Plan Review Details - Permit 14011502
Plan Review Stops For Permit 14011502
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-05-20 Cont ID  
Sent By JWITMER Date 2014-05-20 Time 20:50 Rev Time 0.00
Received By jwitmer Date 2014-05-20 Time 19:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-16 Cont ID  
Sent By jwitmer Date 2014-04-16 Time 18:28 Rev Time 0.00
Received By jwitmer Date 2014-04-16 Time 17:03 Sent To  
Notes
2014-04-16 18:28:05BUILDING PLAN REVIEW
 PERMIT: 14011502
 ADD:7915 S DIXIE HWY SUITE # 7731
 CONT: SISCA CONSTRUCTION
 TEL: (561)248-9041
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. APRIL 16/ 2014
 ACTION: DENIED
  
 NOTE: ONE SET OF PLANS ARE MISSING A3.0, A4.0, A5.0,
 A6.0 & A7.0 SHEETS.
  
 1-5) COMPLIED.
  
 6) 2ND REQUEST PROVIDE MANUFACTURERS CUT SHEETS FOR THE
 RUBBER MATS, NO NEW A6.0 SHEET. SHEET A3.0 FLOOR
 COVERINGS INDICATE THE USE OF RUBBER MATS RF-1 & RF-2,
 PLEASE PROVIDE DOCUMENTATION THESE PRODUCTS ARE IN
 OCMPLIANCE WITH THE 2010 FBC-B:
 804.4 INTERIOR FLOOR FINISH REQUIREMENTS.
 IN ALL OCCUPANCIES, INTERIOR FLOOR FINISH AND FLOOR
 COVERING MATERIALS IN EXIT ENCLOSURES, EXIT
 PASSAGEWAYS, CORRIDORS AND ROOMS OR SPACES NOT
 SEPARATED FROM CORRIDORS BY FULL-HEIGHT PARTITIONS
 EXTENDING FROM THE FLOOR TO THE UNDERSIDE OF THE
 CEILING SHALL WITHSTAND A MINIMUM CRITICAL RADIANT FLUX
 AS SPECIFIED IN SECTION 804.4.1.
  
 804.4.1 MINIMUM CRITICAL RADIANT FLUX.
 INTERIOR FLOOR FINISH AND FLOOR COVERING MATERIALS IN
 EXIT ENCLOSURES, EXIT PASSAGEWAYS AND CORRIDORS SHALL
 NOT BE LESS THAN CLASS I IN GROUPS I-1, I-2 AND I-3 AND
 NOT LESS THAN CLASS II IN GROUPS A, B, E, H, M, R-1,
 R-2 AND S. IN ALL AREAS, FLOOR COVERING MATERIALS SHALL
 COMPLY WITH THE DOCFF-1 ?PILL TEST? (CPSC 16 CFR, PART
 1630).
  
 EXCEPTION: WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH
 AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1 OR 903.3.1.2, CLASS II MATERIALS ARE
 PERMITTED IN ANY AREA WHERE CLASS I MATERIALS ARE
 REQUIRED, AND MATERIALS COMPLYING WITH THE DOC FF-1
 ?PILL TEST? (CPSC 16 CFR, PART 1630) ARE PERMITTED IN
 ANY AREA WHERE CLASS II MATERIALS ARE REQUIRED.
  
 7-8) COMPLIED
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-02-06 Cont ID  
Sent By jwitmer Date 2014-02-06 Time 08:14 Rev Time 0.00
Received By jwitmer Date 2014-02-06 Time 05:29 Sent To  
Notes
2014-02-06 06:03:18BUILDING PLAN REVIEW
 PERMIT: 14011502
 ADD:7915 S DIXIE HWY SUITE # 7731
 CONT: SISCA CONSTRUCTION
 TEL: (561)248-9041
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. FEB. 06/ 2014
 ACTION: DENIED
  
 NOTE: ONE SET OF PLANS ARE MISSING A3.0, A4.0, A5.0,
 A6.0 & A7.0 SHEETS.
  
 1-5) COMPLIED.
  
