Plan Review Details - Permit 14011775
Plan Review Stops For Permit 14011775 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2014-08-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-18 |
Time |
15:19 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-08 |
Time |
11:47 |
Sent To |
|
|
Notes |
2014-08-08 11:48:42 | INCOMING SENT TO ROBERT MCDOUGAL, PLAN REVIEWER. JW, | | ENTERED INTO THE M STOP BY MISTAKE. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2014-09-03 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-09-03 |
Time |
07:25 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-09-03 |
Time |
07:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2014-09-02 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2014-09-02 |
Time |
15:25 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2014-09-02 |
Time |
15:03 |
Sent To |
|
|
Notes |
2014-09-02 15:25:45 | PLAN DENIED | | | | RETURN AIR IN MASTER BEDROOM MUS BE 14'' DUCT. | | REFER TO SECTION 601.4 BALANCED RETURN AIR | | 2010 FBC (M) | | PER LAST REVIEW NOTE # 5 PROVIDE VALUE OF | | AIR CONDITIONING WORK FOR THIS PROJECT. CITY | | AMENDMENTS 109.3 | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2014-08-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-08-18 |
Time |
15:18 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-18 |
Time |
13:14 |
Sent To |
|
|
Notes |
2014-08-18 14:17:10 | 2010 FBC | | | | MECHANICAL REVIEW IS DENIED | | | | NOTE: NO MECHANICAL PLANS WERE SUBMITTED WITH THE | | MASTER. THE BUILDING CONTRACTOR REQUESTED THE | | MECHANICAL TO BE A SEPARATE PERMIT. | | | | 1) SUBMIT TWO SETS OF MECHANICAL PLANS WITH DUCT SIZES, | | LOCATIONS, GRILL SIZES, CFMS. SPECIFY THE LOCATIONS OF | | THE MECHANICAL EQUIPMENT ON THE PLANS. CITY AMENDMENTS | | 107.3.5.3 ( THE SUPPLY AND RETURN GRILL SIZES WERE NOT | | SPECIFIED ON THE PLANS. ) | | | | 2) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS. | | FBCR M1401.3 ( THE CALCULATIONS THAT WERE SUBMITTED ARE | | NOT ACCEPTABLE IN THIS JURISDICTION. THE CALCS. DO NOT | | MATCH THE THE EQUIPMENT. 27,637 BTU VS. 40,000 BTU ) | | | | 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL | | PLANS THAT MATCHES THE EQUIPMENT SIZING CALCULATIONS. | | CITY AMENDMENTS 107.3.5.3 ( THERE IS NO EQUIPMENT | | SCHEDULE ON THE PLANS. ) | | | | 4) COMPLIED. | | | | 5) SPECIFY THE VALUE OF THE MECHANICAL WORK FOR THIS | | PROJECT. CITY AMENDMENTS 109.3 ( THIS ITEM WAS NOT | | ADDRESSED. ) | | | | 6) NEW COMMENT. THE NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS. | | CITY AMENDMENTS 107.2.1 | | | | 7) NEW COMMENT. IN THE BOTTOM RIGHT OF THE PLAN, IT IS | | SPECIFIED THAT THIS IS AN A/C CHANGE OUT. IN ORDER TO | | AVOID CONFUSION, PLEASE CHANGE TO INDICATE THAT THIS IS | | A NEW INSTALLATION. CITY AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2014-02-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2014-02-10 |
Time |
08:46 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2014-08-08 |
Time |
11:47 |
Sent To |
|
|
Notes |
2014-02-10 09:14:41 | 2010 FBC | | | | MECHANICAL REVIEW IS DENIED | | | | NOTE: NO MECHANICAL PLANS WERE SUBMITTED WITH THE | | MASTER. THE BUILDING CONTRACTOR REQUESTED THE | | MECHANICAL TO BE A SEPARATE PERMIT. | | | | 1) SUBMIT TWO SETS OF MECHANICAL PLANS WITH DUCT SIZES, | | LOCATIONS, GRILL SIZES, CFMS. SPECIFY THE LOCATIONS OF | | THE MECHANICAL EQUIPMENT ON THE PLANS. CITY AMENDMENTS | | 107.3.5.3 | | | | 2) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS. | | FBCR M1401.3 | | | | 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL | | PLANS THAT MATCHES THE EQUIPMENT SIZING CALCULATIONS. | | CITY AMENDMENTS 107.3.5.3 | | | | 4) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED | | RETURN AIR. | | | | 5) SPECIFY THE VALUE OF THE MECHANICAL WORK FOR THIS | | PROJECT. CITY AMENDMENTS 109.3 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
|