Plan Review Details - Permit 14020497
Plan Review Stops For Permit 14020497
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-05-24 Cont ID  
Sent By rmcdouga Date 2014-05-24 Time 08:05 Rev Time 0.00
Received By rmcdouga Date 2014-05-23 Time 18:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-05-01 Cont ID  
Sent By rmcdouga Date 2014-05-01 Time 18:04 Rev Time 0.00
Received By rmcdouga Date 2014-05-01 Time 10:21 Sent To  
Notes
2014-05-01 18:04:462010 FBC
  
 DENIED BY BUILDING
  
 1) SHOW COMPLIANCE WITH FBC R318.6 WHICH REQUIRES
 GUTTERS WITH DOWNSPOUTS ON ALL BUILDINGS WITH EAVES OF
 LESS THAN 6 INCH HORIZONTAL PROJECTION. GUTTERS ARE
 REQUIRED ANYWHERE THE ROOF IS SLOPED TO DRAIN THE WATER
 FROM THE ROOF AND THE EAVES OVERHANG LESS THAN 6
 INCHES.
  
 2) SHEET S-1 HAS BASE SHEET ENHANCED FASTENING
 CALCULATIONS FOR GAF MODIFIED ROOFING NOA NUMBER
 12-1003.05. PLEASE SUBMIT TWO COPIES OF THE PRODUCT
 APPROVALS THAT HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD. DCA RULE 9N-3
  
 3) THE BASE SHEET ENHANCED FASTENING CALCULATIONS ON
 SHEET S-1 STATE THEY ARE FOR A ROOF HEIGHT OF LESS THAN
 15'. THE PLANS SHOW THAT THE ROOF HEIGHT IS MORE THAN
 20'. PLEASE REVISE TO SHOW ROOF HEIGHT OF LESS THAN
 25'. FBC R301.2.1
  
 4) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 CONNECTORS, HANGERS AND ANCHORS SHOWN ON THE PLANS OR
 SPECIFY THE PRODUCT APPROVAL NUMBER FOR EACH ON THE
 PLANS. DCA RULE 9N-3 THE ONE THAT WAS SUBMITTED DID NOT
 INCLUDE THE SIMPSON LUS210, HM9KT, ABU66 AND BCS2-3/6
 CONNECTORS.
  
 5) THE PLANS SHOW BARREL TILE ON THE COVERED PATIO
 ROOF. SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 ROOF TILE THAT WILL BE USED. SPECIFY HOW IT WILL BE
 ATTACHED TO RESIST OVERTURNING MOMENT BY MARKING ONE OF
 THE FASTENING OPTIONS ON THE PRODUCT APPROVAL. IF
 ADHESIVES ARE TO BE USED FOR TILE INSTALLATION, SUBMIT
 TWO C0PIES OF ITS PRODUCT APPROVALS AS REQUIRED BY DCA
 RULE 9N-3.
  
 6) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 7) THE PRODUCT APPROVAL INSTALLATION DRAWINGS FOR THE
 FRENCH DOORS AND LAWSON SINGLE HUNG WINDOWS WERE NOT
 SHRUNK TO FIT ON 8.5" X 11" PAPER WHEN THEY WERE
 PRINTED. THIS CAUSED SOME OF THE REQUIRED INFORMATION
 TO BE MISSING FROM THE DRAWINGS. SUBMIT COMPLETE
 INSTALLATION DRAWINGS. DCA RULE 9N-3
  
 8) IN ORDER TO SPEED THE PLAN REVIEW PROCESS, PLEASE
 SUBMIT A RESPONSE LETTER WITH THE RE-SUBMITTAL
 INDICATING HOW EACH OF THE REVIEW COMMENTS WAS
 ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-18 Cont ID  
Sent By rmcdouga Date 2014-03-18 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2014-03-17 Time 17:16 Sent To  
Notes
2014-03-18 14:29:322010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TO COPIES OF A SURFACE WATER DRAINAGE PLAN
 SHOWING COMPLIANCE WITH FBC R401.3.
  
 2) SHOW THAT THE FOOTING FOR THE STRUCTURE IS A MINIMUM
 OF 12" BELOW GRADE AS REQUIRED BY FBC R403.1.4.
  
 3) SHOW COMPLIANCE WITH SECTION R318 FOR PROTECTION
 AGAINST TERMITES. ON SHEET S-1 TERMITE PROTECTION IS
 ONLY SPECIFIED FOR THE PORCH SLAB.
  
