Plan Review Details - Permit 14011471
Plan Review Stops For Permit 14011471
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-30 Cont ID  
Sent By jwitmer Date 2014-01-30 Time 14:32 Rev Time 0.00
Received By jwitmer Date 2014-01-24 Time 10:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-01-30 Cont ID  
Sent By jwitmer Date 2014-01-30 Time 14:32 Rev Time 0.00
Received By jwitmer Date 2014-01-27 Time 10:06 Sent To  
Notes
2014-01-27 10:07:01PLUMBING PROVISO:
 AIR ADMITTANCE VALVE ON KITCHEN SINK:
 917.3.2 RELIEF VENT.
 WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK,
 THE HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF
 VENT THAT SHALL CONNECT TO A VENT STACK OR
 STACK VENT, OR EXTEND OUTDOORS TO THE OPEN AIR. THE
 RELIEF VENT SHALL CONNECT TO THE HORIZONTAL BRANCH
 DRAIN BETWEEN THE STACK AND THE MOST DOWNSTREAM FIXTURE
 DRAIN CONNECTED TO THE HORIZONTAL BRANCH
 DRAIN. THE RELIEF VENT SHALL BE SIZED IN ACCORDANCE
 WITH SECTION 916.2 AND INSTALLED IN ACCORDANCE WITH
 SECTION 905. THE RELIEF VENT SHALL BE PERMITTED TO
 SERVE AS THE VENT FOR OTHER FIXTURES.