 6) 2ND REQUEST PROVIDE MANUFACTURERS CUT SHEETS FOR THE
 RUBBER MATS, NO NEW A6.0 SHEET. SHEET A3.0 FLOOR
 COVERINGS INDICATE THE USE OF RUBBER MATS RF-1 & RF-2,
 PLEASE PROVIDE DOCUMENTATION THESE PRODUCTS ARE IN
 OCMPLIANCE WITH THE 2010 FBC-B:
 804.4 INTERIOR FLOOR FINISH REQUIREMENTS.
 IN ALL OCCUPANCIES, INTERIOR FLOOR FINISH AND FLOOR
 COVERING MATERIALS IN EXIT ENCLOSURES, EXIT
 PASSAGEWAYS, CORRIDORS AND ROOMS OR SPACES NOT
 SEPARATED FROM CORRIDORS BY FULL-HEIGHT PARTITIONS
 EXTENDING FROM THE FLOOR TO THE UNDERSIDE OF THE
 CEILING SHALL WITHSTAND A MINIMUM CRITICAL RADIANT FLUX
 AS SPECIFIED IN SECTION 804.4.1.
  
 804.4.1 MINIMUM CRITICAL RADIANT FLUX.
 INTERIOR FLOOR FINISH AND FLOOR COVERING MATERIALS IN
 EXIT ENCLOSURES, EXIT PASSAGEWAYS AND CORRIDORS SHALL
 NOT BE LESS THAN CLASS I IN GROUPS I-1, I-2 AND I-3 AND
 NOT LESS THAN CLASS II IN GROUPS A, B, E, H, M, R-1,
 R-2 AND S. IN ALL AREAS, FLOOR COVERING MATERIALS SHALL
 COMPLY WITH THE DOCFF-1 ?PILL TEST? (CPSC 16 CFR, PART
 1630).
  
 EXCEPTION: WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH
 AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1 OR 903.3.1.2, CLASS II MATERIALS ARE
 PERMITTED IN ANY AREA WHERE CLASS I MATERIALS ARE
 REQUIRED, AND MATERIALS COMPLYING WITH THE DOC FF-1
 ?PILL TEST? (CPSC 16 CFR, PART 1630) ARE PERMITTED IN
 ANY AREA WHERE CLASS II MATERIALS ARE REQUIRED.
  
 7-8) COMPLIED
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-05-27 Cont ID  
Sent By DHARVEY Date 2014-05-27 Time 19:11 Rev Time 0.00
Received By albarran Date 2014-05-27 Time 18:27 Sent To I
Notes
2014-05-27 19:12:33ELECTRICAL PROVISO: PERMIT 14011502
 BECAUSE ALL THESE SERVICES ARE EXISTING STRICT CODE
 COMPLIANCE IS NOT BEING MANDATED, BUT IN THE INTEREST
 OF LIFE SAFETY ALL SERVICES DEVIATING FROM NEC 230.2 OR
 NEC 230.3 SHALL BE PERMANENTLY LABELED TO INDICATE
 AREAS SERVED.
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-04-10 Cont ID  
Sent By rlecky Date 2014-04-10 Time 14:11 Rev Time 0.00
Received By rlecky Date 2014-04-10 Time 13:15 Sent To  
Notes
2014-04-10 14:20:2314011502
 7731 SOUTH DIXIE
 PLANET FITNESS
 2ND REVIEW
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 THE ELECTRICAL SERVICE AS NOTED ON SHEET E4.1 INDICATES
 A 600A, 277/480 VOLT SERVICE WHICH FEEDS AN EXISTING
 800A, 120/208 VOLT MDB. REVISE PLANS TO SHOW CORRECT
 VOLTAGE AND PHASE. NEC 215.5
  
 THE PLANS ARE NOT CLEAR REGARDING THE LIMITATIONS
 PROVIDED WITHIN THE CODE FOR THE NUMBER OF SERVICES
 ALLOWED TO THE BUILDING AND THE LOCATIONS OF THE MAIN
 DISCONNECTS FOR THE EXISTING AND NEW OCCUPANCIES. FIRE
 SEPARATIONS ARE ONE METHOD TO PROVIDE SEPARATION WITHIN
 STRUCTURES FOR OCCUPANCIES REQUIRING THEIR OWN ELECTRIC
 SERVICE. THE PLAN NEEDS TO VERIFY THAT THERE IS ONLY
 ONE POINT OF SERVICE TO EACH BUILDING AND THAT THE
 ELECTRICAL SERVICE MAINS FOR EACH SERVICE ARE SIX OR
 LESS AND GROUPED IN ONE LOCATION. NEC 230.2, 230.71,
 230.72
  