 4) SHOW COMPLIANCE WITH FBC R318.6 WHICH REQUIRES
 GUTTERS WITH DOWNSPOUTS ON ALL BUILDINGS WITH EAVES OF
 LESS THAN 6 INCH HORIZONTAL PROJECTION.
  
 5) SHEET S-1 HAS BASE SHEET ENHANCED FASTENING
 CALCULATIONS FOR EXPIRED NOA NUMBER 09-0224.01. PLEASE
 REMOVE THEM.
  
 6) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 CONNECTORS, HANGERS AND ANCHORS SHOWN ON THE PLANS OR
 SPECIFY THE PRODUCT APPROVAL NUMBER FOR EACH ON THE
 PLANS. DCA RULE 9N-3
  
 7) THE PLANS SHOW BARREL TILE ON THE COVERED PATIO
 ROOF. HOWEVER, PRODUCT APPROVALS WERE SUBMITTED FOR GAF
 ASPHALT SHINGLES (NOA NO. 11-112-04) WHICH HAS BEEN
 SUPERSEDED. PLEASE CLARIFY AND SUBMIT CURRENT PRODUCT
 APPROVALS. IF BARREL TILE IS TO BE USED SPECIFY HOW IT
 WILL BE ATTACHED TO RESIST OVERTURNING MOMENT. IF
 ADHESIVES ARE TO BE USED FOR TILE INSTALLATION, SUBMIT
 TWO C0PIES OF ITS PRODUCT APPROVALS AS REQUIRED BY DCA
 RULE 9N-3.
  
 8) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 9) THE PRODUCT APPROVAL FOR THE TPO ROOFING WAS NOT
 APPROVED IN WRITING BY THE DESIGNER. IT IS FOR STEEL
 DECK APPLICATION AND THE PLANS SPECIFY A WOOD DECK.
 PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 10) THE FRENCH DOOR PRODUCT APPROVAL THAT WAS SUBMITTED
 IS NON-IMPACT RATED. STORM PANELS ARE REQUIRED. SUBMIT
 TWO COPIES OF PRODUCT APPROVALS FOR THE STORM PANELS
 WITH AN INSTALLATION SCHEDULE AND A KEY PLAN. DCA RULE
 9N-3
  
 11) THE REQUIRED EGRESS DOOR (FRONT DOOR) IS NOT
 ALLOWED TO BE SHUTTERED. SUBMIT PRODUCT APPROVALS FOR A
 LARGE MISSILE IMPACT RATED DOOR. FBC R311.2
  
 12) THE PRODUCT APPROVALS FOR THE LARGE MISSILE IMPACT
 RATED LAWSON WINDOWS IS EXPIRED. SUBMIT CURRENT PRODUCT
 APPROVALS. DCA RULE 9N-3.
  
