Plan Review Details - Permit 14011176
Plan Review Stops For Permit 14011176
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2014-08-22 Cont ID  
Sent By rmcdouga Date 2014-08-22 Time 16:37 Rev Time 0.00
Received By rmcdouga Date 2014-08-22 Time 16:37 Sent To  
Notes
2014-08-22 16:42:45BUILDING PROVISO / APPROVED WITH EXCEPTION.
  
 SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE ROOF
 COVERING MATERIALS THAT HAVE BEEN REVIEWED AND APPROVED
 BY THE DESIGNER OF RECORD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-08-21 Cont ID  
Sent By rmcdouga Date 2014-08-21 Time 09:35 Rev Time 0.00
Received By rmcdouga Date 2014-08-21 Time 06:38 Sent To E
Notes
2014-08-21 08:58:242010 FBC
  
 DENIED BY BUILDING
  
 1) THE NON-ENGINEERED FLOOD OPENINGS SPECIFIED ON
 SHEETS A-1 AND A-4 OF THE PLANS ARE ALL LOCATED ON THE
 SAME EXTERIOR WALL. FBCR322.2.2(2)(2.1) REQUIRES A
 MINIMUM OF TWO OPENINGS ON DIFFERENT SIDES OF EACH
 ENCLOSED AREA. PROVIDE OPENINGS ON ONE OF THE OTHER
 EXTERIOR WALLS. ONLY THE "NET OPEN AREA" OF THE
 NON-ENGINEERED OPENINGS CAN BE COUNTED TOWARD THE
 REQUIRED FLOOD OPENING AREA. THE MEASUREMENT OF THE NET
 OPEN AREA MUST TAKE INTO CONSIDERATION ANY COVERINGS
 THAT HAVE SOLID OBSTRUCTIONS, SUCH AS GRILLS, FIXED
 LOUVERS OR FACEPLATES.
  
 2) THE ROOFING PRODUCT APPROVALS THAT WERE SUBMITTED
 ARE FOR A CONCRETE DECK AND THIS PROJECT HAS A PLYWOOD
 ROOF DECK. THE PRODUCT APPROVALS ARE REQUIRED TO BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD. SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR
 THE ROOFING MATERIALS THAT WILL BE USED AS REQUIRED BY
 DCA RULE 9N-3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-07-03 Cont ID  
Sent By RMCDOUGA Date 2014-07-03 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2014-07-02 Time 18:54 Sent To E
Notes
2014-07-03 07:32:312010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WITH A
 REQUIRED BASE FLOOD ELEVATION OF 7' NGVD. THE ELEVATION
 FOR THE FINISH FLOOR OF THE GARAGE IS SPECIFIED ON THE
 PLANS AS 5.74', WHICH DOES NOT COMPLY WITH THE CITY'S
 FLOOD ORDINANCE (6" ABOVE BFE). BECAUSE THE ADDITION OF
 A SECOND FLOOR TO THE GARAGE IS A SUBSTANTIAL
 IMPROVEMENT THE EXISTING GARAGE IS REQUIRED TO COMPLY
 WITH THE FLOOD ORDINANCE. THE FINISH FLOOR OF THE
 GARAGE CAN BE RAISED TO 7.5' NGVD. IF THE GARAGE IS
 USED SOLELY FOR THE PARKING OF VECHICLES, THE FINISHED
 FLOOR CAN BE BELOW THE BFE AND ENGINEERED FLOOD VENTS
 OR FLOOD OPENINGS CAN BE INSTALLED IN THE WALLS OF THE
 GARAGE ( SEE FEMA TECHINICAL BULLETIN 1 / AUGUST 2008 )
 OR SOME OTHER APPROVED METHOD MAY BE USED.
 THE NOTE ON THE NEW S-1 SHEET THAT WAS SUBMITTED
 REQUIRES THE CONTRACTOR TO VERIFY EXISTING FLOOD VENTS
 ARE PRESENT AND NOTIFY ENGINEER IF NONE ARE PRESENT.
 THIS NEEDS TO BE ADDRESSED BEFORE THE PERMIT IS ISSUED.
 SPECIFY THE SIZE AND LOCATION OF THE FLOOD OPENINGS ON
 THE PLANS. PROVIDE CALCULATIONS TO SHOW THAT REQUIRED
 AREA OF FLOOD OPENINGS HAS BEEN PROVIDED. IF ENGINEERED
 FLOOD VENTS, SUCH AS 'SMART VENTS' ARE USED SUBMIT TWO
 COPIES OF THE PRODUCT APPROVALS FOR THEM AS REQUIRED BY
 DCA RULE 9N-3. YOU WILL ALSO NEED TO SHOW THAT NO
 EQUIPMENT OR MATERIALS THAT ARE NOT FLOOD
 DAMAGE-RESISTANT IS LOCATED BELOW THE 7.5' BFE.
  
