Plan Review Details - Permit 14020277
Plan Review Stops For Permit 14020277
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-03-12 Cont ID  
Sent By jgomez Date 2014-03-12 Time 11:35 Rev Time 0.00
Received By jgomez Date 2014-03-05 Time 09:08 Sent To  
Notes
2014-03-10 09:09:26PLACED ON JGOMEZ DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-20 Cont ID  
Sent By jgomez Date 2014-02-20 Time 11:11 Rev Time 0.00
Received By jgomez Date 2014-02-19 Time 17:33 Sent To  
Notes
2014-02-19 17:33:45TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-10 Cont ID  
Sent By jgomez Date 2014-02-10 Time 16:50 Rev Time 0.00
Received By jgomez Date 2014-02-10 Time 16:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-03-12 Cont ID  
Sent By jgomez Date 2014-03-12 Time 11:35 Rev Time 0.00
Received By jgomez Date 2014-03-12 Time 11:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-02-20 Cont ID  
Sent By jgomez Date 2014-02-20 Time 11:12 Rev Time 0.00
Received By jgomez Date 2014-02-20 Time 11:12 Sent To  
Notes
2014-02-20 11:16:38MECHANICAL REVIEW SECOND CHECKLIST.
 CODE: 2010 FBC.
  
  
 ***ORIGINAL COMMENT:
 1- PROVIDE 2 COMPLETE SITE SPECIFIC ENGINEERING
 DRAWINGS FOR THE A/C STANDS. SEC. 301.12 OF 2010
 FBC-MECHANICAL.
  
 ***ENGINEERING INFORMATION SUBMITTED FROM "ENGINEERING
 EXPRESS" NEED TO HAVE ENGINEER'S ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
 IN ADDITION, ENGINEERING EXPRESS PACKAGE SUBMITTED
 REQUIRES SITE SPECIFIC ENGINEERING.
  
 ***RESPONSE TO SUBMITTAL:
 ENGINEERING INFORMATION SUBMITTED IS NOT SITE SPECIFIC.
 IT'S GENERIC INFORMATION. ENGINEER NEEDS TO PROVIDE
 COMPLETE INFORMATION FOR THIS SPECIFIC BUILDING.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-02-10 Cont ID  
Sent By jgomez Date 2014-02-10 Time 16:50 Rev Time 0.00
Received By jgomez Date 2014-02-10 Time 16:50 Sent To  
Notes
2014-02-10 17:10:18MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE 2 COMPLETE SITE SPECIFIC ENGINEERING
 DRAWINGS FOR THE A/C STANDS. SEC. 301.12 OF 2010
 FBC-MECHANICAL.
  
 ***ENGINEERING INFORMATION SUBMITTED FROM "ENGINEERING
 EXPRESS" NEED TO HAVE ENGINEER'S ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
 IN ADDITION, ENGINEERING EXPRESS PACKAGE SUBMITTED
 REQUIRES SITE SPECIFIC ENGINEERING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712