Plan Review Details - Permit 14020547
Plan Review Stops For Permit 14020547 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2014-07-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-07-01 |
Time |
15:25 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-07-01 |
Time |
15:25 |
Sent To |
|
|
Notes |
2014-07-01 15:26:06 | ****PROVISOS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER, [email protected], | | 561-805-6724 | | 1. PER APPLICANT, SCOPE OF THIS FOUNDATION PERMIT IS | | LIMITED TO VIBROCOMPACTION, BELOW GRADE FOUNDATIONS, | | AND WATER, SEWER AND STORM PIPING. | | 2. PER APPLICANT, PLAT PLAN HAS BEEN SUBMITTED. | | 3. FBC 110.7 IMPACT OF CONSTRUCTION. PER MANNY | | GONZALEZ, A POLLUTION PREVENTION PLAN HAS BEEN FILED | | WITH THE ENGINEERING DEPARTMENT. | | 4. INFORMATIONAL SHEETS NOT RELATED TO FOUNDATION HAVE | | NOT BEEN REVIEWED. | | 5. REVISE SHEET S5.1, TYPICAL CONCRETE COLUMN, TO | | REMOVE TEXT RELATED TO PILE CAPS. | | 6. PRIOR TO RESUBMITTAL OF THE BUILDING PLANS, PERMIT | | 14030096, PLEASE CONTACT CAROLINE PUELL, 561.805.6659, | | [email protected] TO DISCUSS NAMING CONVENTION FOR THE | | FILES. FOUNDATION PLAN SHEETS WERE NOT NAMED IN A | | MANNER WHICH IS EXPEDITIOUS FOR PLAN REVIEW. MS. PUELL | | IS ABLE TO GIVE GUIDANCE IN THIS AREA. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2014-06-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-06-11 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-06-11 |
Time |
13:43 |
Sent To |
|
|
Notes |
2014-06-11 15:47:03 | ****PROVISOS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER, [email protected], | | 561-805-6724 | | 1. PER APPLICANT, SCOPE OF THIS FOUNDATION PERMIT IS | | LIMITED TO VIBROCOMPACTION, BELOW GRADE FOUNDATIONS, | | AND WATER, SEWER AND STORM PIPING. | | 2. PER APPLICANT, PLAT PLAN HAS BEEN SUBMITTED. | | 3. FBC 110.7 IMPACT OF CONSTRUCTION. PER MANNY | | GONZALEZ, A POLLUTION PREVENTION PLAN HAS BEEN FILED | | WITH THE ENGINEERING DEPARTMENT. | | 4. INFORMATIONAL SHEETS NOT RELATED TO FOUNDATION HAVE | | NOT BEEN REVIEWED. | | 5. REVISE SHEET S5.1, TYPICAL CONCRETE COLUMN, TO | | REMOVE TEXT RELATED TO PILE CAPS. | | 6. PRIOR TO RESUBMITTAL OF THE BUILDING PLANS, PERMIT | | 14030096, PLEASE CONTACT CAROLINE PUELL, 561.805.6659, | | [email protected] TO DISCUSS NAMING CONVENTION FOR THE | | FILES. FOUNDATION PLAN SHEETS WERE NOT NAMED IN A | | MANNER WHICH IS EXPEDITIOUS FOR PLAN REVIEW. MS. PUELL | | IS ABLE TO GIVE GUIDANCE IN THIS AREA. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2014-05-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-05-01 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-04-29 |
Time |
14:56 |
Sent To |
|
|
Notes |
2014-05-01 11:12:54 | ****CORRECTIONS**** | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | PROJECT: LOFTIN PLACE | | CONTRACTOR CONTACT: [email protected] | | ARCHITECT: MSA ARCHITECTS, INC., JOSE I. SAUMELL | | ENGINEER: BBM STRUCTURAL ENGINEERS, JOEL R. | | MIDDLEBROOKS PE | | CONTACT: NEYITA LEIVA, LICENSE & PERMIT SERVICES: | | NEYITALPS01.NET 561-856-6655 | | | | 1. PROVISO - PER APPLICANT, SCOPE OF THIS FOUNDATION | | PERMIT IS LIMITED TO VIBROCOMPACTION, BELOW GRADE | | FOUNDATIONS, AND WATER, SEWER AND STORM PIPING. | | | | 2. PROVISO - PER APPLICANT, PLAT PLAN HAS BEEN | | SUBMITTED. | | | | 3-8. OK | | | | 9. SEE THRESHOLD PLAN REVIEW - THIS IS REQUIRED PRIOR | | TO PERMIT ISSUANCE PER FLORIDA STATUTE 553. | | | | SHEETS S0.5 AND 0.6 (THRESHOLD INSPECTION PLAN) FROM | | THE BUILDING PERMIT ARE IN REVIEW. PLEASE INCLUDE IN | | THIS PERMIT. | | | | 10. PROVISO - FBC 110.7 IMPACT OF CONSTRUCTION. PER | | MANNY GONZALEZ, A POLLUTION PREVENTION PLAN HAS BEEN | | FILED WITH THE ENGINEERING DEPARTMENT. | | | | 11. COMMENT FROM REVIEW #1: FBC 110.3.7.4.4 ALL PLANS | | FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED AND | | SEALED BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A | | STATEMENT THAT, TO THE BEST OF THE ARCHITECT'S OR | | ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS | | COMPLY WITH THE APPLICABLE FIRE SAFETY STANDARDS AS | | DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH | | THIS SECTION AND 633 FLORIDA STATUTE. | | | | 2ND REVIEW, RESPONSE LETTER STATES THAT THIS IS DULY | | NOTED BUT I WAS UNABLE TO LOCATE THE STATEMENT ON THE | | PLANS (REQUIRED TO BE STATED BY THE ARCHITECT AND BY | | THE ENGINEER). | | | | PLEASE ALSO SEE FLORIDA STATUTE 553.79(7) (D): | | ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE | | SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF | | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE | | ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND | | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM | | BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS | | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH | | THIS CHAPTER AND CHAPTER 633. | | | | PLEASE ADVISE AS TO WHICH SHEET THIS STATEMENT CAN BE | | LOCATED, OR ADD TO AT LEAST ONE ARCHITECTURAL AND ONE | | STRUCTURAL SHEET. THIS IS REQUIRED FOR ALL THRESHOLD | | BUILDINGS. | | | | 12-13. OK | | | | 14. PROVISO - INFORMATIONAL SHEETS NOT RELATED TO | | FOUNDATION HAVE NOT BEEN REVIEWED. | | | | 15-16. OK | | | | 17. COMMENT FROM REVIEW #1: REVISE PLAN TO INCLUDE WIND | | DESIGN CRITERIA FBC1603.1.4. | | | | RESPONSE IS THAT THIS IS INCLUDED ON THE BUILDING PLAN. | | THE MASTER HAS NOT YET BEEN ISSUED AND IS STILL IN | | REVIEW; THEREFORE IS NOT A PART OF THE PUBLIC | | RECORD/PERMIT DOCUMENT. FOR THIS FOUNDATION PERMIT | | BEING REQUESTED, PLEASE REVISE PLAN TO INCLUDE WIND | | DESIGN CRITERIA AS REQUIRED BY FBC 1603.1.4. IF THE | | STRUCTURAL ENGINEER FEELS THAT WIND DESIGN CRITERIA IS | | NOT RELEVANT TO THE FOUNDATION DESIGN, PLEASE HAVE HIM | | CALL ME TO DISCUSS. | | | | 18. COMMENT FROM REVIEW #1: PROVIDE MORE INFORMATION | | FOR THE PILES : TYPE, SIZE, ETC., FBC 107. | | 2ND REVIEW, PILES ARE NOT TO BE INSTALLED PER RESPONSE | | LETTER AND PER GEOTECHNICAL REPORT. SEE S5.1, TYPICAL | | CONCRETE COLUMN. THIS DETAIL SHOWS A PILE CAP, PLEASE | | CLARIFY OR REMOVE FROM DETAIL. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-03-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-03-11 |
Time |
15:13 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-03-08 |
Time |
13:37 |
Sent To |
|
|
Notes |
2014-03-11 15:13:12 | ****CORRECTIONS**** | | ****REVISED 3/14/14**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | PROJECT: LOFTIN PLACE | | CONTRACTOR CONTACT: [email protected] | | ARCHITECT: MSA ARCHITECTS, INC., JOSE I. SAUMELL | | ENGINEER: BBM STRUCTURAL ENGINEERS, JOEL R. | | MIDDLEBROOKS PE | | CONTACT: NEYITA LEIVA, LICENSE & PERMIT SERVICES: | | NEYITALPS01.NET 561-856-6655 | | | | | | 1. DEFINE SCOPE OF WORK TO BE INCLUDED ON THIS PERMIT, | | FBC 107. APPLICATION IS FOR FOUNDATION FOR RESIDENTIAL | | AND PARKING STRUCTURES; FOR EXAMPLE, AUGER PILES, ISO | | FOOTINGS, FIRST FLOOR SLAB, WALLS? | | | | 2. C02, SCOPE OF WORK SHOWN ON MULTIPLE LOTS AS WELL AS | | A STREET/ALLEY TO BE ABANDONED. HAS THIS PROPERTY BEEN | | REPLATTED, OR HAS A UNITY OF TITLE BEEN FILED? PLEASE | | ADVISE AS TO STATUS. | | | | 3. SEPARATE DEMO PERMITS REQUIRED, PLEASE ADVISE AS TO | | STATUS OF DEMO PERMITS. | | | | 4. SHEET SD1, TABLES 601 AND 602 APPEAR TO BE THE | | TABLES AND FOOTNOTES FROM FBC 2007 RATHER THAN | | GOVERNING CODE FOR THIS PROJECT, FBC 2010. PLEASE | | REVISE TO CURRENT CODE. | | | | 5. SHEET SD1, FIRE SEPARATIONS, APPEARS TO HAVE A TYPO. | | A 1 HOUR REDUCTION FOR OCCUPANCY SEPARATION IS | | INDICATED. ALTHOUGH THIS REDUCTION WAS NOT TAKEN | | (PROVIDED RATING IS 1), PLEASE REMOVE TO AVOID | | CONFUSION OR PROVIDE CODE SECTION WHERE THIS IS | | PERMITTED. | | | | 6. SHEET SD1, FIRE SEPARATIONS, TENANT SEPARATION | | OPENING PROTECTION REQUIRED IS 45 MINUTES, FBC TABLE | | 715.4, PLEASE REVISE. | | | | 7. SHEET SD1, OPENING PROTECTIVES, 3 HOUR REQUIRED FOR | | A 3 HOUR FIRE WALL OR FIRE BARRIER, 90 MINUTE REQUIRED | | FOR 3 HOUR EXTERIOR WALL, FBC TABLE 715.4. PLEASE | | REVISE LANGUAGE IN TABLE TO BE CONSISTENT WITH FBC | | TABLE 715.4. | | | | 8. PROVIDE MORE INFORMATION ABOUT PHASE II. WILL PHASE | | II BE DESIGNED TO BE ONE BUILDING WITH PHASE I, OR WILL | | IT BE A SEPARATE BUILDING WITH FIRE RATED SEPARATIONS? | | WHAT IS THE PROPOSED HEIGHT AND AREA OF PHASE II, | | HIGHEST HABITABLE FLOOR AND ROOF HEIGHT? FBC 107, FBC | | CHAPTER 5. | | | | 9. FS553.79, FBC 110.3.7, SPECIAL INSPECTOR REQUIRED | | FOR THIS THRESHOLD BUILDING. A COPY OF THE SPECIAL | | INSPECTOR AGREEMENT AND PROGRAM INFORMATION HAS BEEN | | EMAILED TO [email protected]. | | | | 10. FBC 110.7 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION | | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A | | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF | | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO | | AFFECT SAID PROPERTY PURSUANT TO A CONSENT GRANTED BY | | THE APPLICABLE PROPERTY OWNER, UNDER TERMS OR | | CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER. | | THIS INCLUDES, BUT IS NOT | | LIMITED TO, THE CONTROL OF DUST, NOISE, WATER OR | | DRAINAGE RUN-OFFS, DEBRIS, AND THE STORAGE OF | | CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL | | NOT ADVERSELY IMPACT LEGAL HISTORIC SURFACE WATER | | DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, AND MAY | | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH | | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE DRAINAGE | | PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, | | DEVELOPERS, CONTRACTORS AND OWNERS OF ALL NEW | | RESIDENTIAL DEVELOPMENT, INCLUDING | | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR | | ITEMS, ON EXISTING PROPERTIES RESULTING IN A | | SIGNIFICANT DECREASE OF PERMEABLE LAND AREA ON ANY | | PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON THE | | DEVELOPED PROPERTY SHALL, AS A PERMIT CONDITION, | | PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY | | INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON | | COMPLETION OF THE IMPROVEMENT, A CERTIFICATION FROM A | | LICENSED PROFESSIONAL SHALL BE SUBMITTED TO THE | | INSPECTOR IN ORDER TO RECEIVE | | APPROVAL OF THE FINAL INSPECTION. | | | | 11. FBC 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH | | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT | | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE | | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE | | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | FIRE SAFETY STANDARDS AS DETERMINED BY THE LOCAL | | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | FLORIDA STATUTE. | | | | 12. SEE FBC CHAPTER 33, SAFEGUARDS DURING CONSTRUCTION; | | PLEASE NOTE ON PLAN. | | | | 13. PROVIDE THE SOILS INVESTIGATION REPORT PREPARED BY | | ARDAMAN & ASSOCIATES DATED OCTOBER 22, 2013 (REFERENCE | | ON SHEET S5.2), FBC 1803. | | | | 14. ADVISORY ONLY; INFORMATIONAL SHEETS NOT RELATED TO | | FOUNDATION HAVE NOT BEEN REVIEWED (FLOOR PLAN, | | ELEVATIONS). | | | | 15. INFORMATIONAL ONLY: IMPACT FEE ASSESSMENT BY PALM | | BEACH COUNTY REQUIRED PRIOR TO BUILDING PERMIT | | ISSUANCE. SEE IMPACT FEE REVIEW (NOT REQUIRED AT THIS | | TIME FOR FOUNDATION PERMIT). | | | | 16. INDEX REFERS TO S0.1, UNABLE TO LOCATE, FBC 107. | | | | 17. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA | | FBC1603.1.4. | | | | 18. PROVIDE MORE INFORMATION FOR THE PILES - TYPE, | | SIZE, ETC., FBC 107. | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2014-04-25 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-04-25 |
Time |
10:22 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-04-25 |
Time |
09:40 |
Sent To |
|
|
Notes |
2014-04-25 10:23:22 | APPROVED AS NOTED |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-03-17 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-03-17 |
Time |
18:36 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-03-17 |
Time |
18:05 |
Sent To |
|
|
Notes |
2014-03-17 18:39:58 | THE SCOPE OF THIS PERMIT AS PRESENTED IS LIMITED TO A | | FOUNDATION, YET ADDITIONAL ELECTRICAL DATA IS SUBMITED. | | SPECIFY THE SCOPE OF THE WORK AND SUBMITT ACCORDINGLY. | | INDICATE PROPOSED CONDUCTOR INSULATION FOR PROPER | | CALCULATIONS OF CONDUIT FILL. AS IT IS, THEY ARE NOT | | CORRECT. | | PAGE E1.1.1 IS STAMPED AS PASSED BECAUSE THAT IS ALL | | THAT IS FOR THE FOUNDATION. UNTIL ALL RESPECTIVE SHEETS | | ARE STAMPED AND A PASS ENTERED INTO THE SYSTEM A | | COMPLETE APPROVAL IS NOT OBTAINED. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2014-02-21 |
|
|
Cont ID |
|
Sent By |
Mgonzale |
Date |
2014-02-21 |
Time |
|
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
2014-02-21 |
Time |
|
Sent To |
I |
|
Notes |
2014-02-21 16:34:54 | PROVISO: | | | | FORMAL PLAN SUBMITTAL HAS BEEN REGISTERED FOR SITE | | DEVELOPMENT REVIEW WITH THE | | CITY OF WPB ENGINEERING DEPARTMENT | | PLEASE REFER TO: | | HTTP://WPB.ORG/WP-CONTENT/UPLOADS/SITES/7/2012/05/2012- | | 09-11-15-59-45-DEVELOPMENTPERMITPACKAGE2011.PDF | | | | MANUEL JULIAN GONZALEZ | | ENGINEERING PROJECT COORDINATOR | | ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT | | 401 CLEMATIS STREET, 4TH FLOOR | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | DIRECT: (561) 494-1085 | | FAX: (561) 494-1116 | | MOBILE: (561) 644-7301 | | EMAIL: [email protected] | | WWW.WPB.ORG/ENGINEERING | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2014-07-02 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2014-07-02 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2014-07-02 |
Time |
14:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2014-04-22 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2014-04-22 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2014-04-22 |
Time |
16:52 |
Sent To |
|
|
Notes |
2014-04-22 16:52:41 | FOUNDATION WORK ONLY |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2014-02-25 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2014-02-25 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2014-02-25 |
