Plan Review Stops For Permit 14020248 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2014-03-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-03-31 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-03-31 |
Time |
16:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2014-03-14 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-03-13 |
Time |
16:57 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-03-13 |
Time |
16:57 |
Sent To |
|
|
Notes |
2014-03-13 17:23:35 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE 2010 FBC ENERGY CONSERVATION SECTION 101.4.4 AND | | TABLE 101.4.1 REQUIRES BUILDINGS PERMITTED BEFORE MARCH | | 1979 UNDERGOING A CHANGE OF OCCUPANCY TO MEET MINIMUM | | EFFICIENCY LEVELS FOR THE ENVELOPE, THE EQUIPMENT AND | | LIGHTING. THE FORM 402-2010 THAT WAS SUBMITTED REQUIRES | | EACH COMPONENT PRESENT IN THE HOME TO MEET OR EXCEED | | EACH OF THE PERFORMANCE CRITERIA LISTED IN TABLE 402A | | OF THE FORM IN ORDER TO COMPLY WITH CODE USING THIS | | METHOD, OTHERWISE SECTION 405 COMPLIANCE MUST BE USED. | | THE INFORMATION ON THE FORM THAT WAS SUBMITTED DOES NOT | | COMPLY. | | | | 2) SUBMIT A STRUCTURAL DETAIL SHOWING HOW THE GARAGE | | DOOR OPENING WAS ENCLOSED AND THAT IT MEETS THE | | REQUIREMENTS OF THE 2010 FBC. CITY AMENDMENTS 107.2.1 | | | | NOTE: ADDITIONAL DRAWINGS AND DETAILS MAY BE REQUIRED | | BY THE FIELD INSPECTORS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] | 2014-03-13 09:59:26 | PLACED IN THE BLDG BOX | 2014-03-13 09:45:24 | ACCIDENTALLY TOOK IN MY REVIEW UNDER THIS HEADING. | 2014-03-13 09:42:01 | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2014-03-25 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2014-03-25 |
Time |
10:15 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2014-03-25 |
Time |
10:15 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2014-03-13 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-03-13 |
Time |
09:43 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-03-13 |
Time |
9:00 |
Sent To |
B |
|
Notes |
2014-03-13 09:42:56 | NOTICE: REGARDLESS OF WHEN THE NON-PERMITTED WORK WAS | | DONE, IT IS BEING PERMITTED UNDER THE CURRENT CODES AND | | THEREFORE SHALL COMPLY WITH SAME. ALL ELECTRICAL WORK | | SHALL COMPLY WITH THE 2008 EDITION OF THE NATIONAL | | ELECTRICAL CODE. | | AT FIRST SIGHT THE OUTLET SPACING IS NOT CORRECT. I | | DREW IN A FEW MISSING OUTLETS AND NOTED THE PERMIT AS | | ABOVE. | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | CONTACT: | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | PH: (561) 805-6718, EMAIL: [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-03-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-03-31 |
Time |
16:18 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-03-25 |
Time |
10:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-03-14 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-03-14 |
Time |
07:10 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-02-06 |
Time |
11:20 |
Sent To |
|
|
Notes |
2014-02-10 11:20:31 | SENT TO R3 SHELF FOR REVIEW. JG. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
3 |
Status |
P |
Date |
2014-04-01 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-04-01 |
Time |
09:12 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-04-01 |
Time |
09:12 |
Sent To |
|
|
Notes |
2014-04-01 09:13:30 | MU2014-6091 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
F |
Date |
2014-03-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-03-31 |
Time |
16:24 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-03-31 |
Time |
16:24 |
Sent To |
|
|
Notes |
2014-03-31 16:30:27 | SUBMIT A COPY OF THE PAID IMPACT FEE RECIEPT. THE | | OWNER/AGENT'S SIGNATURE IS REQUIRED ON THE ENERGY | | CALCULATION FORMS. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2014-03-13 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-03-13 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-03-13 |
Time |
15:46 |
Sent To |
|
|
Notes |
2014-03-13 15:47:29 | AN IMPACT FEE REVIEW IS REQUIRED BY PALM BEACH COUNTY. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2014-03-31 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-03-31 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-03-31 |
Time |
16:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2014-03-13 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-03-13 |
Time |
17:23 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-03-13 |
Time |
17:23 |
Sent To |
|
|
Notes |
2014-03-13 17:27:08 | 2010 FBC | | | | DENIED BY PLUMBING | | | | 1) PROVIDE PROOF THAT THE BATHROOM SHOWN ON THE PLANS | | WAS INSTALLED WITH A PERMIT, INSPECTED AND APPROVED BY | | THE CITY BUILDING DEPARTMENT. OTHERWISE, SUBMIT TWO | | SETS OF A PLUMBING RISER DIAGRAM WITH THE SIGNATURE, | | NAME AND LICENSE NUMBER OF THE DESIGNER ON THE PLANS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2014-03-25 |
|
|
Cont ID |
|
Sent By |
DKittred |
Date |
2014-03-25 |
Time |
14:56 |
Rev Time |
0.00 |
Received By |
dkittred |
Date |
2014-03-25 |
Time |
12:03 |
Sent To |
|
|
Notes |
2014-03-25 14:56:08 | 3/25/14 SENT TO RM. DK | 2014-03-25 12:03:40 | 3/25/14 RESUB ZONING, SENT TO DK.SG |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2014-02-19 |
|
|
Cont ID |
|
Sent By |
dkittred |
Date |
2014-02-19 |
Time |
08:35 |
Rev Time |
0.00 |
Received By |
dkittred |
Date |
2014-02-18 |
Time |
16:46 |
Sent To |
|
|
Notes |
2014-02-19 08:36:03 | 2/19/14 SENT BACK TO R3. DK | | | 2014-02-19 08:33:48 | PLANNING AND ZONING COMMENTS: ***FAILED*** | | | | 2/19/14 | | | | 1. PLEASE PROVIDE A SURVEY OR PLOT PLAN OF THE PROPERTY | | INDICATING THE LOCATION OF THE RENOVATED SPACE. | | | | 2. THIS PROPERTY IS LOCATED IN THE SF11 ZONING DISTRICT | | AND ACCESSORY APARTMENTS ARE NOT PERMITTED. PLEASE | | CLARIFY THE INTENDED USE OF THIS SPACE. IT MAY BE | | POSSIBLE TO UTILIZE THE SPACE AS A DETACHED BEDROOM (NO | | KITCHEN PERMITTED) IN ASSOCIATION WITH A MAIN HOUSE | | (RENOVATED AREA NOT TO BE RENTED AS A SEPARATE UNIT), | | HOWEVER, ADDITIONAL SITE INFORMATION NEEDS TO BE | | SUBMITTED. | | | | IT IS RECOMMENDED YOU CONTACT THE PLANNING DIVISION | | PRIOR TO RESUBMITTAL TO DISCUSS YOUR OPTIONS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | DANIELLE J. KITTREDGE, AICP | | SENIOR PLANNER | | PLANNING & ZONING DIVISION | | PHONE: (561)-822-1443 | | EMAIL: [email protected] | | | 2014-02-18 15:08:20 | 2/18/14 |
|
|