 2) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER/AGENT. THIS COMMENT WAS NOT
 ADDRESSED.
  
 3) THE ENERGY CALCULATION FORM LISTS THE INSULATION FOR
 THE FLOOR OVER THE GARAGE AS R-21.0 AND THE SECTIONS ON
 SHEET A-6 SPECIFY R-11 BATT INSULATION. PLEASE CORRECT.
 THIS COMMENT WAS NOT ADDRESSED.
  
 4) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 ROOFING MATERIALS THAT WILL BE USED AS REQUIRED BY DCA
 RULE 9N-3. THIS COMMENT WAS NOT ADDRESSED.
  
 5) THE VALUE OF $23,000.00 SPECIFIED ON THE PERMIT
 APPLICATION IS TOO LOW FOR THE SCOPE OF WORK SHOWN ON
 THE PLANS. CITY AMENDMENTS 109.3 THIS COMMENT WAS NOT
 ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-05-29 Cont ID  
Sent By rmcdouga Date 2014-05-29 Time 17:10 Rev Time 0.00
Received By rmcdouga Date 2014-05-28 Time 15:56 Sent To Z
Notes
2014-05-29 11:10:582010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WITH A
 REQUIRED BASE FLOOD ELEVATION OF 7' NGVD. THE ELEVATION
 FOR THE FINISH FLOOR OF THE GARAGE IS SPECIFIED ON THE
 PLANS AS 5.74', WHICH DOES NOT COMPLY WITH THE CITY'S
 FLOOD ORDINANCE (6" ABOVE BFE). BECAUSE THE ADDITION OF
 A SECOND FLOOR TO THE GARAGE IS A SUBSTANTIAL
 IMPROVEMENT THE EXISTING GARAGE IS REQUIRED TO COMPLY
 WITH THE FLOOD ORDINANCE. THE FINISH FLOOR OF THE
 GARAGE CAN BE RAISED TO 7.5' NGVD. IF THE GARAGE IS
 USED SOLELY FOR THE PARKING OF VECHICLES, THE FINISHED
 FLOOR CAN BE BELOW THE BFE AND ENGINEERED FLOOD VENTS
 OR FLOOD OPENINGS CAN BE INSTALLED IN THE WALLS OF THE
 GARAGE ( SEE FEMA TECHINICAL BULLETIN 1 / AUGUST 2008 )
 OR SOME OTHER APPROVED METHOD MAY BE USED.
  
 2) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER/AGENT.
  
 3) THE ENERGY CALCULATION FORM LISTS THE INSULATION FOR
 THE FLOOR OVER THE GARAGE AS R-21.0 AND THE SECTIONS ON
 SHEET A-6 SPECIFY R-11 BATT INSULATION. PLEASE CORRECT.
  
 4) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 ROOFING MATERIALS THAT WILL BE USED AS REQUIRED BY DCA
 RULE 9N-3.
  
 5) THE VALUE OF $23,000.00 SPECIFIED ON THE PERMIT
 APPLICATION IS TOO LOW FOR THE SCOPE OF WORK SHOWN ON
 THE PLANS. CITY AMENDMENTS 109.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-03-07 Cont ID  
Sent By rmcdouga Date 2014-03-07 Time 19:14 Rev Time 0.00
Received By rmcdouga Date 2014-03-07 Time 08:06 Sent To  
Notes
2014-03-07 18:19:392010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE. THE
 ELEVATION CERTIFICATE ON FILE FOR THE CONSTRUCTION OF
 THE SINGLE FAMILY DWELLING, PERMIT NUMBER 02100307,
 INDICATES THAT THE TOP OF THE LOWEST FLOOR IS 7.5'
 WHICH COMPLIES WITH THE CITY'S FLOOD ORDINANCE (6"
 ABOVE BFE).
  
