Plan Review Details - Permit 14011279
Plan Review Stops For Permit 14011279
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-01-27 Cont ID  
Sent By jwitmer Date 2014-01-27 Time 05:57 Rev Time 0.00
Received By jwitmer Date 2014-01-27 Time 05:30 Sent To  
Notes
2014-01-27 06:02:1414011279
 INSTALATION OF NATURAL GAS LINE
 NATURAL
 0.5 PS
 TABLE 402.4(19)
 PRESSURE DROP O.5 IN. W.C.
 SPECIFIC GRAVITY 0.60
 METHOD: LONGEST LENGTH
 20'-0"
 3/4 " PE PIPE
  
 2010 FUEL GAS PROVISO:
 404.15.3 TRACER.
 A YELLOW INSULATED COPPER TRACER WIRE OR OTHER APPROVED
 CONDUCTOR SHALL BE
 INSTALLED ADJACENT TO UNDERGROUND NONMETALLIC PIPING .
 ACCESS SHALL BE PROVIDED
 TO THE TRACER WIRE OR THE TRACER WIRE SHALL TERMINATE
 ABOVE GROUND AT EACH END
 OF THE NONMETALLIC PIPING . THE TRACER WIRE SIZE SHALL
 NOT BE LESS THAN 18 AWG AND
 THE INSULATION TYPE SHALL BE SUITABLE FOR DIRECT
 BURIAL.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-01-25 Cont ID  
Sent By jwitmer Date 2014-01-25 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2014-01-25 Time 12:45 Sent To  
Notes
2014-01-25 13:49:33FUEL GAS PLAN REVIEW
 PERMIT: 14011279
 ADD: 816 ARDMORE RD
 CONT: APEX GAS CONTRACTORS
 TEL: (561)202-7873
  
 2010 FLORIDA FUEL GAS CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SATURDAY JAN. 25/ 2014
 ACTION: DENIED
  
 1) SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2.
  
 2) 503.4.2 SPECIAL GAS VENTS. SPECIAL GAS VENTS SHALL
 BE LISTED AND INSTALLED IN ACCORDANCE WITH THE SPECIAL
 GAS VENT MANUFACTURER?S INSTALLATION INSTRUCTIONS.
 TO PROVIDE THE MINIMUM PROXIMATY OF THE APPLIANCE TO
 WINDOWS, DOORS, INSIDE CORNERS AND ROOF OVER HANGS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-27 Cont ID  
Sent By jwitmer Date 2014-01-27 Time 06:11 Rev Time 0.00
Received By jwitmer Date 2014-01-27 Time 05:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-01-25 Cont ID  
Sent By jwitmer Date 2014-01-25 Time 13:57 Rev Time 0.00
Received By jwitmer Date 2014-01-25 Time 12:45 Sent To  
Notes
2014-01-22 14:31:06ROUTED TO PLUMBING LESS THAN $5000