Plan Review Details - Permit 14011308
Plan Review Stops For Permit 14011308
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-25 Cont ID  
Sent By jwitmer Date 2014-01-25 Time 14:29 Rev Time 0.00
Received By jwitmer Date 2014-01-22 Time 16:43 Sent To  
Notes
2014-01-22 16:43:39ROUTED TO PLUMBING $5000 & UNDER

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-01-25 Cont ID  
Sent By jwitmer Date 2014-01-25 Time 14:29 Rev Time 0.00
Received By jwitmer Date 2014-01-25 Time 13:58 Sent To  
Notes
2014-01-25 14:18:53FUEL GAS PLAN REVIEW
 PERMIT: 14011308
 ADD: 425 33RD ST
 CONT: ANYTIME COMPANIES, INC
 TEL: (561)969-3996
  
 2010 FLORIDA FUE GAS CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SATURDAY JAN. 25/ 2014
 ACTION: DENIED
  
 1) SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, 2010 FBC- FUEL GAS 402.3.
  
 2) TYPE OF GAS, (LP OR NATURAL).
  
 3) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 4) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 5) SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2.
  
 6) MANUFACTURERS SPECIFICATION SHEETS TO IDENTIFY WHERE
 THE UNITS CAN OR CAN NOT BE INSTALLED, CLOSENESS TO
 DOORS, WINDOWS & SOFFITS. 503.4.2 SPECIAL GAS VENTS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  