 2) THE PLANS THAT WERE SUBMITTED ARE INCOMPLETE. THE
 STRUCTURAL SHEETS ARE NUMBERED S-6, S-7 AND S-8. SHEETS
 S-1 THRU S-5 ARE MISSING. SUBMIT TWO SETS OF ELEVATION
 DRAWINGS AND A SITE PLAN SHOWING THE LOCATION OF THE
 STRUCTURES ON THE LOT. CITY AMENDMENTS 107.2.1
  
  
 3) THE STRUCTURE IS LOCATED ON THE INTERCOASTAL
 WATERWAY MAKING IT EXPOSURE CATEGORY D. PLEASE CORRECT
 THE EXPOSURE CATEGORY AND THE WIND PRESSURES IN THE
 SCHEDULE ON SHEET S-6. FBC R301.2.1.4
  
 4) THE SCOPE OF WORK SHOWN ON THE PLANS IS NOT CLEAR.
 PLEASE PROVIDE A COMPLETE LIST OF THE WORK THAT IS TO
 BE DONE UNDER THIS PERMIT. CITY AMENDMENTS 107.2.1
  
 5) THERE ARE NOT AND GUARDS SHOWN ON THE DRAWINGS FOR
 THE STAIRS, THE WALKWAY OR THE ROOF DECK. SHOW
 COMPLIANCE WITH FBC R312.
  
 6) SHOW COMPLIANCE WITH FBC R311.7.7 FOR THE REQUIRED
 HANDRAILS.
  
 7) FROM THE INFORMATION PROVIDED ON SHEET S-6, IT
 APPEARS THAT NEW WINDOWS ARE BEING INSTALLED INTO NEW
 OPENINGS INTO THE GARAGE WALLS. PLEASE CLARIFY.
  
 8) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE NEW
 EXTERIOR DOOR WITH SIDELIGHT, THE ROOFING MATERIAL THAT
 WILL BE INSTALLED ON THE GARAGE ROOF DECK AND THE
 ELEVATED WALKWAY ( PLYWOOD), THE METAL CONNECTORS,
 ANCHORS AND HANGERS, THE NEW WINDOWS AND 8" STRUCTURAL
 LINTELS AS REQUIRED BY DCA RULE 9N-3.
  
 9) THE NEW WINDOWS WILL BE REQUIRED TO HAVE LARGE
 MISSILE IMPACT PROTECTION. FBCR 301.2.1.2 IF STORM
 PANELS ARE USED, SUBMIT TWO SETS OF PRODUCT APPROVALS
 FOR THEM. DCA RULE 9N-3
  
 10) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 PROJECT. CITY AMENDMENTS 107.3.4.1
  
 11) PROVIDE BUCK DETAILS FOR THE NEW DOOR AND WINDOW
 OPENINGS. FBCR612.10.2
  
 12) SUBMIT THE MANUFACTURER'S LOAD TABLES FOR THE 5-14"
 X 14" MICROLAM BEAMS. FBCR 301.1
  
 13) UPDATE THE ACI STANDARDS SPECIFIED ON SHEET S-8 TO
 THE 2008 EDITIONS. THIS IS THE EDITION THAT IS
 REFERENCED IN THE 2010 FBC. SEE CHAPTER 43.
  
 NOTE: IN ORDER TO SPEED REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS WAS ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2014-08-22 Cont ID  
Sent By dhayes Date 2014-08-22 Time 14:27 Rev Time 0.00
Received By dhayes Date 2014-08-22 Time 14:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-07-03 Cont ID  
Sent By ALBARRAN Date 2014-07-03 Time 10:49 Rev Time 0.00
Received By dhayes Date 2014-07-03 Time 10:49 Sent To  
Notes
2014-07-03 11:37:04DATE: 7/3/2014
 PROJECT:
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) THE SMOKE/CARBON MONOXIDE DETECTORS SHOWN ON THE
 LANDING APPEAR TO BE OUT IN THE OPEN. NOT ONLY ARE
 THESE DEVICES NOT LISTED FOR OUTDOOR USE, BUT THEY ARE
 NOT NEEDED.
 2) A CORRECTION/ADDITION TO "NOTE 8" TO INCLUDE THE NEC
 314.27 REQUIREMENT STATING THAT THESE BOXES SHALL BE
 LISTED TO SUPPORT 50#.
 3) ADDITIONAL OUTLETS REQUIRED IN THE BEDROOMS TO MEET
 THE SPACING CRITERIA OF NEC 210.52
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-05-21 Cont ID  
Sent By rmcdouga Date 2014-06-02 Time 11:20 Rev Time 0.00
Received By albarran Date 2014-05-21 Time 08:32 Sent To  
Notes
2014-05-21 10:14:57THE FOLLOWING DEFICIENCIES WERE NOTED ON THE SECOND
 REVIEW:
  
