Plan Review Details - Permit 14020274
Plan Review Stops For Permit 14020274
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-03-24 Cont ID  
Sent By jgomez Date 2014-03-24 Time 17:59 Rev Time 0.00
Received By jgomez Date 2014-03-24 Time 15:36 Sent To  
Notes
2014-03-24 15:36:57SENT TO JULIO'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-10 Cont ID  
Sent By jgomez Date 2014-02-10 Time 09:37 Rev Time 0.00
Received By jgomez Date 2014-02-10 Time 09:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-03-25 Cont ID  
Sent By jgomez Date 2014-03-24 Time 17:59 Rev Time 0.00
Received By jgomez Date 2014-03-24 Time 17:49 Sent To  
Notes
2014-03-24 17:59:38***REVIEW IN PROGRESS...

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-02-10 Cont ID  
Sent By jgomez Date 2014-02-10 Time 09:37 Rev Time 0.00
Received By jgomez Date 2014-02-10 Time 09:37 Sent To  
Notes
2014-02-10 10:50:31RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS
 CODE: 2010 FBC.
  
 1- PROVIDE REPLACEMENT SIZING CALCULATIONS (2 COPIES)
 AS REQUIRED BY SEC. 101.4.7.1.2 OF 2010 FBC-ENERGY
 CONSERVATION.
 ***NOTE: PLEASE MAKE SURE CALCULATIONS SPECIFY
 EQUIPMENT SHOWN ON THE A/C PLAN SUBMITTED.
  
 2- A/C CONTRACTOR TO PROVIDE COMPLETE SIGNED AND
 NOTARIZED PERMIT APPLICATION. SEC. 105.3 CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  