2014-01-23 16:16:28****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE FBC 2010 RESIDENTIAL 301, PLEASE SEE DEFINITION
 OF EXPOSURE B. STRUCTURE APPEARS TO BE LOCATED IN
 EXPOSURE C, PLEASE REVISE FLAT DECK CALCULATIONS.
  
 2. CALCULATIONS REFER TO PAGE 23, BUT THIS PAGE WAS NOT
 SUBMITTED. PAGE 31 WAS SUBMITTED, BUT THIS ASSEMBLY
 REFERS TO GENERAL LIMITATION #9 WHICH DOES NOT ALLOW
 ENHANCED FASTENING. CALCULATIONS NOT REVIEWED AT THIS
 TIME UNTIL THE PAGE WITH THE PROPOSED ASSEMBLY IS
 PROVIDED.
  
  
  