Plan Review Details - Permit 14011702
Plan Review Stops For Permit 14011702
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2014-05-16 Cont ID  
Sent By albarran Date 2014-05-16 Time 11:58 Rev Time 0.00
Received By albarran Date 2014-05-16 Time 11:02 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2014-05-06 Cont ID  
Sent By albarran Date 2014-05-06 Time 10:08 Rev Time 0.00
Received By albarran Date 2014-05-06 Time 09:34 Sent To I
Notes
2014-05-06 10:28:41THE RESUBMITTAL DOES NOT ADDRESS THE COMMENTS FOR THE
 PREVIOUS DENIAL. I SPOKE W/JOSE OF CARPENTER ELECTRIC
 TO DISCUSS THE ITEMS I NEED ON THE RESUBMITTAL.
 1. DEFINE THE SCOPE OF WORK ON THE PLANS AND PERMIT.
 2. REVISE THE RISER DIAGRAM TO SHOW LOAD CALC FOR THE
 EM PANEL.
 3. SHOW RATING OF THE ATS
 4. INDICATE THE SIZE OF THE GENERATOR TO CONFIRM IT CAN
 SUSTAIN THE LOADS APPLIED.
 5, LABEL THE ROOMS ON THE SUBMITTED FLOOR PLANS.
 6. REDO THE TITLE BLOCK TO INDICATE THE JOB ADDRESS AND
 ALL REQUIRED FBC DATA. (107.2.1)
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-04-01 Cont ID  
Sent By albarran Date 2014-04-01 Time 19:35 Rev Time 0.00
Received By albarran Date 2014-04-01 Time 19:14 Sent To I
Notes
2014-04-01 19:47:26THE FOLLOWING CORRECTIONS SHALL BE MADE FOR A
 SUCCESSFUL ELECTRICAL PLANS REVIEW:
 1. DEFINE THE SCOPE OF WORK ON THE PERMIT APPLICATION.
 2. PROVIDE PROOF OF DECLARED VALUATION
 3. INDICATE LIGHTING COMPLIANCE AND INCLUDE ON THE
 DRAWINGS THE REQUIRED EMERGENCY AND EXIT LIGHTS. IF ANY
 WORK, BESIDES THE REQUIRED EMERGENCY & EXIT LIGHTING,
 GOES BEYOND THE SCOPE OF YOUR WORK, SO STATE, BUT THE
 EMERGENCY AND EXIT LIGHTING COMPLIANCE WILL BE ADHERED
 TO.
 4.PERMIT APPLICATION STATES "REPAIR ELECTRICAL PANEL",
 YET THERE APPEARS TO BE 5 NEW PANELS INDICATED ON PG.
 E3
 5. THE NOTE BENEATH "EXISTING ELECTRICAL RISER" READS,
 "REPLACE ALL FPE PANELS" DOES THAT MEAN THAT ALL PANELS
 ARE FPE AND SHALL BE REPLACED OR DOES IT MEAN THAT ALL
 FPE PANELS WILL BE REPLACED? IF THE LATER, INDICATE
 WHICH.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-02-24 Cont ID  
Sent By albarran Date 2014-02-24 Time 15:07 Rev Time 0.00
Received By albarran Date 2014-02-24 Time 14:53 Sent To I
Notes
2014-02-24 15:13:41PLANS CALL FOR NEW HVAC AS WELL AS OTHER ELECTRICAL
 WORK NOT ADDRESSED ON THE PERMIT APPLICATION. PLEASE
 REVISE THE PLANS TO DEFINE THE ACTUAL SCOPE OF WORK. IF
 THE SAME SHEET IS TO BE RE-SUBMITTED, MARK THE EXISTING
 AS SUCH AND INDICATE THE NEW AS NEW WORK. FURTHERMORE,
 THE SUBMITTED DRAWINGS CALL FOR WORK ON A GENERATOR NOT
 ADDRESSED ON THE PERMIT EITHER. THE HVAC CONDENSING
 UNITS DO NOT INDICATE THAT THEY COMPLY WITH NEC 210.63.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-05-16 Cont ID  
Sent By albarran Date 2014-05-16 Time 10:40 Rev Time 0.00
Received By albarran Date 2014-05-14 Time 10:39 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-05-06 Cont ID  
Sent By albarran Date 2014-05-06 Time 10:29 Rev Time 0.00
Received By albarran Date 2014-05-05 Time 18:25 Sent To  
Notes
2014-05-06 10:30:18SMALL DENIED BIN "C"
2014-05-05 18:25:24SENT TO M ALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-01 Cont ID  
Sent By albarran Date 2014-04-01 Time 19:47 Rev Time 0.00
Received By albarran Date 2014-03-12 Time 15:28 Sent To  
Notes
2014-04-01 19:48:09SENT TO LARGE DENIED BIN "C"
2014-03-12 15:29:31INCOMING SENT TO ELECTRIC BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2014-02-24 Cont ID  
Sent By albarran Date 2014-02-24 Time 16:25 Rev Time 0.00
Received By albarran Date 2014-01-29 Time 14:45 Sent To I
Notes
2014-02-24 16:26:59I FAXED A LIST OF THE DEFICIENCIES TO EDWIN CALDERON OF
 CARPENTER ELECTRIC AND PLACED FILE IN SMALL DENIED BIN
 "C"
2014-01-29 14:46:13ROUTED TO ELCTRICAL