 13) IN ORDER TO SPEED THE PLAN REVIEW PROCESS, PLEASE
 SUBMIT A RESPONSE LETTER WITH THE RE-SUBMITTAL
 INDICATING HOW EACH OF THE REVIEW COMMENTS WAS
 ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-04-16 Cont ID  
Sent By albarran Date 2014-04-16 Time 14:28 Rev Time 0.00
Received By albarran Date 2014-04-16 Time 13:26 Sent To  
Notes
2014-04-16 14:33:43APPROVED AS NOTED ON THE APPROVED PLANS:
 1. AS PER NEC 210.52(A)2 THERE IS A MISSING FLOOR
 OUTLET ALONG THE STAIR RAIL ON THE 2ND FLOOR.
 2. AN OUTLET ALONG THE OUTSIDE WALL MAY HAVE TO BE
 RELOCATED AS MARKED FOR LINEAR FLOOR AREA COMPLIANCE.
 3. SERVICE RISER FAILED TO MENTION THE GROUNDED
 CONDUCTOR INSIDE THE SUB-FEEDS, A NOTE WAS ADDED WITH
 SPECIFIC REQUIREMENTS (THIS WILL NEED AN (EGC)
 EQUIPMENT GROUNDING CONDUCTOR PER TABLE NEC 250.122,
 UNLESS METAL CONDUIT IS USED.) WAS ADDED TO THE RISER
 DIAGRAMS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-03-04 Cont ID  
Sent By albarran Date 2014-03-04 Time 16:45 Rev Time 0.00
Received By albarran Date 2014-03-04 Time 16:06 Sent To  
Notes
2014-03-04 17:15:28FIRST ELECTRICAL REVIEW FAILED AS NOTED BELOW;
 1. NEC 210.52 HAS SPECIFIC REQUIREMENTS FOR OUTLET
 PLACEMENTS IN DWELLING UNITS WHICH ARE NOT FOLLOWED ON
 THE SUBMITTED DRAWING. BESIDES THE MISSING OUTLETS OF
 THE BALCONY, THE FRONT AND REAR OF THE RESIDENCE, YOU
 MUST ADHERE TO THE 6-2-12 RULE: AN OUTLET WITHIN 6' OF
 EVERY DOOR. EVERY WALL GREATER THAN 2' SHALL HAVE AN
 OUTLET. THERE CAN BE NO MORE THAN 12 LINEAR FT ALONG
 THE WALL BETWEEN OUTLETS.
 2. NEC 300.5(B) DESIGNATE THE INTERIOR OF UNDERGROUND
 RACEWAYS AS WET LOCATIONS, THEREFORE THE INSULATION OF
 THE FEEDER CONDUCTORS SHALL BE LISTED ACCORDINGLY.
 3. MARK ON THE FLOOR PLAN THE LOCATION OF BOTH, THE
 ELECTRIC SERVICE METER AND THE ELECTRICAL PANEL.
 4. NEC 210.12 HAS BROADER ARC-FAULT REQUIREMENTS THAN
 REFLECTED ON YOUR PANEL SCHEDULE.
 5. NEC 406.8 REQUIRES THAT ALL OUTSIDE OUTLETS BE
 LISTED "WR" WEATHER RESISTANT AND BE UNDER AN IN-USE
 TYPE COVER.
 6. NEC 406.11 REQUIRES THAT OUTLETS IN DWELLING UNITS
 BE LISTED "TR" TAMPER-RESISTANT.
 7. THERE IS A CONFLICT BETWEEN YOUR ELECTRICAL NOTE #13
 AND THE PANEL SCHEDULE CIRCUIT 23. THE ELECTRICAL NOTE
 SHALL PREVAIL. THE SMOKE DETECTORS SHOULD BE ON A
 LIGHTING CIRCUIT RATHER THAN ON A DEDICATED CIRCUIT.
 8. AS PER THE FBC-ENERGY CONSERVATION, AT LEAST 50% OF
 YOUR LAMPS SHALL BE OF THE ENERGY EFFICIENT TYPE
 9. THE INSTALLATION OF THE AIR HANDLER IN THE ATTIC
 CREATES CONFLICTS WITH THE FBC-ENERGY SECTION 402,
 BUILDING THERMAL ENVELOP, AND FURTHER REQUIRES
 ADDITIONAL ITEMS, SUCH AS A PERMANENT LADDER TO THE
 ATTIC BY THE NEC
 THE FOLLOWING ARE RECOMMENDATIONS:
 1. RELOCATE THE LIVING ROOM SMOKE DETECTOR AWAY FROM
 THE KITCHEN AND CLOSER TO THE STAIRS.
 2. THE CEILING FANS WITH A LIGHT KIT SHOULD HAVE A
 SECOND SWITCH LEG TO INDEPENDENTLY CONTROL EACH
 FUNCTION.
 3. CHECK YOUR ELECTRICAL NOTES FOR CONFLICTING DATA AND
 REDUNDANCY.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-05-24 Cont ID  
Sent By rmcdouga Date 2014-05-24 Time 08:05 Rev Time 0.00
Received By rmcdouga Date 2014-05-08 Time   Sent To B
Notes
2014-05-09 09:49:51ROUTED TO R. MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-01 Cont ID  
Sent By rmcdouga Date 2014-05-01 Time 18:04 Rev Time 0.00
Received By rmcdouga Date 2014-04-15 Time 15:50 Sent To  
Notes
2014-04-15 15:50:47RESUBMITTAL SENT TO R10 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-18 Cont ID  
Sent By rmcdouga Date 2014-03-18 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2014-02-12 Time 11:37 Sent To  
Notes
2014-02-13 11:38:07SENT TO R12 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2014-06-02 Cont ID  
Sent By rmcdouga Date 2014-06-02 Time 10:47 Rev Time 0.00
Received By rmcdouga Date 2014-06-02 Time 10:47 Sent To  
Notes
2014-06-02 10:48:31MU 2014-4911 NO FEES WERE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-05-24 Cont ID  
Sent By rmcdouga Date 2014-05-24 Time 08:05 Rev Time 0.00
Received By rmcdouga Date 2014-05-24 Time 08:05 Sent To  
Notes
2014-05-24 08:09:17CONTRACTOR NEEDS TO SIGN OUT ONE SET OF PLANS AND TAKE
 THEM TO PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW.
 AFTER THE PLANS ARE REVIEWED AND STAMPED BY THE COUNTY,
 THEY ARE TO BE RETURNED TO THE CITY BUILDING DEPARTMENT
 WITH A COPY OF THE PAID IMPACT FEE RECEIPT.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-03-17 Cont ID  
Sent By rmcdouga Date 2014-03-17 Time 17:06 Rev Time 0.00
Received By rmcdouga Date 2014-03-17 Time 17:06 Sent To  
Notes
2014-03-17 17:07:25AN IMPACT FEE REVIEW BY PALM BEACH COUNTY WILL BE
 REQUIRED AFTER THE PLANS HAVE BEEN APPROVED BY THE CITY
 OF WEST PALM BEACH.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-03-18 Cont ID  
Sent By rmcdouga Date 2014-03-18 Time 07:26 Rev Time 0.00
Received By rmcdouga Date 2014-03-17 Time 17:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-03-17 Cont ID  
Sent By rmcdouga Date 2014-03-17 Time 17:15 Rev Time 0.00
Received By rmcdouga Date 2014-03-17 Time 17:05 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-05-24 Cont ID  
Sent By rmcdouga Date 2014-05-24 Time 11:09 Rev Time 0.00
Received By rmcdouga Date 2014-05-24 Time 11:09 Sent To  
Notes
2014-05-24 11:14:07ROOFING PRODUCT APPROVALS SUBMITTED:
 TAMKO MODIFIED OVER WOOD DECK NOA NO. 12-1003.05
 SANTAFE TILE MISSION BARREL CLAY TILE NOA NO.
 12-0529.12
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-05-02 Cont ID  
Sent By llouie Date 2014-05-02 Time 08:58 Rev Time 0.00
Received By llouie Date 2014-04-23 Time 08:58 Sent To  
Notes
2014-04-23 09:02:36ZONING APPROVED.
 REFERENCE: LANDSCAPE PERMIT #14041021
  