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE
 ALARM SYSTEMS, SECURITY AND DATA SYSTEMS.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
 561-373-3701
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-02-05 Cont ID  
Sent By dharvey Date 2014-02-05 Time 12:43 Rev Time 0.00
Received By dharvey Date 2014-02-05 Time 10:37 Sent To  
Notes
2014-02-05 10:37:2414011502
 7731 SOUTH DIXIE
 PLANET FITNESS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.22, 110.16, 110.22
  
 PROVIDE DIMENSIONS FOR THE DESIGNATED CLEAR WORKING
 SPACES REQUIRED AROUND THE ELECTRICAL SERVICE EQUIPMENT
 AND PANEL BOARDS. NEC 215.5, 110.26
  
 VERIFY THE EXISTING ELECTRICAL MDP HAS A FAULT CURRENT
 RATING THAT IS SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE
 FOR THE CURRENT THAT MUST BE INTERRUPTED. NEC 110.9
  
 VERIFY THE REQUIRED GFCI PROTECTED RECEPTACLE IS
 AVAILABLE TO SERVICE ROOF TOP MECHANICAL EQUIPMENT. NEC
 210.8(B)
 PROVIDE A STRUCTURAL DETAIL FOR HANGING THE B.A. FANS
 AND TVS FROM THE EXISTING STRUCTURE. FBC 1604.1
  
 PROVIDE A KEY PLAN SHOWING OCCUPANCY LOCATION WITH
 ADJACENT TENANTS. INDICATE LOCATION OF ALL EXISTING OR
 PROPOSED ELECTRICAL SERVICES WITH MAIN DISCONNECTS
 SERVING THE PLAZA. NEC 230.2, 230.7
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE
 ALARM, SECURITY AND DATA SYSTEMS.
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
 561-373-3701
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2014-05-19 Cont ID  
Sent By WJOLIN Date 2014-05-19 Time   Rev Time 0.00
Received By pleduc Date 2014-05-19 Time 14:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-04-17 Cont ID  
Sent By wjolin Date 2014-04-17 Time 15:47 Rev Time 0.00
Received By wjolin Date 2014-04-17 Time 15:04 Sent To  
Notes
2014-04-17 15:42:117731 SOUTH DIXIE HIGHWAY
 PERMIT #14011502
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: THE ASTM E648 TEST RESULTS (CRITICAL
 RADIANT FLUX) ARE FOR "ULTIMATE SYSTEMS LTD" FLOORING;
 HOWEVER, SHEET A6.0 STILL INDICATES "EVERLAST" AND
 "ECORE" FLOORING COMPANIES.
 ORIGINAL COMMENT - SHEET A6.0: FLOOR COVERINGS (RUBBER
 FLOORING), OTHER THAN CARPET, THAT MAY REPRESENT AN
 UNUSUAL HAZARD SHALL HAVE A CRITICAL RADIANT FLUX OF AT
 LEAST 0.1 W/CM2 (RESISTANCE TO FLAME PROPAGATION) AS
 PER NFPA 253.
  
 REPEAT COMMENT - SHEET A6.0: FINISH GB-2 INDICATES SOME
 SORT OF STYROFOAM. THE INTERIOR FINISH MATERIALS FOR
 WALLS AND CEILINGS SHALL MEET THE SMOKE DEVELOPMENT
 (0-450) AND FLAME SPREAD (76-200) REQUIREMENTS FOR
 CLASS C INTERIOR FINISHES PER NFPA 101.
  
 REPEAT COMMENT - GENERAL: PROVIDE AN EXTERIOR KEY SAFE
 TO ALLOW EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO
 THE BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN
 BE ORDERED FROM WWW.KNOXBOX.COM.
  
 REPEAT COMMENT - GENERAL: PROVIDE DRAWING NOTE
 INDICATING ALL CONSTRUCTION AND DEMOLITION WORK SHALL
 CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH AND
 CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 REPEAT COMMENT - GENERAL: PROVIDE DRAWING NOTE
 INDICATING, "FIRE PROTECTION SYSTEMS SHALL REMAIN
 ACTIVE DURING DEMOLITION AND RENOVATION ACTIVITIES. IN
 THE EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE
 FOR MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED BY EMAIL ([email protected]) OR
 IN WRITING (FAX: 561-804-4774) AND APPROVED BY THE
 OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE
 HIGHWAY."
  