Time |
14:29 |
Sent To |
|
|
Notes |
2014-02-25 14:40:59 | 705 NORTH OLIVE AVENUE | | PERMIT #14020547 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | *****FOUNDATION PERMIT ONLY - CONTRACTOR PROCEEDING AT | | RISK***** | | | | PER NFPA 20, THE LOCATION OF THE FIRE PUMP SHALL BE | | PRE-APPROVED BY THE FIRE DEPARTMENT. | | | | PER NFPA 241, FIRE HYDRANTS SHALL BE INSTALLED, TESTED | | AND INSPECTED PRIOR TO ANY VERTICAL CONSTRUCTION. | | | | PER NFPA 1 SECTION 18.4 INDICATE THE BUILDING/SITE FIRE | | FLOW REQUIREMENTS. | | | | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, | | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2 | | TEMPORARY CONSTRUCTION TRAILERS SHALL BE SEPARATED FROM | | ADJACENT TRAILERS OR STRUCTURES IN ACCORDANCE WITH | | TABLE 4.2.1. PER TABLE 4.2.1: | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | PER NFPA 1 SECTION 18.3.4.1, FIRE HYDRANTS SHALL BE | | PROVIDED WITH CLEARANCES OF 7'-6" TO THE FRONT AND | | SIDES AND 4' TO THE BACKSIDE. | | | | PER NFPA 24 SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE | | FIRE SERVICE MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE | | ARRANGED IN ACCORDANCE WITH ONE OF THE FOLLOWING SO | | THAT THEY CAN BE ISOLATED: | | (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 | | FEET FROM THE BUILDING. | | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST | | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED | | CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE | | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST | | INDICATOR VALVE. | | (2) A WALL POST INDICATOR VALVE | | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN | | ACCORDANCE WITH SECTION 6.4 | | (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING | | VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. | | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A | | BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE | | SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET | | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF | | THE WALL FACING THE BACKFLOW PREVENTER. | | (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM | | ACCESSIBLE FROM THE EXTERIOR | | (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE | | ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE | | AUTHORITY HAVING JURISDICTION | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2014-07-03 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-07-03 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-06-20 |
Time |
14:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2014-06-11 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2014-06-11 |
Time |
16:16 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2014-05-19 |
Time |
13:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-05-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-05-01 |
Time |
18:10 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-04-17 |
Time |
16:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-03-18 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-03-18 |
Time |
16:56 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-02-18 |
Time |
16:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
N |
Date |
2014-03-13 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2014-03-13 |
Time |
17:54 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2014-03-13 |
Time |
17:53 |
Sent To |
|
|
Notes |
2014-03-13 17:58:14 | PER THE EMAIL SENT ON 3/13/14 BY WILLIE SWOOPE, PALM | | BEACH COUNTY IMPACT FEE OFFICE, THE FOUNDATION PERMIT | | MAY BE ISSUED PRIOR TO THE PAYMENT OF IMPACT FEES | | PROVIDED THE IMPACT FEES ARE PAID PRIOR TO THE ISSUANCE | | OF THE BUILDING PERMIT FOR VERTICAL CONSTRUCTION. | | | | ROBERT BROWN | | TELEPHONE: (561) 805 6652 | | E-MAIL: [email protected] |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2014-03-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-03-08 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-03-08 |
Time |
16:04 |
Sent To |
|
|
Notes |
2014-03-08 16:05:48 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED | | PRIOR TO PERMIT ISSUANCE. 561-233-5045 FOR MORE | | INFORMATION. | | | | THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING | | THAT FEES DUE, IF ANY, WERE PAID IS TO BE PROVIDED. | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2014-05-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-05-26 |
Time |
17:25 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-05-26 |
Time |
17:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2014-05-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-05-01 |
Time |
18:09 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-05-01 |
Time |
17:00 |
Sent To |
|
|
Notes |
2014-05-01 18:09:40 | PLUMBING PLAN REVIEW | | LOFTIN PLACE -FOUNDATION PERMIT | | PERMIT: 14020547 | | ADD: 705 N OLIVE AVE | | CONT: KAST CONSTRUCTION | | TEL: (561)689-2910 | | CONTACT: NEYITA (561)856-6655 | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | 2ND REVIEW | | DATE: THURSDAY MAY 01/2014 | | ACTION: DENIED | | | | 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 107.3.5 | | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE | | EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL | | SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND | | DOCUMENTS: | | 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.3 PLUMBING | | SANITARY DRAINAGE | | VENTS | | ROOF DRAINAGE | | SAND INTERCEPTOR OR TRAPS | | ENVIRONMENTAL REQUIREMENTS | | PLUMBING RISER | | | | 2A) 2ND REQUEST, SHEET P-2.1.1.A INDICATES A 8 INCH | | PIPE FOR GARAGE DRAINAGE TO SAND FILTER SEE CIVIL DWGS, | | IF THE PLANS SHOW A SAND FILTER TO GET RID OF OILY | | WATER PLEASE PROVIDE DETAILS FOR SUCH FILTER. AS IN | | YOUR RESPONCE PARKING GARGES DO NOT REQUIRE THE SAND | | FILTER BUT YOU AS THE DESIGNER REQUIRE IT, SHOWN ON | | TTHE PLANS THEN WE WILL NEED THE BACK UP LITERATURE FOR | | THE SIZING OF THE SAND FILTER. | | | | PLEASE COMPLY WITH 2010 FBC-P 1003.1 WHERE REQUIRED. | | INTERCEPTORS AND SEPARATORS SHALL BE PROVIDED TO | | PREVENT THE DISCHARGE OF OIL, GREASE, SAND AND OTHER | | SUBSTANCES HARMFUL OR HAZARDOUS TO THE BUILDING | | DRAINAGE SYSTEM, THE PUBLIC SEWER, THE PRIVATE SEWAGE | | DISPOSAL SYSTEM OR THE SEWAGE TREATMENT PLANT OR | | PROCESSES. | | | | 2B) 2ND REQUEST. 1003.11 (IPC 1003.5) SAND INTERCEPTORS | | IN COMMERCIAL ESTABLISHMENTS. SAND AND SIMILAR | | INTERCEPTORS FOR HEAVY SOLIDS SHALL BE DESIGNED AND | | LOCATED SO AS TO BE PROVIDED WITH READY ACCESS FOR | | CLEANING,AND SHALL HAVE A WATER SEAL OF NOT LESS THAN 6 | | INCHES (152 MM). | | | | 2C) COMPLIED. | | | | 2D) 2ND REQUEST, THIS MAY BE A FOUNDATION PERMIT BUT | | THE ROOF DRAINAGE IS SIZED FROM THE ROOF AREA AND 1/2 | | OF THE HEIGHT OF THE PARAET WALLS, THE PLANS ALSO FAIL | | TO PROVIDE THE CRITERIA FOR SIZING OF THE ROOF | | DRAINAGE, 2010 FBC-P 1106.1 WITH OUT THIS INFORMATION | | WE CAN NOT BE SURE THE CONDUCTORS ARE SIZED PROPERLY. | | 100 YEAR 1 HOUR RAIN FALL 4,5 INCHES. | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | CODE, CHAPTER 1, ADMINISTRATION, 2010 107.3.5.1.3 | | PLUMBING ROOF DRAINAGE ISOMETRIC FOR THE BUILDING. | | PLEASE NOTE THE SHEET INDICATED IN THE DRAWING FILE AS | | 471-P-2.19 IS ACTUALLY SHEET P-218. THE ROOF DECK | | DRAINAGE SHEET. | | | | | | 3) COMPLIED. | | | | 4) COMPLIED. | | | | 5) 2ND REQUEST. THE RESPONSE INDICATES SHEET P6.1 NOTE | | FOR TRAP RESEAL, NOT A TRAP PRIMER. PLEASE REVIEW 2010 | | FBC-P | | THE PLANS INDICATE THE USE OF FLOOR DRAINS IN THE | | GARAGE, FIRE PUMP ROOM, DOMESTIC PUMP ROOM AND TREASH | | ROOMS WITH OUT THE USE OF TRAP PRIMER VALVES. | | 2010 FBC-P 1002.3 PROHIBITED TRAPS. | | THE FOLLOWING TYPES OF TRAPS ARE PROHIBITED: 1. TRAPS | | THAT DEPEND ON MOVING PARTS TO MAINTAIN THE SEAL. | | | | 1002.4 TRAP SEALS. | | EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS | | THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 | | MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO | | ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO | | LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE | | INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE | | TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A | | TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR | | ASSE 1044. | | | | 6) PLEASE NOTE SHOWER ARE BASED ONTHE TOTAL FLOW RATE | | THROUGH SHOWER HEADS AND BODY SPRAYS A 2 INCH TRAP WILL | | ALLOW FOR 5.7 GPM TO 12.3 GPM PER FBC-P TABLE 709.1. NO | | ACTION IS REQUIRED, JUST INFORMATIONAL. | | | | 7) PROJECT DOCS < A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2014-03-10 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-03-10 |
Time |
17:35 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-03-10 |
Time |
14:15 |
Sent To |
|
|
Notes |
