Cont ID  
Sent By skennedy Date 2014-03-16 Time 11:36 Rev Time 0.00
Received By skennedy Date 2014-03-16 Time 11:36 Sent To  
Notes
2014-03-16 11:37:56FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 VENTILATION/EXHAUST FOR BATHROOM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-05-11 Cont ID  
Sent By skennedy Date 2014-05-11 Time 12:18 Rev Time 0.00
Received By skennedy Date 2014-05-11 Time 12:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-04-25 Cont ID  
Sent By skennedy Date 2014-04-25 Time 12:03 Rev Time 0.00
Received By skennedy Date 2014-04-25 Time 12:03 Sent To  
Notes
2014-04-25 12:05:29SEE PREVIOUS COMMENTS WHICH WERE NOT ADDRESS IN
 RESUBMITTAL.

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-03-16 Cont ID  
Sent By skennedy Date 2014-03-14 Time 15:51 Rev Time 0.00
Received By skennedy Date 2014-03-14 Time 15:51 Sent To  
Notes
2014-03-16 11:19:33PLAN INDICATES CONNECTION TO SEPTIC TANK, SHOW EVIDENCE
 OF AN APPROVED PRIVATE SEWAGE DISPOSAL SYSTEM IN
 ACCORDANCE WITH CHAPTER 64E-6, FLORIDA ADMINISTRATIVE
 CODE.
 IS THE BATHROOM TO BE AFFORDED PRIVACY? IF SO, SHOW
 PARTITION AND DOOR DETAILS.
 FBC R306.3 SEWAGE DISPOSAL.
 ALL PLUMBING FIXTURES SHALL BE CONNECTED TO A SANITARY
 SEWER OR TO AN APPROVED PRIVATE SEWAGE DISPOSAL SYSTEM
 IN ACCORDANCE WITH CHAPTER 64E-6, FLORIDA
 ADMINISTRATIVE CODE, STANDARDS FOR ONSITE SEWAGE
 TREATMENT AND DISPOSAL SYSTEMS..
  
 SHOW CLEANOUTS REQUIRED PER FBC R-P3005.2
 SHOW HORIZONTAL DRAINAGE PIPE SLOPING PER FBC R-P3005.2
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-02-27 Cont ID  
Sent By dkittred Date 2014-02-25 Time 14:32 Rev Time 0.00
Received By dkittred Date 2014-02-25 Time 13:41 Sent To  
Notes
2014-02-25 14:32:312/25/14 SENT BACK TO R02. DK
  
2014-02-25 14:31:59PLANNING AND ZONING COMMENTS:
  
 2/25/14 (UPDATED 2/27/14)
  
 1. DETACHED GARAGE SIZE AND SETBACKS REVIEWED ONLY. A
 SEPARATE PERMIT IS REQUIRED FOR THE PROPOSED DRIVEWAY.
 (NOTE: NEW DRIVEWAY CANNOT EXCEED 10 FEET IN WIDTH.)
  
 2. IF ANY TREES WILL BE REMOVED OR RELOCATED DUE TO THE
 PROPOSED CONSTRUCTION, A TREE ALTERATION APPLICATION
 WILL NEED TO BE SUBMITTED THROUGH THE PLANNING DIVISION
 AND RECEIVE APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2014-02-24 14:11:032/24/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved