Plan Review Details - Permit 14020551
Plan Review Stops For Permit 14020551
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-09-20 Cont ID  
Sent By jwitmer Date 2014-09-20 Time 11:58 Rev Time 0.00
Received By jwitmer Date 2014-09-20 Time 11:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-08-06 Cont ID  
Sent By jwitmer Date 2014-08-06 Time 16:08 Rev Time 0.00
Received By jwitmer Date 2014-08-06 Time 13:00 Sent To  
Notes
2014-08-06 16:08:37BUILDING PROVISO:
  
 SHEET AE101B & AE101F THE MAIN ENTRY GATE BETWEEN THE
 FITNESS CENTER & BISTRO WILL NEED TO MEET BOTH
 REQUIREMENTS FOR EGRESS:
  
 2010 FBC-B 424.1.3.1.9. ACCESS THROUGH THE BARRIER OR
 FENCE FROM DWELLING UNITS, SUCH AS HOMES, APARTMENTS,
 MOTEL ROOMS AND HOTEL ROOMS, SHALL BE THROUGH
 SELF-CLOSING, SELF-LATCHING LOCKABLE GATES OF 48 INCH
 (1219 MM) MINIMAL HEIGHT FROM THE FLOOR OR GROUND WITH
 THE LATCH LOCATED A MINIMUM OF 54 INCHES (1372 MM) FROM
 THE BOTTOM OF THE GATE OR AT LEAST 3 INCHES (76 MM)
 BELOW THE TOP OF THE GATE ON THE POOL SIDE. IF THE
 SELF-CLOSING, SELF-LATCHING GATE IS ALSO SELF-LOCKING
 AND IS OPERATED BY A KEY LOCK, ELECTRONIC OPENER OR
 INTEGRAL COMBINATION LOCK, THEN THE OPERABLE PARTS OF
 SUCH LOCKS OR OPENERS SHALL BE 34 INCHES MINIMUM (864
 MM) AND 48 INCHES MAXIMUM (1219 MM) ABOVE THE FINISHED
 FLOOR OR GROUND. GATES SHALL OPEN OUTWARD AWAY FROM THE
 POOL AREA.
  
 2010 FBC-B 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING
 ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN
 A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 THE GATES WILL NEED TO BE DESIGNED SO PANIC HARDWARE
 (1008.1.10) WILL BE INSTALLED ON THE INTERIOR SIDE OF
 THE GATE AND THE EXTERIOR SIDE WILL HAVE A RELEASING
 MECHANISM LOCATED AT 54 INCHES ABOVE THE
 DECK(424.1.1.9) . THE RELEASING MECHANISM WILL NEED TO
 BE TIED INTO THE PANIC HARDWARE RELEASING MECHANISM.
 NOTE THE CONCERNS OF A CHILD ON THE EXTERIOR SIDE OF
 THE GATE WILL NOT BE ABLE TO ACTIVATE THE PANIC
 HARDWARE AND GAIN ENTRY INTO THE POOL AREA. THE GATE
 WILL HAVE TO HAVE SELF CLOSING AND SELF LATCHING
 HARDWARE.
  
 THIS TYPE OF SITUATION WILL NEED TO BE ADDRESSED ON ALL
 GATES AND OR DOORS THAT LEAD TO THE POOL DECK FROM THE
 EXTERIOR.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-06-30 Cont ID  
Sent By jwitmer Date 2014-06-30 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2014-06-30 Time 05:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-14 Cont ID  
Sent By jwitmer Date 2014-03-14 Time 16:53 Rev Time 0.00
Received By jwitmer Date 2014-03-14 Time 15:09 Sent To  
Notes
2014-03-14 16:40:50BUILDING PLAN REVIEW
 REVISION: 14020551
 MASTER PERMIT: 13070299
 ADD: 8100 IBIS BLVD
 CONT: THE WEITZ CO.
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: FRIDAY MARCH 14/2014
 ACTION: DENIED
  
 1) PLEASE PROVIDE A NARATIVE FOR EACH SHEET WHAT
 REVISIONS ARE BEING COVERED UNDER THIS SUBMITTAL.
 PLEASE LIGHTEN ALL PREVIOUS REVISIONS SO ONLY THE
 NEWEST REVISIONS ARE HIGHLIGHTED. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-06-25 Cont ID  
Sent By skennedy Date 2014-06-25 Time 15:25 Rev Time 0.00
Received By skennedy Date 2014-06-25 Time 15:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-03-19 Cont ID  
Sent By albarran Date 2014-03-19 Time 15:50 Rev Time 0.00
Received By albarran Date 2014-03-19 Time 09:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2014-09-16 Cont ID  
Sent By wjolin Date 2014-09-16 Time 15:42 Rev Time 0.00
Received By wjolin Date 2014-09-16 Time 15:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2014-08-12 Cont ID  
Sent By wjolin Date 2014-08-12 Time 10:31 Rev Time 0.00
Received By wjolin Date 2014-08-12 Time 08:14 Sent To  
Notes
2014-08-12 08:16:138100 IBIS BOULEVARD
 TRACKING #14020551
 PERMIT #13070299
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET AE324: OPEN FLAME NATURAL GAS FIRE PIT NEEDS A
 FENCE/BARRIER TO PREVENT POOL DECK OCCUPANTS ON THE
 STONE WALL FROM INTENTIONALLY OR ACCIDENTALLY COMING
 INTO CONTACT WITH OPEN FLAMES AND/OR HOT GLASS ROCKS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-06-27 Cont ID  
Sent By wjolin Date 2014-06-27 Time 14:42 Rev Time 0.00
Received By wjolin Date 2014-06-27 Time 10:15 Sent To  
Notes
2014-06-27 11:39:198100 IBIS BOULEVARD
 TRACKING #14020551
 PERMIT #13070299
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET AS105: PLAN INDICATES A NEW GAS FIRE PIT. COULD
 NOT LOCATE ANY SHEETS DETAILING THIS NEW FEATURE.
 INDICATE THE FUEL TYPE (PROPANE, METHANE, ETC.) AND HOW
 THIS FLAME WILL BE GUARDED FROM OCCUPANTS. NOTE:
 OUTDOOR FIREPLACES SHALL BE PROVIDED WITH AN APPROVED
 SPARK ARRESTER, SCREEN OR DOOR.
  
 SHEET AE101F: WHY HAS PANIC HARDWARE BEEN REMOVED FROM
 ALUMINUM GATE EXIT DOORS?
  
 SHEET AE101P: WHY HAS PANIC HARDWARE BEEN REMOVED FROM
 ALUMINUM GATE EXIT DOORS?
  
 SHEET EP101B: THE FIRE ALARM CONTROL PANEL IS NOW
 LOCATED IN STORAGE ROOM #B108B. DEDICATED CLEARANCES
 AND WORKING SPACE SHALL BE PROVIDED AT ALL TIMES TO
 ALLOW EXPEDIENT ACCESS TO THE CONTROL UNIT AT ALL
 TIMES.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-03-12 Cont ID  
Sent By wjolin Date 2014-03-12 Time 07:36 Rev Time 0.00
Received By wjolin Date 2014-03-12 Time 07:27 Sent To  
Notes
2014-03-12 07:36:418100 IBIS BOULEVARD
 PERMIT #14020551
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE DRAWING LAYERS CONTAINING THE PREVIOUS REVISION
 CLOUDS AND PREVIOUS DELTAS NEED TO BE FROZEN TO MAKE
 THE DRAWING READABLE.
  
 PLEASE PROVIDE A NARRATIVE OR DESCRIPTION OF WHAT HAS
 CHANGED..."COORDINATION" IS NOT SPECIFIC ENOUGH.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-09-20 Cont ID  
Sent By jwitmer Date 2014-09-20 Time 11:59 Rev Time 0.00
Received By jwitmer Date 2014-09-05 Time 20:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-08-12 Cont ID  
Sent By cpuell Date 2014-08-12 Time 14:33 Rev Time 0.00
Received By cpuell Date 2014-07-25 Time 11:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-30 Cont ID  
Sent By jwitmer Date 2014-06-30 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2014-05-29 Time 09:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2014-03-19 Time   Rev Time 0.00
Received By rregueir Date 2014-02-13 Time 08:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-06-25 Cont ID  
Sent By skennedy Date 2014-06-25 Time 15:26 Rev Time 0.00
Received By skennedy Date 2014-06-25 Time 15:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-03-01 Cont ID  
Sent By rregueir Date 2014-03-01 Time 09:32 Rev Time 0.00
Received By rregueir Date 2014-03-01 Time 09:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-06-30 Cont ID  
Sent By jwitmer Date 2014-06-30 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2014-06-30 Time 05:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-03-14 Cont ID  
Sent By jwitmer Date 2014-03-14 Time 16:53 Rev Time 0.00
Received By jwitmer Date 2014-03-14 Time 15:39 Sent To  
Notes
2014-03-14 16:53:02PLUMBING PLAN REVIEW
 REVISION: 14020551
 MASTER PERMIT: 13070299
 ADD: 8100 IBIS BLVD
 CONT: THE WEITZ CO.
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: FRIDAY MARCH 14/2014
 ACTION: DENIED
  
 1) PLEASE PROVIDE A NARATIVE FOR EACH SHEET WHAT
 REVISIONS ARE BEING COVERED UNDER THIS SUBMITTAL.
 PLEASE LIGHTEN ALL PREVIOUS REVISIONS SO ONLY THE
 NEWEST REVISIONS ARE HIGHLIGHTED. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-09-29 Cont ID  
Sent By skennedy Date 2014-09-29 Time 14:31 Rev Time 0.00
Received By skennedy Date 2014-09-25 Time 15:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status N Date 2014-06-25 Cont ID  
Sent By avann Date 2014-06-25 Time 15:24 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2014-06-06 10:59:116/5/14

Review Stop Z ZONING
Rev No 1 Status N Date 2014-03-13 Cont ID  
Sent By avann Date 2014-03-13 Time 14:14 Rev Time 0.00
Received By ajones Date 2014-03-13 Time 14:14 Sent To  
Notes
2014-03-03 14:55:453/3/14