2014-03-10 16:22:29 | PLUMBING PLAN REVIEW | | LOFTIN PLACE -FOUNDATION PERMIT | | PERMIT: 14020547 | | ADD: 705 N OLIVE AVE | | CONT: KAST CONSTRUCTION | | TEL: (561)689-2910 | | CONTACT: NEYITA (561)856-6655 | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | 1ST REVIEW | | DATE: MONDAY MARCH 10/2014 | | ACTION: DENIED | | | | 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 107.3.5 | | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE | | EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL | | SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND | | DOCUMENTS: | | 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.3 PLUMBING | | SANITARY DRAINAGE | | VENTS | | ROOF DRAINAGE | | SAND INTERCEPTOR OR TRAPS | | ENVIRONMENTAL REQUIREMENTS | | PLUMBING RISER | | | | 2A) SHEET P-2.1.1.A INDICATES A 8 INCH PIPE FOR GARAGE | | DRAINAGE TO SAND FILTER SEE CIVIL DWGS, COMPLY WITH | | 2010 FBC-P 1003.1 WHERE REQUIRED. INTERCEPTORS AND | | SEPARATORS SHALL BE PROVIDED TO PREVENT THE DISCHARGE | | OF OIL, GREASE, SAND AND OTHER SUBSTANCES HARMFUL OR | | HAZARDOUS TO THE BUILDING DRAINAGE SYSTEM, THE PUBLIC | | SEWER, THE PRIVATE SEWAGE DISPOSAL SYSTEM OR THE SEWAGE | | TREATMENT PLANT OR PROCESSES. | | | | 2B) 1003.11 (IPC 1003.5) SAND INTERCEPTORS IN | | COMMERCIAL ESTABLISHMENTS. SAND AND SIMILAR | | INTERCEPTORS FOR HEAVY SOLIDS SHALL BE DESIGNED AND | | LOCATED SO AS TO BE PROVIDED WITH READY ACCESS FOR | | CLEANING,AND SHALL HAVE A WATER SEAL OF NOT LESS THAN 6 | | INCHES (152 MM). | | | | 2C) THE PLANS INDICATE PART OF THE GARAGE FLOOR DRAINS | | (GD) EMPTYING INTO A 8" PIPE TO THE SAND FILTER AND | | ALSO A 10 INCH THAT EMPTIES INTO A 15 INCH RWL TO | | STORM? | | | | 2D) THIS MAY BE A FOUNDATION PERMIT BUT THE ROOF | | DRAINAGE IS SIZED FROM THE ROOF AREA AND 1/2 OF THE | | HEIGHT OF THE PARAET WALLS, THE PLANS ALSO FAIL TO | | PROVIDE THE CRITERIA FOR SIZING OF THE ROOF DRAINAGE, | | 2010 FBC-P 1106.1 WITH OUT THIS INFORMATION WE CAN NOT | | BE SURE THE CONDUCTORS ARE SIZED PROPERLY. 100 YEAR 1 | | HOUR RAIN FALL 4,5 INCHES. | | | | 3) THE SANITARY PLUMBING ISOMETRIC SHEET P-2.1.1.A FOR | | THE WASHING MACHINES ON THE PLUMBING RISERS IDENTIFIED | | AS 7, 42 & 50 APPEAR TO HAVE FLIPPED THELABELING OF THE | | 2" AND 3 " PIPES BACKWARDS THAT WOULD BE REDUCING THE | | SIZE OF THE VENT FROM 3 INCH TO 2 INCH. | | | | 4) THE STRUCTURAL SHEET S-2.0 DETAIL # 6 INDICATES THE | | USE OF A ELEVATOR PIT AND SUMP, PLEASE PROVIDE | | COMPLIANCE WITH 2010 FBC-P 1003.4 OIL SEPARATORS | | REQUIRED. | | AT REPAIR GARAGES, CAR-WASHING FACILITIES, AT FACTORIES | | WHERE OILY AND FLAMMABLE LIQUID WASTES ARE PRODUCED AND | | IN HYDRAULIC ELEVATOR PITS, SEPARATORS SHALL BE | | INSTALLED INTO WHICH ALL OIL-BEARING, GREASE-BEARING OR | | FLAMMABLE WASTES SHALL BE DISCHARGED BEFORE EMPTYING | | INTO THE BUILDING DRAINAGE SYSTEM OR OTHER POINT OF | | DISPOSAL. | | | | EXCEPTION: AN OIL SEPARATOR IS NOT REQUIRED IN | | HYDRAULIC ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM | | IS INSTALLED. | | | | 5) THE PLANS INDICATE THE USE OF FLOOR DRAINS IN THE | | GARAGE, FIRE PUMP ROOM, DOMESTIC PUMP ROOM AND TREASH | | ROOMS WITH OUT THE USE OF TRAP PRIMER VALVES. 2010 | | FBC-P | | 1002.4 TRAP SEALS. | | EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS | | THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 | | MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO | | ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO | | LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE | | INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE | | TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A | | TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR | | ASSE 1044. | | | | 6) PLEASE NOTE SHOWER ARE BASED ONTHE TOTAL FLOW RATE | | THROUGH SHOWER HEADS AND BODY SPRAYS A 2 INCH TRAP WILL | | ALLOW FOR 5.7 GPM TO 12.3 GPM PER FBC-P TABLE 709.1. NO | | ACTION IS REQUIRED, JUST INFORMATIONAL. | | | | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | THIS REVIEW. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2014-07-11 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-07-11 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-07-11 |
Time |
13:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2014-07-11 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-07-11 |
Time |
07:27 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-07-10 |
Time |
17:00 |
Sent To |
|
|
Notes |
2014-07-11 07:29:44 | 1ST REVIEW: | | | | SUBMITTED ACCEPTABLE "SIGNATURE REPORTS" ARE AS | | FOLLOWS: | | | | JOSE I SAUMELL, LICENSE AR 0013085, 29 ARCHITECTURAL | | FILES. | | JOEL MIDDLEBROOKS, LICENSE PE 35422, 25 | | STRUCTURAL/THRESHOLD FILES. | | | | "SIGNATURE DOCUMENTS" HAVE BEEN SUBMITTED FOR FOUR | | OTHER DESIGN PROFESSIONALS, BUT THE "SIGNATURE | | REPORTS", WERE NOT INCLUDED. THESE REPORTS MAY BE | | E-MAILED TO ME AND SHOULD INCLUDE A " "DELIVERY | | MANIFEST DOCUMENT" AS WELL. | | | | THE DOCUMENTS ARE MISSING FOR THE FOLLOWING DESIGN | | PROFESSIONALS: | | | | RANDY WERTEPNY, PE 72504, 14 FILES. THIS ONE HAS A | | DELIVERY MANIFEST DOCUMENT. | | BUI WEI, PE 52146, 2 FILES. THIS ONE HAS A DELIVERY | | MANIFEST DOCUMENT. | | GREGORY M. JOHNSON, PE 63828, THIS ONE HAS A DELIVERY | | MANIFEST DOCUMENT. | | EDUARDO RAMOS, PE 58741, 17 FILES. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | | | | | |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