 1. THE SMOKE/CARBON MONOXIDE DETECTORS SHOWN ON THE
 LANDING APPEAR TO BE OUT IN THE OPEN. NOT ONLY ARE
 THESE DEVICES NOT LISTED FOR OUTDOOR USE, BUT THEY ARE
 NOT DESIGNED FOR THE PURPOSE.
 2. A CORRECTION/ADDITION TO "NOTE 8" TO INCLUDE THE NEC
 314.27 REQUIREMENT STATING THAT THESE BOXES SHALL BE
 LISTED TO SUPPORT 50#.
 3. THERE SHALL BE A CARBON MONOXIDE DETECTOR OUTSIDE OF
 THE SLEEPING OF THE ROOMS AND WITHIN 10' OF THE DOOR AS
 PER FBC-R 315.
 4. ADDITIONAL OUTLETS REQUIRED IN THE BEDROOMS TO MEET
 THE SPACING CRITERIA OF NEC 210.52.
 5. INDICATE ON THE PLANS THE ACTUAL LOCATION OF THE
 ELECTRICAL PANELS. THERE IS A CONFLICT BETWEEN THE
 LOCATIONS INDICATED ON PAGES A-0 & E-1.
 6. PROVIDE LOAD CALCS IN ACCORDANCE WITH NEC 220.83(B).
 7. PROVIDE AN ACCURATE AND SITE SPECIFIC ELECTRICAL
 RISER DIAGRAM AND PANEL SCHEDULE.
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-03-05 Cont ID  
Sent By albarran Date 2014-03-05 Time 09:30 Rev Time 0.00
Received By albarran Date 2014-03-05 Time 09:08 Sent To  
Notes
2014-03-05 09:33:48ELECTRICAL PLAN & PERMIT REQUIRED. IF THERE IS EXISTING
 ELECTRIC IN THE GARAGE BELOW, THERE SHALL BE A MINIMUM
 OF ONE ELECTRIC OUTLET ON THE DECK. FOR LIFE SAFETY,
 THE STAIRS LEADING TO THIS DECK SHALL BE PROPERLY
 ILLUMINATED AS WELL.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-05-07 Cont ID  
Sent By shill Date 2015-05-07 Time 16:59 Rev Time 0.00
Received By shill Date 2015-05-07 Time 16:57 Sent To  
Notes
2015-05-07 16:57:31****EXPEDITED****
 TO ZONING BOX
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-08-21 Cont ID  
Sent By rmcdouga Date 2014-08-22 Time 14:27 Rev Time 0.00
Received By dhayes Date 2014-07-15 Time 18:33 Sent To  
Notes
2014-07-15 18:34:03R26
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-03 Cont ID  
Sent By dhayes Date 2014-07-03 Time 10:50 Rev Time 0.00
Received By dhayes Date 2014-06-17 Time 13:52 Sent To  
Notes
2014-06-17 13:56:02R06

