Plan Review Details - Permit 14020098
Plan Review Stops For Permit 14020098
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-04-15 Cont ID  
Sent By rlecky Date 2014-04-15 Time 12:33 Rev Time 0.00
Received By rlecky Date 2014-04-15 Time 12:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-02-25 Cont ID  
Sent By rlecky Date 2014-02-25 Time 10:44 Rev Time 0.00
Received By rlecky Date 2014-02-25 Time 10:36 Sent To  
Notes
2014-02-25 10:44:2914020098
 5713 CORPORATE WAY
 ADDITION OF TWO DUCT DETECTORS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE SPECIFICATIONS ON THE DUCT DETECTORS. NEC 110.3
 PROVIDE BATTERY CALCULATION FOR THE ALARM SYSTEM. NFPA
 72, 4.5.1
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-04-14 Cont ID  
Sent By rferguso Date 2014-04-14 Time 12:55 Rev Time 0.00
Received By rferguso Date 2014-04-14 Time 12:55 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-02-19 Cont ID  
Sent By rferguso Date 2014-02-19 Time 15:14 Rev Time 0.00
Received By rferguso Date 2014-02-19 Time 15:14 Sent To E
Notes
2014-02-19 15:32:075713 CORPORATE WAY
 PERMIT #14020098
 WEST PALM BEACH FIRE RESCUE PLAN REVIEW COMMENTS.
  
 * PLEASE SUBMIT A DETAILED PLAN OF THE BUILDING, SIZE,
 FIRE ALARM SYSTEM AND LOCATION/INSTALLATION OF NEW
 DEVICES.
 * CORRECTION IN THE STATMENT, IF THE CIRCUIT IS
 COMPROMISED THE SYSTEM MUST GO INTO GENERAL ALARM.
  
 RONALD E. FERGUSON, ASSITANT FIRE MARSHAL
 BUREAU OF FIRE PREVENTION
 WEST PALM BEACH FIRE RESCUE
 PHONE (561) 804-4700

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-16 Cont ID  
Sent By skennedy Date 2014-04-16 Time 17:46 Rev Time 0.00
Received By skennedy Date 2014-04-09 Time 17:07 Sent To PC
Notes
2014-04-10 17:08:06RESUBMITTAL SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-20 Cont ID  
Sent By skennedy Date 2014-03-20 Time 14:55 Rev Time 0.00
Received By skennedy Date 2014-02-04 Time 11:17 Sent To  
Notes
2014-02-04 11:18:09ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-04-16 Cont ID  
Sent By skennedy Date 2014-04-16 Time 17:46 Rev Time 0.00
Received By skennedy Date 2014-04-16 Time 17:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-03-20 Cont ID  
Sent By skennedy Date 2014-03-20 Time 14:55 Rev Time 0.00
Received By skennedy Date 2014-03-20 Time 14:55 Sent To  
Notes
2014-03-20 15:03:08FBC-M 606.1 PROVIDE LISTING INFORMATION TO DEMONSTRATE
 COMPLIANCE WITH UL 268A.