6 |
Status |
P |
Date |
2014-07-11 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-07-11 |
Time |
15:05 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-07-11 |
Time |
15:05 |
Sent To |
|
|
Notes |
2014-07-11 15:07:20 | KEN CONRAD INDICATED ADDITIONAL COPIES OF THRESHOLD | | AGREEMENT CAN BE PROVIDED AFTER ISSUANCE. |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
5 |
Status |
F |
Date |
2014-07-10 |
|
|
Cont ID |
|
Sent By |
kconrad |
Date |
2014-07-10 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
kconrad |
Date |
2014-07-10 |
Time |
11:04 |
Sent To |
I |
|
Notes |
2014-07-10 11:07:40 | NEED (3) ORIGINALS OF AGREEMENT. THRESHOLD PLAN SHALL | | BE PROVIDED BY ARDAMAN. |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
4 |
Status |
F |
Date |
2014-07-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-07-01 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-07-01 |
Time |
15:26 |
Sent To |
|
|
Notes |
2014-07-01 15:27:21 | ****CORRECTIONS**** | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. FS553.79, FBC 110.3.7, SPECIAL INSPECTOR REQUIRED | | FOR THIS THRESHOLD BUILDING. A COPY OF THE SPECIAL | | INSPECTOR AGREEMENT AND PROGRAM INFORMATION HAS BEEN | | EMAILED TO [email protected]. | | | | PLEASE SUBMIT INFORMATION TO KEN CONRAD | | ([email protected], 561-805-6666). PLEASE ADVISE WHEN | | THIS PROCESS HAS BEEN COMPLETED. | | | | FS 553.71 (12) "THRESHOLD BUILDING" MEANS ANY BUILDING | | WHICH IS GREATER THAN THREE STORIES OR 50 FEET IN | | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY | | CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE | | WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT | | CONTENT OF GREATER THAN 500 PERSONS. | | | | SEE THRESHOLD INSPECTION PLAN ON THE MASTER PERMIT | | SHEETS S0.5, S0.6. THRESHOLD INSPECTOR REQUIRED FOR ALL | | STRUCTURAL ELEMENTS (INCLUDING FOUNDATION). | | |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
3 |
Status |
F |
Date |
2014-06-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-06-11 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-06-11 |
Time |
13:44 |
Sent To |
|
|
Notes |
2014-06-11 13:45:37 | ****CORRECTIONS**** | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. FS553.79, FBC 110.3.7, SPECIAL INSPECTOR REQUIRED | | FOR THIS THRESHOLD BUILDING. A COPY OF THE SPECIAL | | INSPECTOR AGREEMENT AND PROGRAM INFORMATION HAS BEEN | | EMAILED TO [email protected]. | | | | PLEASE SUBMIT INFORMATION TO KEN CONRAD | | ([email protected], 561-805-6666). PLEASE ADVISE WHEN | | THIS PROCESS HAS BEEN COMPLETED. | | | | FS 553.71 (12) "THRESHOLD BUILDING" MEANS ANY BUILDING | | WHICH IS GREATER THAN THREE STORIES OR 50 FEET IN | | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY | | CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE | | WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT | | CONTENT OF GREATER THAN 500 PERSONS. | | | | SEE THRESHOLD INSPECTION PLAN ON THE MASTER PERMIT | | SHEETS S0.5, S0.6. THRESHOLD INSPECTOR REQUIRED FOR ALL | | STRUCTURAL ELEMENTS (INCLUDING FOUNDATION). | | | | AS APPLICANT HAS SUBMITTED THRESHOLD INSPECTION PLAN AS | | A PART OF THE BUILDING PLAN WHICH HAS NOT YET BEEN | | ISSUED, PLEASE INCLUDE SHEETS S0.5 AND S0.6 WITH THIS | | PERMIT. | | |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
2 |
Status |
F |
Date |
2014-04-29 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-05-01 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-04-29 |
Time |
14:57 |
Sent To |
|
|
Notes |
2014-04-29 14:59:10 | ****CORRECTIONS**** | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. FS553.79, FBC 110.3.7, SPECIAL INSPECTOR REQUIRED | | FOR THIS THRESHOLD BUILDING. A COPY OF THE SPECIAL | | INSPECTOR AGREEMENT AND PROGRAM INFORMATION HAS BEEN | | EMAILED TO [email protected]. | | | | PLEASE SUBMIT INFORMATION TO KEN CONRAD | | ([email protected], 561-805-6666). PLEASE ADVISE WHEN | | THIS PROCESS HAS BEEN COMPLETED. | | | | FS 553.71 (12) "THRESHOLD BUILDING" MEANS ANY BUILDING | | WHICH IS GREATER THAN THREE STORIES OR 50 FEET IN | | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY | | CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE | | WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT | | CONTENT OF GREATER THAN 500 PERSONS. | | | | SEE THRESHOLD INSPECTION PLAN ON THE MASTER PERMIT | | SHEETS S0.5, S0.6. THRESHOLD INSPECTOR REQUIRED FOR ALL | | STRUCTURAL ELEMENTS (INCLUDING FOUNDATION). | | | | AS APPLICANT HAS SUBMITTED THRESHOLD INSPECTION PLAN AS | | A PART OF THE BUILDING PLAN WHICH HAS NOT YET BEEN | | ISSUED, PLEASE INCLUDE SHEETS S0.5 AND S0.6 WITH THIS | | PERMIT. | | |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