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-02 Cont ID  
Sent By rmcdouga Date 2014-06-02 Time 11:19 Rev Time 0.00
Received By rmcdouga Date 2014-05-20 Time 17:21 Sent To E
Notes
2014-05-20 17:21:50SENT MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-03-07 Cont ID  
Sent By rmcdouga Date 2014-03-07 Time 19:14 Rev Time 0.00
Received By rmcdouga Date 2014-01-21 Time 13:17 Sent To  
Notes
2014-01-23 13:17:52SENT TO R8 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2014-08-21 Cont ID  
Sent By rmcdouga Date 2014-08-21 Time 09:54 Rev Time 0.00
Received By rmcdouga Date 2014-08-21 Time 09:54 Sent To  
Notes
2014-08-21 09:53:44MU2014-18470
 NO IMPACT FEES WERE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-05-28 Cont ID  
Sent By rmcdouga Date 2014-05-28 Time 16:21 Rev Time 0.00
Received By rmcdouga Date 2014-05-28 Time 16:21 Sent To  
Notes
2014-05-28 16:29:05THE NEW PLANS THAT WERE SUBMITTED INDICATE THAT
 ADDITIONAL LIVING SPACE IS BEING ADDED. WHEN THE PLANS
 HAVE BEEN APPROVED, ONE SET IS TO BE SIGNED OUT AND
 TAKEN TO PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW.
 THE PLANS WITH THE PLAN REVIEW STAMP AND A COPY OF THE
 PAID IMPACT FEE RECIEPT CAN THEN BE RETURNED TO THE
 CITY BUILDING DEPARTMENT.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-03-07 Cont ID  
Sent By rmcdouga Date 2014-03-07 Time 16:49 Rev Time 0.00
Received By rmcdouga Date 2014-03-07 Time 16:49 Sent To  
Notes
2014-03-07 17:17:48NO HABITABLE SPACE IS BEING ADDED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-05-28 Cont ID  
Sent By rmcdouga Date 2014-05-28 Time 18:44 Rev Time 0.00
Received By rmcdouga Date 2014-05-28 Time 17:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-05-28 Cont ID  
Sent By rmcdouga Date 2014-05-28 Time 16:03 Rev Time 0.00
Received By rmcdouga Date 2014-05-28 Time 16:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2014-07-17 Cont ID  
Sent By dkittred Date 2014-07-17 Time 16:32 Rev Time 0.00
Received By dkittred Date 2014-07-17 Time 08:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2014-06-23 Cont ID  
Sent By DKITTRED Date 2014-06-23 Time 12:42 Rev Time 0.00
Received By dkittred Date 2014-06-23 Time 12:27 Sent To  
Notes
2014-06-23 13:03:36PLANNING AND ZONING COMMENTS: ***FAILED***
  
 6/23/14
  
 JUNE 17, 2014 RESUBMITTAL DID NOT ADDRESS ANY OF
 PLANNING AND ZONING'S PREVIOUS COMMENTS DATED 6/5/14.
 PLEASE ADDRESS PREVIOUS COMMENTS WHEN RESUBMITTING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2014-05-30 Cont ID  
Sent By dkittred Date 2014-05-30 Time 12:13 Rev Time 0.00
Received By dkittred Date 2014-05-29 Time 10:32 Sent To  
Notes
2014-06-05 17:07:486/5/14 NOTE TO FILE: CONNECTED BUILDINGS MEET MINIMUM 5
 FOOT SIDE SETBACK REQUIREMENT. A SETBACK THAT JOGS WITH
 THE BUILDING HAS BEEN APPROVED, PER AV, ALLOWING THE
 STRUCTURE TO MEET THE MINIMUM TOTAL SIDE SETBACK
 REQUIREMENT OF 15 FEET. DK
  
2014-06-05 14:47:49PLANNING AND ZONING COMMENTS: ***FAILED***
  
 REVISED COMMENTS 6/5/14
 [VOID COMMENTS - 5/30/14 (UPDATED 6/2/14)]
  
 REVISED PLANS CHANGED THE PROPOSED SCOPE OF WORK AND
 REQUIRED RE-REVIEW BY ZONING.
  
 1. DRAWINGS SHOW A CONNECTION BETWEEN THE ACCESSORY
 STRUCTURE AND PRINCIPAL STRUCTURE, HOWEVER, THIS IS NOT
 ILLUSTRATED ON THE SITE PLAN.
  
 2. ACCESSORY APARTMENTS ARE NOT PERMITTED IN THE SF7
 ZONING DISTRICT. PLEASE BE SURE ADDITION DOES NOT
 CONTAIN STOVE, FULL SIZE REFRIDGERATOR (UNDER
 COUNTER-STYLE REFRIGERATORS ARE PERMITTED), AND/OR
 DOUBLE STYLE SINK. FOR CLARIFICATION OF THE NEW
 ADDITION, PLANS SHOULD INDICATE THE SPACE WILL NOT BE
 USED AS AN ACCESSORY APARTMENT.
  
 3. VERIFY OVERALL HEIGHT OF HOUSE AS DEPICTED ON THE
 PLANS.
  
 4. PLAN INDICATES AN EXISTING RAILING AROUND THE TOP OF
 THE PRINCIPAL STRUCTURE. THE PERMIT TO INSTALL THIS
 RAILING AND ROOF IMPROVEMENTS (PERMIT NO. 13010304) HAS
 EXPIRED. PLEASE NOTE, PER THE BUILDING DIVISION, ONLY A
 104 FINAL INSPECTION LEFT. - "THEY WILL HAVE TO APPLY
 FOR A REISSUE, BUT THEY DON'T NEED A CONTRACTOR, AND
 THE FEE WILL BE $80. THE PERMIT WILL BE ISSUED AT THE
 FRONT COUNTER IMMEDIATELY AND THE INSPECTION CAN BE
 SCHEDULED FOR THE NEXT BUSINESS DAY."
  
