Plan Review Details - Permit 14011702
Plan Review Stops For Permit 14011702 |
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2014-05-16 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-05-16 |
Time |
11:58 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-05-16 |
Time |
11:02 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2014-05-06 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-05-06 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-05-06 |
Time |
09:34 |
Sent To |
I |
|
Notes |
2014-05-06 10:28:41 | THE RESUBMITTAL DOES NOT ADDRESS THE COMMENTS FOR THE | | PREVIOUS DENIAL. I SPOKE W/JOSE OF CARPENTER ELECTRIC | | TO DISCUSS THE ITEMS I NEED ON THE RESUBMITTAL. | | 1. DEFINE THE SCOPE OF WORK ON THE PLANS AND PERMIT. | | 2. REVISE THE RISER DIAGRAM TO SHOW LOAD CALC FOR THE | | EM PANEL. | | 3. SHOW RATING OF THE ATS | | 4. INDICATE THE SIZE OF THE GENERATOR TO CONFIRM IT CAN | | SUSTAIN THE LOADS APPLIED. | | 5, LABEL THE ROOMS ON THE SUBMITTED FLOOR PLANS. | | 6. REDO THE TITLE BLOCK TO INDICATE THE JOB ADDRESS AND | | ALL REQUIRED FBC DATA. (107.2.1) | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | CONTACT: | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | PH: (561) 805-6718, EMAIL: [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2014-04-01 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-04-01 |
Time |
19:35 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-04-01 |
Time |
19:14 |
Sent To |
I |
|
Notes |
2014-04-01 19:47:26 | THE FOLLOWING CORRECTIONS SHALL BE MADE FOR A | | SUCCESSFUL ELECTRICAL PLANS REVIEW: | | 1. DEFINE THE SCOPE OF WORK ON THE PERMIT APPLICATION. | | 2. PROVIDE PROOF OF DECLARED VALUATION | | 3. INDICATE LIGHTING COMPLIANCE AND INCLUDE ON THE | | DRAWINGS THE REQUIRED EMERGENCY AND EXIT LIGHTS. IF ANY | | WORK, BESIDES THE REQUIRED EMERGENCY & EXIT LIGHTING, | | GOES BEYOND THE SCOPE OF YOUR WORK, SO STATE, BUT THE | | EMERGENCY AND EXIT LIGHTING COMPLIANCE WILL BE ADHERED | | TO. | | 4.PERMIT APPLICATION STATES "REPAIR ELECTRICAL PANEL", | | YET THERE APPEARS TO BE 5 NEW PANELS INDICATED ON PG. | | E3 | | 5. THE NOTE BENEATH "EXISTING ELECTRICAL RISER" READS, | | "REPLACE ALL FPE PANELS" DOES THAT MEAN THAT ALL PANELS | | ARE FPE AND SHALL BE REPLACED OR DOES IT MEAN THAT ALL | | FPE PANELS WILL BE REPLACED? IF THE LATER, INDICATE | | WHICH. | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | CONTACT: | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | PH: (561) 805-6718, EMAIL: [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-02-24 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-02-24 |
Time |
15:07 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-02-24 |
Time |
14:53 |
Sent To |
I |
|
Notes |
2014-02-24 15:13:41 | PLANS CALL FOR NEW HVAC AS WELL AS OTHER ELECTRICAL | | WORK NOT ADDRESSED ON THE PERMIT APPLICATION. PLEASE | | REVISE THE PLANS TO DEFINE THE ACTUAL SCOPE OF WORK. IF | | THE SAME SHEET IS TO BE RE-SUBMITTED, MARK THE EXISTING | | AS SUCH AND INDICATE THE NEW AS NEW WORK. FURTHERMORE, | | THE SUBMITTED DRAWINGS CALL FOR WORK ON A GENERATOR NOT | | ADDRESSED ON THE PERMIT EITHER. THE HVAC CONDENSING | | UNITS DO NOT INDICATE THAT THEY COMPLY WITH NEC 210.63. | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | CONTACT: | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | PH: (561) 805-6718, EMAIL: [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2014-05-16 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-05-16 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-05-14 |
Time |
10:39 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2014-05-06 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-05-06 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-05-05 |
Time |
18:25 |
Sent To |
|
|
Notes |
2014-05-06 10:30:18 | SMALL DENIED BIN "C" | 2014-05-05 18:25:24 | SENT TO M ALBARRAN |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2014-04-01 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-04-01 |
Time |
19:47 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-03-12 |
Time |
15:28 |
Sent To |
|
|
Notes |
2014-04-01 19:48:09 | SENT TO LARGE DENIED BIN "C" | 2014-03-12 15:29:31 | INCOMING SENT TO ELECTRIC BOX. JW |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
F |
Date |
2014-02-24 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2014-02-24 |
Time |
16:25 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2014-01-29 |
Time |
14:45 |
Sent To |
I |
|
Notes |
2014-02-24 16:26:59 | I FAXED A LIST OF THE DEFICIENCIES TO EDWIN CALDERON OF | | CARPENTER ELECTRIC AND PLACED FILE IN SMALL DENIED BIN | | "C" | 2014-01-29 14:46:13 | ROUTED TO ELCTRICAL |
|
|
|