1 |
Status |
F |
Date |
2014-03-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-03-11 |
Time |
09:14 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2014-03-11 |
Time |
09:14 |
Sent To |
|
|
Notes |
2014-03-11 09:14:52 | SEE BUILDING COMMENTS | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2014-06-27 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2014-06-27 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2014-06-27 |
Time |
13:26 |
Sent To |
|
|
Notes |
2014-06-25 11:37:35 | 6/25/14 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2014-06-11 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2014-06-11 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2014-06-11 |
Time |
08:48 |
Sent To |
|
|
Notes |
2014-06-11 09:07:55 | 1. SHEET SP-1.1V2 AND A-2.1.1V2 STILL SHOW THE PARKING | | GARGE COLUMNS ENCROACHING INTO THE SETBACK (SETBACK | | LINE IS MEASURED FROM THE CURB FURTHEST FROM THE CENTER | | LINE OF THE ROAD). | | 2. SHEET SP-1.1V2- PARKING SPACES LISTED ON TABLE DO | | NOT CORRESPOND TO NUMBER LISTED ON GARAGE LABEL. | | 3. PLEASE DRAW THE SETBACK LINE ON ALL FLOOR PLANS. IT | | SHALL BE DRAWN STRAIGHT AS A PARALELL LINE TO THE CURB | | FURTHEST FROM THE CENTER LINE OF THE ROAD. | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439. | 2014-05-21 14:40:48 | 5/21/14 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2014-05-01 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2014-05-01 |
Time |
11:29 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2014-05-01 |
Time |
11:29 |
Sent To |
|
|
Notes |
2014-05-01 11:32:46 | FOUNDATION RELATED COMMENTS ONLY: | | 1. BUILDIGN COLUMNS AT PARKING ENTRANCE ARE ENCROACHING | | INTO THE MINIMUM REQUIRED SETBACK (REPEAT COMMENT). | | 2. SWITCH CABINET AND TRANSFORMET ON 6TH STREET SHALL | | BE RELOCATED OUTSIDE THE ROW. | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439. | | | 2014-04-21 15:00:58 | 4/21/14 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2014-03-18 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2014-03-18 |
Time |
13:04 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2014-03-18 |
Time |
13:04 |
Sent To |
|
|
Notes |
2014-03-18 13:15:32 | 1- PLEASE CLEARLY INDICATE COMPLIANCE WITH THE REQUIRED | | SETBACK, AS MEASURED FROM THE BACK OF CURB CLOSER TO | | THE BUIDLING FACADE. | | 2- DRAWINGS INDICATE A POLE TO REMIAN ON THE NW CORNER | | OF 6TH STREET AND OLIVE. IS THERE ANY REASON WHY THIS | | POLE CANNOT BE REMOVED? | | 3- BACK FLOW PREVENTORS LOCATED OUTSIDE THE LOADING | | AREA SHALL BE RELOCATED. PROPOSED LOCATION WILL | | PRECLUDE ANY LANDSCAPE TO BE PLANTED AT THAT LOCATION, | | EXPOSIGN THE PARKING GARAGE FACADE. | | 4- PHASE II INDICATES THE BUS STOP ON DIXIE HWAY TO BE | | RELOCATED. WHERE IS IT GOING? | | 5- PLEASE INCLUDE DETAILS ON THE EXISTING STREETSCAPE | | ON OLIVE AVENUE AND HOW IT IS GOING TO BE MODIFIED WITH | | THE PROJECT. THE GENERAL STREETSCAPE DESIGN ON OLIVE | | SHALL REMAIN CONSISTENT WITH THE REST OF THE STREET. | | FURTHER DISCUSSION IS NECESSARY. | | 6- PARKING SPACES ON OLIVE AVE ARE DIFFERENT THAN SITE | | PLAN, PLEASE DISCUSS CHANGES. (MISSING CURB LINE ON | | SHEET SP-1) | | 7- NEW CURB ON NORTH SIDE OF 6TH STREET SHALL MATCH THE | | BUB OUT ON OLIVE. CURRENTLY SHOWN WITH A SMALL ANGLE TO | | MATCH. | | 8- PLEASE INCLUDE DETAILS ON PROPOSED TRAFFIC CALMING | | ON 6TH STREET. IT NEEDS APPROVAL FROM THE ENGINEERING | | DEPARTMENT (TRANSPORTATION ENG - BRIAN COLLINS). | | 9- SHEET SP-1 SHOWS DIFFERENT CURB LOCATION ON 6TH | | STREET THAN CIVIL DRAWINGS. PLEASE CORRECT FOR | | CONSISTENCY. | | 10- BUILDING COLUMN AT PARKING ENTRANCE ON 6TH STREET | | IS ENCROACHING INTO THE REQUIRED SETBACK. | | 11- MAIN ENTRNACE ON DIXIE HWAY WAS REMOVED. SITE PLAN | | APPROVAL SHOW A MAIN ENTRANCE FROM DIXIE HWAY, AS | | INDICATED BY THE MAIN BUIDLING FEATURES (ENTRY PORCH). | | 12- A NEW COLUMN IS NOW SHOWN IN THE WALK UP UNITS. | | SETBACK SHALL BE MEASURED TO THAT COLUMN IF IT IS | | CLOSER TO THE CURB. | | 13- PARKING DETAIL SHALL COMPLY WITH CITY STANDARD | | STRIPING DETAIL. | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439. | 2014-02-24 14:07:46 | 2/24/14 |
|
|
|