  
  
  
  
  
2014-04-21 14:58:414/21/14

Review Stop Z ZONING
Rev No 1 Status F Date 2014-02-20 Cont ID  
Sent By llouie Date 2014-02-20 Time 15:58 Rev Time 0.00
Received By llouie Date 2014-02-20 Time 15:58 Sent To  
Notes
2014-02-20 16:02:45** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PLEASE ILLUSTRATE THE LOCATION OF ALL PROPOSED
 MECHANICAL EQUIPMENT (I.E. A/C UNIT, ETC.) IN THE SITE
 PLAN IN SHEET A-1. PLEASE NOTE THAT MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FT. INTO A
 SETBACK. (ZLDR S.94-305(B)(4))
  
 2.) THE PROJECT EXCEEDS 50 PERCENT OF THE VALUE OF THE
 STRUCTURE. THE PROJECT IS REQUIRED TO COME INTO
 COMPLIANCE WITH THE CURRENT LANDSCAPE CODE. A LANDSCAPE
 PLAN SHALL BE SUBMITTED AND APPROVED UNDER A SEPARATE
 PERMIT APPLICATION CONCURRENTLY WITH THIS APPLICATION.
 (ZLDR S.94-441(C)(2))
  
 3.) THE SITE PLAN SHOWS A NEW CHAIN LINK FENCE AND GATE
 ALONG THE PERIMETER OF THE PROPERTY. THE PROPOSED FENCE
 SHALL COMPLY WITH THE HEIGHT REQUIREMENTS FOR A FENCE
 IN ZLDR S.94-302(B)(1), AND SHALL BE APPROVED BY A
 SEPARATE PERMIT.
  
 4.) PLEASE NOTE THAT IT SHALL BE UNLAWFUL TO PERFORM,
 OR FOR THE LANDOWNER OF ANY CONSTRUCTION SITE TO ALLOW
 TO BE PERFORMED, ANY CONSTRUCTION ACTIVITY PRIOR TO: 1)
 THE ISSUANCE OF A BUILDING PERMIT, A DEMOLITION PERMIT
 OR A PUBLIC RIGHT-OF-WAY PERMIT, AND 2) THE CITY?S
 APPROVAL OF A STORMWATER POLLUTION PREVENTION PLAN
 (SWPPP). (ZLDR S.94-450(D)(1))
  
 PLEASE NOTE THAT ANY REVISIONS MAY RESULT IN ADDITIONAL
 COMMENTS. CONTACT LINDA LOUIE @ (561) 822-1458 IF YOU
 HAVE QUESTIONS.
  