 REPEAT COMMENT - GENERAL: FOR ISSUANCE OF A GENERAL
 BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA
 BUILDING CODE REQUIRES SEALED FIRE PROTECTION
 CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF
 50 OR MORE AUTOMATIC FIRE SPRINKLERS. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-01-29 Cont ID  
Sent By wjolin Date 2014-01-29 Time 16:45 Rev Time 0.00
Received By wjolin Date 2014-01-29 Time 15:54 Sent To  
Notes
2014-01-29 16:45:257731 SOUTH DIXIE HIGHWAY
 PERMIT #14011502
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A6.0: FINISH GB-2 INDICATES SOME SORT OF
 STYROFOAM. THE INTERIOR FINISH MATERIALS FOR WALLS AND
 CEILINGS SHALL MEET THE SMOKE DEVELOPMENT (0-450) AND
 FLAME SPREAD (76-200) REQUIREMENTS FOR CLASS C INTERIOR
 FINISHES PER NFPA 101.
  
 SHEET A6.0: FLOOR COVERINGS (RUBBER FLOORING), OTHER
 THAN CARPET, THAT MAY REPRESENT AN UNUSUAL HAZARD SHALL
 HAVE A CRITICAL RADIANT FLUX OF AT LEAST 0.1 W/CM2
 (RESISTANCE TO FLAME PROPAGATION) AS PER NFPA 253.
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING ALL
 CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING, "FIRE
 PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: FOR ISSUANCE OF A GENERAL BUILDING PERMIT,
 SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE
 REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS
 FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC
 FIRE SPRINKLERS. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2014-05-20 Cont ID  
Sent By JWITMER Date 2014-05-20 Time 20:36 Rev Time 0.00
Received By jwitmer Date 2014-05-20 Time 19:51 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2014-04-16 Cont ID  
Sent By jwitmer Date 2014-04-16 Time 19:13 Rev Time 0.00
Received By jwitmer Date 2014-04-16 Time 18:29 Sent To  
Notes
2014-04-16 18:53:21GAS PLAN REVIEW
 PERMIT: 14011502
 ADD:7915 S DIXIE HWY SUITE # 7731
 CONT: SISCA CONSTRUCTION
 TEL: (561)248-9041
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. APRIL 16/ 2014
 ACTION: DENIED
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
  
  
 GAS PLAN REVIEW NOT SUFFICIENT DOCUMENTATION FOR PLAN
 REVIEW.
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. FUEL GAS
 402.3.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE
 SEC. 502 THRU 505.
  
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-02-07 Cont ID  
Sent By jwitmer Date 2014-02-07 Time 14:11 Rev Time 0.00
Received By jwitmer Date 2014-02-07 Time 14:11 Sent To  
Notes
2014-02-07 14:29:14GAS PLAN REVIEW
 PERMIT: 14011502
 ADD:7915 S DIXIE HWY SUITE # 7731
 CONT: SISCA CONSTRUCTION
 TEL: (561)248-9041
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI> . FEB. 07/ 2014
 ACTION: DENIED
  
 GAS PLAN REVIEW NOT SUFFICIENT DOCUMENTATION FOR PLAN
 REVIEW.
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. FUEL GAS
 402.3.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE
 SEC. 502 THRU 505.
  
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-05-27 Cont ID  
Sent By albarran Date 2014-05-27 Time 19:12 Rev Time 0.00
Received By albarran Date 2014-05-12 Time 17:35 Sent To PC
Notes
2014-05-13 17:37:09B25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-21 Cont ID  
Sent By hmoser Date 2014-04-21 Time 13:24 Rev Time 0.00
Received By hmoser Date 2014-04-09 Time 08:35 Sent To  
Notes
2014-04-09 08:37:00INCOMING SENT TO B-13. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-02-26 Cont ID  
Sent By shill Date 2014-02-26 Time 11:43 Rev Time 0.00
Received By shill Date 2014-01-27 Time 09:56 Sent To  
Notes
2014-01-28 09:57:02SENT TO B9 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2014-05-20 Cont ID  
Sent By jwitmer Date 2014-05-20 Time 20:13 Rev Time 0.00
Received By jwitmer Date 2014-05-20 Time 20:13 Sent To  
Notes
2014-05-20 20:14:14PB COUNTY IMPACT FEE OFFICE- STAMPED NO FEES DUE. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-02-07 Cont ID  
Sent By jwitmer Date 2014-02-07 Time 14:57 Rev Time 0.00
Received By jwitmer Date 2014-02-07 Time 14:57 Sent To  
Notes
2014-02-07 14:57:21BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-04-21 Cont ID  
Sent By hmoser Date 2014-04-21 Time 13:24 Rev Time 0.00
Received By hmoser Date 2014-04-21 Time 13:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-02-25 Cont ID  
Sent By hmoser Date 2014-02-25 Time 15:26 Rev Time 0.00
Received By hmoser Date 2014-02-25 Time 15:01 Sent To  
Notes
2014-02-25 15:26:53PLAN DENIED
 1) PROVIDE A DETAIL FROM THE ENGINEER ON THE
 RTU CURB TIE DOWN TO THE ROOF AND THE RTU
 TO CURB TIE DOWN. PROVIDE THE SIZE AND SPACE
 OF THE FASTENER USED. PROVIDE THE TYPE OF FASTENERS
 USED. SAME FOR CENTRIFUGAL FAN ANCHORED TO THE ROOF.
 PER SECTION 301.12 WIND RESISTANCE.2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-05-20 Cont ID  
Sent By jwitmer Date 2014-05-20 Time 20:36 Rev Time 0.00
Received By jwitmer Date 2014-05-20 Time 19:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-04-16 Cont ID  
Sent By jwitmer Date 2014-04-16 Time 18:29 Rev Time 0.00
Received By jwitmer Date 2014-04-16 Time 18:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-02-07 Cont ID  
Sent By jwitmer Date 2014-02-07 Time 14:56 Rev Time 0.00
Received By jwitmer Date 2014-02-07 Time 14:09 Sent To  
Notes
2014-02-07 14:56:07PLUMBING PLAN REVIEW
 PERMIT: 14011502
 ADD:7915 S DIXIE HWY SUITE # 7731
 CONT: SISCA CONSTRUCTION
 TEL: (561)248-9041
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 07/ 2014
 ACTION: DENIED
  
 1) PROVIDE THE MANUFACTURERS SPECIFICATION FOR THE
 LASCO ADA SHOWER, PLEASE PROVIDE COMPLIANCE WITH
 THE2010 FL ACCESSIBLE REQUIREMENTS:
 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES
 (915 MM) BY 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS
 MEASURED AT THE CENTER POINTS OF OPPOSING SIDES AND
 SHALL HAVE A 36 INCH (915 MM) WIDE MINIMUM ENTRY ON THE
 FACE OF THE SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES
 (915 MM) WIDE MINIMUM BY 48 INCHES (1220 MM) LONG
 MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE
 PROVIDED.
  
 2) 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM)
 MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE
 SEAT TOWARD THE SHOWER OPENING.
  
 3) 608.7 THRESHOLDS.
 THRESHOLDS IN ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE
 1/2 INCH (13 MM) HIGH MAXIMUM IN ACCORDANCE WITH 303.
 IN TRANSFER TYPE SHOWER COMPARTMENTS, THRESHOLDS 1/2
 INCH (13 MM) HIGH MAXIMUM SHALL BE BEVELED, ROUNDED, OR
 VERTICAL.
 EXCEPTION: A THRESHOLD 2 INCHES (51 MM) HIGH MAXIMUM
 SHALL BE PERMITTED IN TRANSFER TYPE SHOWER COMPARTMENTS
 IN EXISTING FACILITIES WHERE PROVISION OF A 1/2 INCH
 (13 MM) HIGH THRESHOLD WOULD DISTURB THE STRUCTURAL
 REINFORCEMENT OF THE FLOOR SLAB.
  
 4) 610.3 SHOWER COMPARTMENT SEATS.
 IN TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM
 THE BACK WALL TO A POINT WITHIN 3 INCHES (75 MM) OF THE
 COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL COMPLY
 WITH 610.3.1 OR 610.3.2.
  
 5) SEE GAS COMMENTS SEPERATE REVIEW AND PERMIT
 REQUIRED. PLANS CAN BE INCLUDED UNDER THE MASTER SET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-02-10 Cont ID  
Sent By llouie Date 2014-02-10 Time 17:24 Rev Time 0.00
Received By llouie Date 2014-02-10 Time 17:24 Sent To  
Notes
2014-02-10 17:27:02RENOVATION DOES NOT EXCEED 50 PERCENT OF THE VALUE OF
 THE STRUCTURE; USE PERMITTED IN GC.
  
  
2014-02-10 16:11:482/10/14