 ADDITIONAL COMMENTS MAY BE GENERATED BASED ON ANY
 ALTERATIONS MADE TO THE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
2014-05-30 12:12:21PLANNING AND ZONING COMMENTS: ***FAILED***
  
 5/30/14 (UPDATED 6/2/14)
  
 REVISED PLANS CHANGED THE PROPOSED SCOPE OF WORK AND
 REQUIRED RE-REVIEW BY ZONING.
  
 1. THE MAXIMUM SQUARE FOOTAGE OF TOTAL FLOOR AREA OF
 ALL ROOFED ACCESSORY BUILDINGS ON A PROPERTY SHALL NOT
 EXCEED 75 PERCENT OF THE GROSS FLOOR AREA OF THE
 PRIMARY STRUCTURE WITH A MAXIMUM FLOOR AREA OF 1,000
 SQUARE FEET [ZLDR SEC. 94-304(B)(1)]. THE EXPANSION OF
 THE EXISTING ACCESSORY STRUCTURE INCREASES THE TOTAL
 SQUARE FOOTAGE OF THE ACCESSORY STRUCTURE TO OVER 2,000
 SQUARE FEET AND IS NOT PERMITTED.
  
 2. DRAWINGS SHOW A CONNECTION BETWEEN THE ACCESSORY
 STRUCTURE AND PRINCIPAL STRUCTURE, HOWEVER, THIS IS NOT
 ILLUSTRATED ON THE SITE PLAN. BY CONNECTING THE TWO
 BUILDINGS WITH ANYTHING OTHER THAN A CANVAS AWNING ON
 THE GROUND LEVEL IS CONSIDERED ATTACHING THE BUIDLINGS
 AND THE WHOLE STRUCTURE MUST THEN COMPLY WITH PRINCIPAL
 STRUCTURE SETBACKS OF THE SF7 ZONING DISTRICTED. BASED
 ON THE SITE DIMENSIONS PROVIDED ONTHE SITE PLAN, THE
 STRUCTURES COULD NOT BE ATTACHED AND MEET THE PRINCIPAL
 STRUCTURE SETBACKS.
  
 3. OTHER ZONING CONSIDERATIONS IF MODFICATIONS ARE
 RESUBMITTED:
  
 A. PLEASE BE SURE ANY CHANGES TO THE PLANS ARE
 REFLECTED ACCURATELY ON THE SITE PLAN.
  
 B. ACCESSORY APARTMENTS ARE NOT PERMITTED IN THE SF7
 ZONING DISTRICT.
  
 C. VERIFY OVERALL HEIGHT OF HOUSE AS DEPICTED ON THE
 PLANS. STRUCTURE APPEARS TO BE HIGHER THAN WHAT WOULD
 HAVE ORIGINALLY BEEN PERMITTED.
  
 D. PLAN INDICATES AN EXISTING RAILING AROUND THE TOP OF
 THE PRINCIPAL STRUCTURE. THE PERMIT TO INSTALL THIS
 RAILING AND ROOF IMPROVEMENTS (PERMIT NO. 13010304) HAS
 EXPIRED. PLEASE NOTE, PER THE BUILDING DIVISION, ONLY A
 104 FINAL INSPECTION LEFT. - "THEY WILL HAVE TO APPLY
 FOR A REISSUE, BUT THEY DON'T NEED A CONTRACTOR, AND
 THE FEE WILL BE $80. THE PERMIT WILL BE ISSUED AT THE
 FRONT COUNTER IMMEDIATELY AND THE INSPECTION CAN BE
 SCHEDULED FOR THE NEXT BUSINESS DAY."
  
 ADDITIONAL COMMENTS MAY BE GENERATED BASED ON ANY
 ALTERATIONS MADE TO THE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-01-27 Cont ID  
Sent By dkittred Date 2014-01-27 Time 17:22 Rev Time 0.00
Received By dkittred Date 2014-01-27 Time 15:25 Sent To  
Notes
2014-01-27 17:29:331/27/14 - SENT BACK TO R08. DK
  
2014-01-27 17:28:041/27/14 - IMPROVEMENTS DO NOT EXCEED 30' AND WALKWAY
 DOES NOT EXTEND PASSED EXISTING BUILDING SETBACKS. DK
2014-01-27 14:37:451/27/14